| 1 | Earthwork in excavation of foundation in hard soil including dressing & levelling of bed within initial lead of 50mt. & lift of 1.5mtr etc complete as per the direction of the Engineer-incharge. |
| 2 | Filling in foundation & plinth with sand including watering & ramming etc complete as per the direction of the Engineer-incharge. |
| 3 | Cement concrete (1:4:8) with 4cm size h.g.c.b. metal of approved quality from approved quarry with ramming watering and curring etc. complete including cost, taxes, royalty convence charge of all material to worksite, supply of cement T&P required etc. complete as per the direction of the Engineer-incharge. |
| 4 | Fly Ash Brick masonry 25cm x 12cm x 8cm size having crushing strength not less than 75kg / cm2 with dimensional tolerrance + 8% in cement mortar (1:6) in foundation & plinth etc. complete as per the Engineer-incharge. |
| 5 | Reinforced Cement Concrete (1:2:4) with 12cm size h.g.c.b. Chips of approved quality from approved quarry with ramming watering and curring etc. complete including cost, taxes, royalty convence charge of all material to worksite, supply of cement T&P required etc. co |
| 6 | Filling the foundation and plinth with excavated material as directed by the Engineer-incharge. |
| 7 | 12mm cement plaster in cement mortar (1:6) finished smooth to brick work after racking out joints including waterring and curring with cost, taxes, royalty and conveyance charges of all material to the worksite and supply of all labour and T&P required for the work etc complete as directed by the Engineer-incharge. |
| 8 | Rigid smooth centering & shuttering for R.C.C. works including false work & dismateling then after including cost of materials in ground floor complete as directed by the Engineer-incharge. |
| 9 | M.S. reinforcement for R.C.C. work including supplying, cutting, bending, binding & tying the grills & placing in position including cost of binding wire 18 to 20 guage per Qntl. Including cost of HYSD Still Bar (FE 415/ FE 500) |
| 10 | Cost of Iron Door of size (1.2m x 1.98m) and grill for ventilator |
| 11 | Dry Brick Khoa of 10cm thick |
| 12 | 2.5cm A.S.Flooring in CC (1:2:4) including punning with 12mm HG Chips |
| 13 | Priming of M.S.Door with approved primer |
| 14 | Painting of 2 coats with approved shade of paint including cost, labour etc complete |
| 15 | White/Colour washing 2 coats with shell lime over 2 coat white washing. |
| 16 | 2.5 cm thick grading concrete (1:2:4) on roof slab with 6 mm size hard granite chips with curring. |
| 17 | Cost of laying & fittings of M.S./PVC Tee along PVC pipeline |
| 18 | Labour charges for letter writting on display board in black colour on yellow back ground painting including cost of material, labour etc. |
| 19 | 7.5 HP Submersible motor pump of 25 mtr head with 900 LPM discharge of reputed brand with BEE Star rated energy efficiency suitable for 200 mm dia tube well as per IS specification with 2 pair U-Clamp & 30 mtr of 4.00 sqmm flat cable andImpeller: Bronze grade LTB-2 of IS 318/1981 as per IS specification |
| 20 | Cost of 63 Amp. Main Switch Triple pole & natural of voltage range 440 volt of re-wirable fuse and shall confirming to IS-4064(PT-I & II ) with ISI markincluding all taxes etc. |
| 21 | 3x10 sqmm PVC insulated (HD) tropoder armoured Electric Cable with alluminum conductor for use in 3 phase power system of working voltage upto & including 1100 volts at 50Hz confirming to IS 7098(Pt-II) including cost of transportation to site and laying below 0.9mtr of the ground and filling the excavated materials including watering and rammin including all taxed etc. |
| 22 | 2.50mm2 Submerssible (3 Core) Flat Cable ISI mark of reputed company. |
| 23 | Electrical Earthing including all materials as per the direction of the Engineer- incharge |
| 24 | Electrical installation and energisation (including cost of volt meter-5 nos, CT type Amp. Meter-5 nos, selector switch- 5 nos, CT - 2 nos(100:5), indicator - 15 nos,100 Amp Kit kat - 15 nos, cable socket, internal and external wiring at pump chamber etc. |
| 25 | T&P materials kit comprising of Electric currentTester, Screw Driver,DE Spanner, Plier and Ring Spanner all suitable for maintainance of LIP etc. complete. |
| 26 | 100mm dia nominal bore G.I.pipe having wall thickness 4.5mm electrical resistance welded of medium class confirming to IS- 1239(part-1/2004) with latest ammendments, screwed at both ends as per IS-554 with socketed at one end and the other end protected with plastic threaded protector including its transportation and unloading at L.I.P. site. The socket confirming to ISI 1239(part II/1992) with latest ammendments in random length of 4 to 7 mtr. Each pipe should bear IS certification and manufacturers name/trade mark. |
| 27 | 100mm dia G.I.Socket( Medium Duty) with ISI mark of reputed company. |
| 28 | 200X100mm dia M.S.T/W Cap with ISI mark of reputed company. |
| 29 | M.ST/W Clamp (Pair) 100mm dia with ISI mark of reputed company. |
| 30 | Cost of 12mm dia PVC Insulated Steel Wire Rope ISI mark of reputed Company. |
| 31 | 100mm dia G.I.Bend( Medium Duty) conforming to IS No-1239 (part II/1992) with ISI mark of reputed company. |
| 32 | 100mm dia G.I.Flange( Medium Duty) conforming to IS No-6392/1971 with ISI mark of reputed company. |
| 33 | 100mm dia C.I.Double Flanged Non Return Valve swing type PN-1.0 (IS-5312(Part-I-2004) with bypass arrangement with ISI mark of reputed company. |
| 34 | Nuts and Bolts |
| 35 | Thick Rubber Insertion 3mm thick |
| 36 | Labour charges for Installation of pumpset and delivery fitting including fitting of Sluice Valve, NR Valve, Air Release Valve, PVC Tee and lowering of pump and transportation etc complete. & fixing suction and delivery pipe to motor, NR Valve, Foot Valve, Sluice Valve and other fitting materials including cutting, welding etc. complete as per the direction of the Engineer-incharge. |
| 37 | 50mm dia C.I.Air Release Valve (single action) with saddle and Raiser pipe conforming to IS 14845 (SI) with ISI mark from reputed company. |
| 38 | Solvent cement of approved quality for jointing of PVC Pipes with all cost and taxes etc |
| 39 | Supply of 160mm dia unplasticised riged UPVCpipe ivory in colour having specific gravity of 1.40 to1.46 gms/cc of straight length of 6(six) meter for portable water supplies conforming to IS-4985/2000 of BIS-Amendment-2 read with Table-1 of IS-specification bearingISImarks for working pressure CI-I UPVC pipe to withstand pressure of 2.5kgf/sqcm& the specification and manufacture name should be prominently marked on body of each pipe as per the latest Amendment of IS-4985. It includes the cost of sockets in case of plain ended pipe. PDI test are to be condcuted and should be marked on body of each pipe and report is to be obtained from CIPET, Bhubaneswar necessary approval of authority including transporation to work site in complete shape and handed over to Pani Panchayat President or Secretary. |
| 40 | Fitting of un-plasticised 160mm diaPVC Pipe for following inside dia mtr. for all classes of pipe including jointing the pipe with solvent cement by non-head application method including fitting and fixing of required no. of PVC Tee for outlet and PVC Shaddle and PVC Riser nipple for fitting air valve, equal Tee etc. complete including conveyance pipe from village to worksite and testing of pipe line etc. complete as per the direction of the Engineer-incharge. |
| 41 | 160mmx160mmx110mm dia Weldless G.I.Tee (3.6mm thickness) with bend, closing and opening arrangement of reputed company. |
| 42 | 150mm diaC.I. Butter Fly Valve BS:5155/15: 13095-CI MOC Lever Operated PN-1.0 with ISI mark of reputed company. |
| 43 | 160 mm F P.V.C End Cap (W.P-10 Kg/cm2) conforming to IS-4995/ 1988 with latest amendment. |
| 44 | Fabrication of special joint including cutting , welding of pipes one end with other end suitable for connection to delivery pipe line of pump set including cost of cutting, welding, welding materials, fitting in proper place. |
| 45 | Construction of 3 phase 11 KV HT line as per REC standard confirming to IE Rules 1956 with 300 kg 9 M long PSC Pole with 55 Sqmm AAA Conductoraverage span 40mtr ,11 KV \"V\" Cross arm required No.of 11 KV T & C Disc. polymer Insulators in tension point &11 KV Pin Polymer insulators, Couping & Padding of Poles with all G.I.Channels. Danger Board at each Pole, Anti Climbing Devices, Stay Set at Bending point & double stay at end point with 18 mm G.I.H.T.Stay, concreting of Stay with Anchor plate, guarding at Road crossings etc if required. including cost of all materials, labour, transportation,inspection & commissioning etc. complete. |
| 46 | Construction anderection of 11 /0.4 KV ,25 KVA Double Pole mounted Substation with5mtrx3mtrx1.5mtr height mesonary toe wall /G.I. Flat fencing boundary wall withFlat with Polymer insulator ,L.T DistBox with MCCB , Aluminim bus bar of single bay with kitkat fuse , sand filling and metal spearding with M.S.Grill gate ,all Channel matrials should be G.I , 7 Nos earthing with chamber with 3mtr G.I pipe of40mm dia with connecting of 25mmx 5mm G.I flat to all earthing including 25KVA BIS Leble-II Star rated Transformer confirming to RE Rules 1956, mounted on 2.44 Mtr. Long structure, supported in 300 kg 9 mtr long PSC pole,transformer hard channel & top channel made of 2.8 M long 100 X 50 X 6 mm G.I.Channel, Transformer belting on 2.80 M long 50mm X 50mm X 5 mm G.I.Angle, (all REC SPN Std.F-3) with all accessories like 3 pole 11 KV HG Fuse(F-5)& A.B.Switches(F-9) both mounted on 2.8 M long 75mm X 40mm X 6 mm G.I.Channel and supported by 1.0 M long 50 X 50 X 5 mm G.I.Angle, with 3 No. 11 KV Lightening Arrestors and Danger board at each Pole, Anti climbing Devices & all other necessary fittings i.e required size Nuts & Bolts, Brackets, Cable, Cable Sockets as per TPCOCL specification etc. including cost of all materials, labour , transportation complete with liasioning for testing inspection & commissioning as per specification of TPCODL etc complete. |