Tender For Repair / Maintenance And Rewinding Of Ceiling Fans, Exhaust Fans, Wall Mounted Fans, Flame Proof Exhaust Fans, Air Circulators Fans, Pedestal Fans And Allied Works In Tech And Domestic Area And Repair / Maintenance Of Lt Oh/Ug Feeder, Pane, kalaikunda-West Bengal

Military Engineer Services-MES has published Tender For Repair / Maintenance And Rewinding Of Ceiling Fans, Exhaust Fans, Wall Mounted Fans, Flame Proof Exhaust Fans, Air Circulators Fans, Pedestal Fans And Allied Works In Tech And Domestic Area And Repair / Maintenance Of Lt Oh/Ug Feeder, Pane. Submission Date for this Tender is 11-10-2023. Electrical Maintenance Tenders in kalaikunda West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

39509370
Corrigendum : Tender For Repair / Maintenance And Rewinding Of Ceiling Fans, Exhaust Fans, Wall Mounted Fans, Flame Proof Exhaust Fans, Air Circulators Fans, Pedestal Fans And Allied Works In Tech And Domestic Area And Repair / Maintenance Of Lt Oh/Ug Feeder, Pane
Open Tender
Indian
West Bengal
kalaikunda
11-10-2023

Tender Details

Repair / Maintenance And Rewinding Of Ceiling Fans, Exhaust Fans, Wall Mounted Fans, Flame Proof Exhaust Fans, Air Circulators Fans, Pedestal Fans And Allied Works In Tech And Domestic Area And Repair / Maintenance Of Lt Oh / Ug Feeder, Panel Board And

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 20-Sep-2023 EXTENSION OF DATE Date 04-10-2023
2 27-Sep-2023 AMENDMENT IN TENDER DOCUMENTS Financial Bid 04-10-2023
3 27-Sep-2023 REVISED BOQ BOQ 04-10-2023
4 04-Oct-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 11-10-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 79000.0 /-
Tender Value
INR 34.50 Lakhs /-

BOQ Items

Name of Work : REPAIR/MAINTENANCE AND REWINDING OF CEILING FANS, EXHAUST FANS, WALL MOUNTED FANS, FLAME PROOF EXHAUST FANS, AIR CIRCULATORS FANS, PEDESTAL FANS AND ALLIED WORKS IN TECH AND DOMESTIC AREAAND REPAIR/MAINTENANCE OF LT OH/UG FEEDER, PANEL BOARD AND VOLTAGE STABILIZER IN TECH AREA AT AIR FORCE STATION KALAIKUNDAAND DDK RANGE UNDER GE (AF) KALAIKUNDA.
Sl. No. Item Description
1Taking down oldceiling fan/Exhaust fans/Wall mounting fans/ Air cirulators fan of any capacity/sweep after disconnecting the electric supplyfromany site, checking for its electrical defect and opening fans for checking of mechanical defect afterdismantling of fan, carry out repair/over hauling including removing dust and grease, and cleaning of internal mechanical parts of fan with lubricant as per OEMs specification, checking of alignment of shaft, oiling and greasing, checking of worn out bearing and other defective parts,winding, condenser etc and re-assembling, and connecting/refixing of fans in its original position , replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, by providing newGI nut bolt, lock washer and lock/split pin complete all as specified and directed by Engr-in-charge. complete all as specified and directed. NOTE:(i) Rewinding and replacement of defective parts, Painting etc shall be measured and paid seperately.
2Supply only the following items as per OEMs specifications, complete. for fixing against defective parts of fan taking down under item No 1 here in before complete all as specified and directed by Engr-in-charge.
3(a) Bearing No 6201 Make :SKF/NBC/FAG
4(b) Bearing No 6202Make :SKF/NBC/FAG
5(c) Bearing No 6203Make :SKF/NBC/FAG
6(d) Bearing No 6204Make :SKF/NBC/FAG
7(e) Rubber Bushas per OEM specificationsuitable for ceiling fan
8Capacitors for electric fan motors, 2.5 mfd, 440 Vconforming to IS:1709 (Cat No. QHPCWC5002X5 of Make Havells or equivalent Model of Make UNIVERSAL/EPCOS)
9Capacitors for electric fan motors, 4.00 mfd, 440 Vconforming to IS:1709 (Cat No. QHPCWC5004X0 of Make Havells or equivalent Model of Make UNIVERSAL/EPCOS)
10Capacitors for electric fan motors, 6.00 mfd, 440 Vconforming to IS:1709Havells / of Make UNIVERSAL/EPCOS)
11(j) Lathe work of Fan shaft any type / size.
12M&L for Earthing complete with Galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground with earth pit not less than 3.25 meter deep below ground level with top edge of plate not less than 2.5 meter below normal ground level connected to galvanised iron strip 32x6 mm as earth lead strip by means of nuts, bolts, check nuts, washers of galvanized iron as steel all as shown electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion, surrounded from all sides by mixture of charcoal and common salt and elctrode by means of steel and GI pipe light grade 20mm bore dia bore for watering funnel with wire mesh,CI cover with frame , PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified. NOTE : 1. The unit rare includes for protectionh GI pipe of 40mm and watering pipe of 20mm bore including excavation for earth pit in any type of soil/disintegrate rock. 2. Contractor has to bring agriculture soil from outside of defence land and fill in earth pit to acheive desired result as the soil resisitivity is very high. 3. The cost of GI strip of 32x6 from top of earth plate upto 7.5 meter above ground level is deemed to be included in the unit rate. 4. All the joints in GI strip and connectgion with earth plate to be welded through brazing and in addition by providing double brass nut bolt and washer. 5.Costing of welding and nut bolts are deemed to be included in the unit rate
13M&L for Rewinding ofceiling fan of sweep 1200 mmany make any model including taking down ,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
14M&L for Rewinding ofceiling fan of sweep 1400 mmany make any model including taking down ,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
15M&L for Rewinding of Exhaust fan of 450 mm any make any model, 1400 rpm including taking down ,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.
16M&L for Rewinding of Exhaust fan of 380 mm any make any model, 1400 rpm including,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
17M&L for Rewinding ofExhaust fan/ fresh air fanupto 300 mm any make any model including,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
18M&L for Rewinding ofwall mounted fan 400 mm sweepany make any model including,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
19M&L for Rewinding ofPedestal fan 400 mm sweepany make any model including,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:-(i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
20M&L for Rewinding ofFlame proof Exhaust fan upto 450 mm any make any model including ,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
21M&L for Rewinding of Industrial Air circulator fan of any make any model and sweep with including ,dismantaling of parts, removing burnt out windings with insulating materials,cleaning throughly internally and externally, rewinding fan motor with super enamelled copper wires of existing size including provision of all insulating materials and varnishing, lubrication of bearing / bushes using fresh lubricant all as per OEMs reccommendations, replacement of defective parts,re-assembling, hanging in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Spare parts for replacement will be deemed to be included in Quoated rates.(ii) Repairs shall be carried out through authorised Vender as approved by GE.
22S & F hot rolled medium and high tensile structural steel of grade E165 as per IS 15911: 2010 as in bands, straps, supports or stays for rainwater, ventilating pipes, including bolts, if required: hooks (stay), heavy, for large gates; hook and pintle hinges: large hasps and staples; chains; hand made sliding bolts; clamps; hold fasts; wall ties; hooks for hanging fans; plain angle cleats for securing purlins to wood trusses or rafters; knee piece inserts; two way and three way straps, plate washers and similar small articles complete all as specified and as directed.
23Materials and labour for painting of ceiling fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc. including writing letters or figures (Block,Roman, Italic or Indian) n exc. 2.5 cm high and stops, commas, short lines, dashes,hyphens, brackets, etc. for writing MES/SM No., complete all as specified and directed.
24Materials and labour for painting of Pedestal fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc. including writing letters or figures (Block,Roman, Italic or Indian) n exc. 2.5 cm high and stops, commas, short lines, dashes,hyphens, brackets, etc. for writing MES/SM No., complete all as specified and directed.
25Materials and labour for painting of exhaust fans complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc. including writing letters or figures (Block,Roman, Italic or Indian) n exc. 2.5 cm high and stops, commas, short lines, dashes,hyphens, brackets, etc. for writing MES/SM No., complete all as specified and directed.
26Supply and fixing "U" clamp for hanging ceiling fan in ceiling to be fixed with 3" long anchor fastener 3 Nos for each clamps as per OEMs specifications complete all as specified and directed by Engr-in-Charge.
27Supply and Fixing ceilling Fan down rod heavy dutyas per existing dia andlength of 50 cm including brass nut bolts, double waher, rubber bush heavy duty andspilit pin washers etc as per OEMs specifications complete all as specified and directed by Engr-in-charge.
28Supply and fixingaluminium blade assy of celling fan of 1200 mm sweep (set of three)in replacement of make and colour as existing as per OEMs specificationsas specified and directed by Engr- in - charge.
29Taking down carefully, existing defective storage type water heater (geyser) of any Capacity and Make for repairing, includingreplacement of defective spares as required and including replacement of terminals with defective connection wires and reinstallation of the geyser in original position including testing and commissioning, complete all as specified and directed. NOTES:- (i) Repairs shall be carried out through authorised Vender as approved by GE. (ii) Spares for replacement will be measured and paid separately under respective items in S&F .
30Supply and fixing the following spares of geyser in repair and testingsuitable for storage type water heaters (Geyser) as per OEMs specifications, complete.
31Thermostat, stem type, adjustable upto 75 Degree Celcius, ISI Marked (IS 3017).
32Heating element 1.5 KW, ISI marked as per existingMake : Bajaj / Usha/Theta
33Heating element2 KW,ISI marked as per existing Make : Bajaj / Usha/Theta
34Glass Incandescent Electric Water Heater Indicator Lamp, in multi-color caps. with including flexibe copper wire of suitable sizeRed/Green
35PVC Connection with steel reinforced pipe for hot water connectionof Size 18" x 1/2" including rubber washers.
36Copper Apperture plate suitable for 25/50 ltrs geyser along with rubber gasket, nuts, bolts,etc complete.
37S&F in repairs Heating element 1.5 KW,ISI marked as per existing type Make : Bajaj / Usha/Theta/ Haveels/ Crompton as per OEMs specifications, complete.(Note heating element replaced without taking down of geysers and other than in item No. ) is measured under this item.
38S&F in repairs Heating element 2.0 KW,ISI marked as per existing type Make : Bajaj / Usha/Theta/ Haveels/ Crompton as per OEMs specifications, complete. (Note heating element replaced without taking down of geysers and other than in item No. ) is measured under this item.
39Supply and replacement of3-Pin plug top 16 Amps. (Code No.39582 of Make Anchor or equivalent ofMake Kinjal/Maru).
40Supply and fixing 2 feet long hot/cold water PVC connection pipe, heavy duty, braided PVC pipe and the connector nuts coated with stainless steel, including rubber washer complete suitable for 50/25 ltrs geyser all as specified and directed including taking out old unserviceable pipe as per OEMs specifications, complete
41M&L for complete servicing of solar hot water system (solar water heater, flate plate collector type), with cleaning of sluge deposited in pipe line of solar pannel by using cleaning regent, check and repair of pipe line for any leakage, including carring outbrazing of copper pipe for leakage, cleaning of glass shell, cleaning of hot water tank, replacement of u/s clamps, adopter, hose pipeincluding filling of distilledwater and coolent in reservior including complete sevicing to keep the plant functional of capacity up to 200 LPD. NOTES:- (i)Servicingshall be carried out through authorised technicians of the OEMs as approved by GE.
42M&L in repairfor replacement of thermostate, long body, ISI marked of solar water heater of cap up to 200 LPD as per OEMs specifications, complete
43M&L in repairfor replacement of electrical heating element of 2.0 KW (long thread type, as per existing), ISI marked,of solar water heater of cap up to 200 LPD as per OEMs specifications, complete. Make: Solar Element or equivelent as approved by GE.
44M&L for replacement in repair hot water pipe insulation with glass wool and aluminium cladding 20 mm bore including all material as required as per OEMs specifications, complete directed by EIC.
45S&F LED 20 Watt tube light fittingintregatedtype, includingLED retrofit tubelamp 20 W , LED tube light nominal power 20 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 2100, lumen efficacy of minimum 100 lumens per watt, , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 2.5 KV, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 20%, CW available CCT of 6500K, power factor of minimum 0.95 extruded aluminium LED battenslife span of minimum 50000 working hours as per catalogue No Make :- Bajaj (Batten Cat No. BCLAB 20W LED Pbatten and tube suitable for 18/20 watt retofit LED tube single side connection type). LED or equivalent in Wipro/Philips/Surya as approved by GEcomplete fittingincluding connecting with PVC insulated multistranded copper flexible cable 1.0 sqmm three core, and PVC round/ square box white colour x 2 Nos for mounting of fittingincluding taking down old unserviceable complete all as specified & directed..
46S & F in repairLEDbulkhead light with pressure die-cast housinglight fittings nominal power 10/12 watt LED of Make Osram; bridge lux; Philips; Nicha; Cree;LED wattage of minimum 3 watt each and Maximum 5 watt each, operational voltage of 170 volts to 270 volts. frequency of 50 Hz, lumen output of minimum 1100, lumen , , integrated electronic driver (SMP based constant current supply) with output short circuit protection and surge protection upto 3 KV, protection grade IP 65, CRI greater than 80%,THD below or less than 15%, CW available CCT of 6500K, power factor of minimum 0.95 polycarbonate housing with aluminium, life span of minimum 50000 working hourscomplete all as specified and as directed.
47Supply and fixing in repairModular electronic fan regulator 2 module , 100 watt flush type , (deluxe) on the existing hylam laminated sheet etc as required complete all as specified and directedake: Anchor (Deluxe /Code:-14502) / L&T/ Havells
48Supply and fixing in repair electronic fan regulator 1 module (mini) 100 watt flush type ,on the existing hylem laminated sheet etc as required complete all as specified and directed. Make: Anchor roma (Code:-289510) / L&T/ Havells
49S&F in repairof stepped type electronic fan regulator 100 watt flush type (delux) on the existing hylem laminated sheet etc as requiredcomplete all as specified and directed by EIC.
50S&Fin repair Polycarbonate angular lamp holder with back plate, suitable for LED Lamp fittings including taking out old u/s complete all as specified and directed by EIC
51Supply and Fix in repairs, decorative wall light fixture Decorative, wall mounting, brushed nickel finish fixture with Opal Glass diffuser suitable with 9 W LEDlamp B22 base.(Spiral B-22 base) complete all as specified and directed. [Model .LHFOAJE1TN1I060for light fittingand lamp Make "Havells" or equivalent Model of Make "Philips"/ "Bajaj/GE/Surya"]
52S & F LED downlight recess round shape nominal power 12 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; bridge lux, LED wattage of minimum 3 watt each and Maximum 5 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 1200, lumen efficacy of minimum 100 lumens per watt, isolated electronic LED driver (SMPS based constant current supply) with output short circuit protection, surge voltage protection upto 2 KVs, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 15%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die cast aluminium housing and ring, life span of minimum 50000 working hours complete all as specified and as directed.Make : :Make Bajaj/Philips/CK Birla Group (Orient Electric)/Surya
53S & F LED downlight recess round shape nominal power 3 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; bridge lux, LED wattage of minimum 3 watt each and Maximum 5 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 360, lumen efficacy of minimum 120 lumens per watt, isolated electronic LED driver (SMPS based constant current supply) with output short circuit protection, surge voltage protection upto 2 KVs, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, THD below or less than 15%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die cast aluminium housing and ring, life span of minimum 50000 working hours complete all as specified and as directed.Make : :Make Bajaj/Philips/CK Birla Group (Orient Electric)/Surya
54Taking down existing panel light fitting any type (300 mm x 300 mm) recess mounting/surface and S&F LED light fitting 18 watt recess mounting of size 300 mm x 300 mm ,LED of Make Osram; Everlight; Philips; Nicha; Cree; bridge lux , LED wattage of minimum 3 watt each and Maximum 5 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, , lumen efficacy of minimum 115 lumens per watt, isolated electronic LED driver (SMPS based constant current supply) with output short circuit protection, over voltage protection, surge voltage protection upto 2 KVs, protection grade IP 20, CRI greater than 80%, bema angle of 1200 clear, ITHD below or less than 15%, CW available CCT of 5700K, power factor of minimum 0.95, CRCA powder coated white after phosphochromate treatment housing, life span of minimum 50000 working hours including making electric connection from source with PVC sheathed copper conductor wire of 1.5 Sqmmx 3 core complete all as specified and directed by EIC. Make Bajaj/Philips/CK Birla Group (Orient Electric)/Surya
55Taking down carefully copper/ aluminium submain wirings of any size (2 runs single core including earth continuity) complete including PVC casing capping/ PVC conduit/Steel Conduit with fittings etc, removing materials from site and making good disturbed surfaces of walls, floors etc., complete all as specified and directed.
56M&L for Sub main wiringwith two single core PVC insulated unsheathed cable 1100 volts grade, 6.0 Sqmm size with multistranded copper conductor FRLSH cable as per IS 694: 2010(with colour code), drawn in but including PVC casing capping not less than 25 mm ISI marked includingall accessories ofcasing caping as approved by EIC, including PVC insulated unsheathed 6.0 Sqmm cable with multistranded copper conductor green PVC insulated as contineous earth conductor cable connected to earth dolly complete all as specified and directed.
57Supply and fixing in repairs wall mounted bed side study lamp aluminium body, 3W LED type warm white including LED driver with on /off button switch ,flexible pipe with lamp head 360 degree rotating type, 220 Volts complete all as specified and directed by Engr- in- charge. Make :BAJAJ or equivalent of make JAQUAR/CG/Wipro.
58S & Fin repair LED street lights nominal power 25 Watt, LED of Make Osram; Everlight; Philips; Nicha; Cree; Samsung, LED wattage of minimum 1 watt each and Maximum 3 watt each, operational voltage of 170 volts to 270 volts, frequency of 50 Hz, lumen output of minimum 3000, lumen efficacy of minimum 120 lumens per watt, built-in integrated electronic LED driver, output open /short circuit protection, phase to phase protection, over voltage protection, surge voltage protection upto 4 KVs, protection grade IP 66, CRI greater than 80%, CW available CCT of 5700K, power factor of minimum 0.95, pressure die-cast aluminium alloy housing with epoxy powder coated metallic silver finish after phosphochromate treatment, life span of minimum 50000 working hours as per catalogue No.Bajaj Cat Part No. BCLST25 W LED IV2 or equivalent of Make mentioned under Appendix "B" including fixing at any height and including wiring using three core PVC insulated, PVC sheathed, flexible stranded copper conductor FR-LSH cables suitable for outdoor use, 1.5 sqmm as per IS 694: 2010 complete all as specified and as directed.
59Supply and fixing in repair PVC insulated multistranded Copper conductor, sheathed round cable ISI marked 1.5 sqmm x 3 corecomplete all as specified and directed by Engr-in-charge. Make :Havells Cat No.WHMFDSKB31X5 or equivalent of make as per PS
60S&F for earth continuity conductor or main earthing lead of 4 mm GI wire laid in pipe/ fixed to wall on batton or recess or chases or buried in ground or drawn in conduit / pipe or any other indicated situation for loop earthing etcincluding jointing by using suitable size lugs, GI nuts, bolts and washer including taking down old unservieable complete all as specified and directed by Engr- In- charge
61Taking down old unserviceable GI/Copper earth plate including all acessories complete from soft and hard soil from any location as directed byEngineer -in- charge.
62S&F in repair Surge protection device Type 1 + 2 to withstand implus current with 10/350 us wave to simulate lightining current. SPD having max contionous operating voltage -440 Uc (v), I imp in KA(10/350 Us wave) - 12.5 KA , I max in KA(8/32 Us wave) - 80 KA,Pole 3+1 (3 Pole + Neutral),4 module including installation inparallel connection in DBand making all electrical connections with4 x 6.0 Sqmm single core copper wire with copper lugs complete all as specified and directed by Engineer in charge. Make ABB cat Part No. OVR T1-T2 3N 12.5-440s P QS (2CTBB15710R4800) or equivalent in Havells/ Hager.
63S&F in repairs 15 mm nominal size, nonrising spindle type fancy bib taps as per IS 8931: 1993 made of cast brass including Knob, knob components, divertor & components, nickel-chromium plated finish complete all as specified and as directed.
64S&F in repairs 15 mm nominal size, nonrising spindle type fancy stop valves as per IS 8931: 1993 made of cast brass including Knob, knob components, divertor & components, nickel-chromium plated finish complete all as specified and as directed.
65S&F in repairplug top metal body suitable for single phase 240V,IP44 ,20A 2P with Earth Make :Hager cat no:VZ1311or equivalent of make:Legrand/ABB
66S & F circuit breakers (MCB), single pole (SP), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 6A to 32 A, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.Make- Legrand/ Seimens/ Schinder/Hager
67Materials and labour for painting of geyser up to capacity 50 ltrs complete, in situ with synthetic enamel paint by spraying including filling cavities with filler, one coat after cleaning all dust etc. including writing letters or figures (Block,Roman, Italic or Indian) n exc. 2.5 cm high and stops, commas, short lines, dashes,hyphens, brackets, etc. for writing MES/SM No., complete all as specified and directed.
68Taking up or down 15 mm bore of steel tubing and connections, including cleaning for refixing or removal to store complete all as specified.
69Taking up or down 20 mm bore of steel tubing and connections, including cleaning for refixing or removal to store complete all as specified.
70Refixing of old steel tubing and connection with new fittings ISI Marked in new or old position (wall, ceiling, floors, etc) of 15 mm bore complete all as specified and as directed.
71Refixing of old steel tubing and connection with new fittings ISI Marked in new or old position (wall, ceiling, floors, etc) of 20 mm bore complete all as specified and as directed.
72Supplying & fixing to floor, walls and ceiling 15 mm nominal bore, medium grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011complete all as specified and as directed.
73Supplying & fixing to floor, walls and ceiling 20 mm nominal bore, medium grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
74Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any kind of soil ,complete all as specified and directed Note : Manual excavation to be done. During excavation if any damage occured to existing cable any type/ water pipe line, it will be contractor responsibilty to get it repair and make functional by providing jointing kit etc without any extra cost. Contractor has to repair it within 24 hrs so that essential service can not be effected due to such damage.If contractor fails to repair it within 24 hrs penalty @ Rs 500/-per hour will be charged to contractor. In this GE decision will be final.
75Returning filling in soft/loose soil, including, spreading levelling watering and well ramming in layers not exc. 25 cm complete all as specified and directed.
76Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting pointall as specified and directed.
77M&L providing sand cushioning with a layer of clean, dry, fine sand for protection of electric cable laid in trenches/ducts, punned down to desired thickness complete all as specified and directed. (Note: For payment purposes only punned down thickness of sand shall be measured )
78M & L for laying old size sub class ‘B’brick for PVC/ XLPE underground cable protection in trench,layedin the manner that width of brick to be peperndicular to the axis of cable ,over LT under ground cable
79Laying onlybricks for PVC/ XLPE underground cable protection in trench,layedin the manner that width of brick to be peperndicular to the axis of cable ,over LT under ground cable (retreived from taking out of old unsv cable) all as specified and directed.
80Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured,3½ core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 120 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. inculding taking out unservieable any type of conductor and cable complete all as specified and as directed.
81All as per Item No 71.00 here-in-before but size of cable 95 sqmm3½ core, complete all as specified and as directed.
82All as per Item No 71.00 here-in-before but size of cable 70 sqmm3½ core, complete all as specified and as directed.
83All as per Item No 71.00 here-in-before but size of cable 50 sqmm3½ core, complete all as specified and as directed.
84All as per Item No 71.00 here-in-before but size of cable 35 sqmm3½ core, complete all as specified and as directed.
85All as per Item No 71.00 here-in-before but size of cable 25 sqmm4 core, complete all as specified and as directed.
86All as per Item No 71.00 here-in-before but size of cable 10 sqmm 4 core, complete all as specified and as directed.
87Material and labour for 15 mm dia galvanized iron tube light grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc,includingall fitting clamps, nut, bolt and washers complete all as specified and directed.
88Horizontal boring of holes by mechanical means, at under road/ pavement / hard standing etc.,not exceeding 15 Metres in length, in any type of soil, suitable for passing through 80 to 100mm bore, galvanised steel tubing,and making good distrubed surfaces as per existing specification complete all as specified and directed. Note : GI pipe of dia 80 mm & 100mm will be measured & paid separately under respective items.
89Material and labour for 80 mm dia galvanized iron tube Medium grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc,including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
90Material and labour for 100 mm dia galvanized iron tube Medium grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc,including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
91Material and labour for 50 mm dia galvanized iron tube Medium grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc,including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
92Material and labour for 40 mm dia galvanized iron tube Medium grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc,including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
93M&Lfor fabricating door offeeder pillar box /DB BOX/bus bar chamer ,dust and vermin proof, cubical type LT panel fabricated from 3.15 mm thick CRCA sheet , with anticorrosive coating and finally epoxy polyester power coatingwith pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 by providing hinges complete all as specified and directed by Eng in Charge.
94Repairs / Maint of LT Panel board/ feeder pillar box of various sizes including disconnecting all incoming and outgoing connection after taking necessary shut down, cleaning the carbon/rust from bus-bar, re-thimbling with new lugs/thimble of existing size,replacingburnt DMC insulator or bus bar supports as per exsiting one, removing old burn out wiringand re-wiring with new cable of exsiting size, includingreplacement of un-serviceable parts and hard ware,replacement of all rusted nut bolts with new steel nut bolts and washer, wrapping of existing incoming and out going cables whose PVC insulation gets detoriated,cableto bewraped with insulation tape (minimum three layers over one another on detoriated portion) with colour code (Red, yellow blue for phase and black for neutral) complete all as specified & directed. Note :- (i) Cost of unsheathed multistranded copper conductor for internal wiring like connection of CTsand DMC insulators are deemed to be included in quoted rate. (ii) Suitable size of cable lugs to be provided by contractor for fixing /jointing the cable in bus bar etc. (iii) Cable gland if required shall be provided and included in cost of repair. (iv) Existing cable to be removed from MCCB/MCB and to be refixed after providing suitable size lugs. Cost of lugs included in cost of repair.
95Supplyandfixing 3 phase digital voltmeter flush mounting 96 X 96 mm of input voltage measurement range 50-520 VAC(P-P) , 5A,accuracy class 0.5forLT panel board, with proper caliberationcomplete all as specified and directed by Engr-in-Charge including taking down unserviceable complete all as specified & directed.
96Supply and Fix in repairs, 3 Phase LED digital ammeter, Accuracy Class 0.5, Aux supply 80-300 VAC, CT secondary site selectable 1A / 5A, flush mounting 96 x 96 mm, with inbuilt selector switch, complete all as specified and directed.
97Supply and fixingin repair Indoor type insulated ring type low tension current transformers of ratio 200/5A accuracy class 1.0for LT panel board, complete all as specified and directed by Engr-in-Charge including taking down unserviceable .
98Supply and Fix in repairs,LED Indicator 16 mm with power consumption < 0.6W, LVGP & surge protection, 64/110 Volts AC/DC / 240 Volts AC, colour Red/Green/ Yellow/Amber/Blue/White, complete all as specified and directed. [Cat No. SIL of Make “L&T” or equivalent Model of Make HPL/ AE]
99Supply and fixingFRLS PVC insulated single core unsheathed multistrand copper conductor for voltage grade 1100 V of size25 Sqmm single core including copper lugs complete all as specified and as directed.
100Preparation of the old decorated existing external and internal steel surface of feeder pillar boxes/LT panels of any description, any size and in any positionby thoroughly cleaning of dirt, fluxing material, other foreign matter and sand papering the surface to remove all scale and rust,wiped finally with mineral turpentine to remove oil, grease and including removal of disintegrated & deteriorated paint either by hand scrapping or by blow lamps, applying necessary filler coat and stopponf required and applying two coats of synthetic enameled paintover a coat of red oxide primer by using spray machine on old prepared surface and writing MES serial No with approved colour code complete all as specified and dircted by engr in charg Note(i) Painting to be done after carrying out all the welding work for replacement of hinges, door lock etc. (ii) Painting shall be done by spray gun. (Approximate minimum area : 40 sqm)
101M&L for taking shut down including repairing of feeder pillars out door typeby providing connectors, copper lugs, nuts, bolts, etc of suitable sizes for incoming and outgoing UG cables includingproper LT insulation tapes to cables which are deteriorated and cleaning the internal area of panel, cleaning the rusted parts by WD-40 and replacing the damaged spare parts like nuts, bolts , screws etc with new one including repairing of panel doors by welding broken hinges, providing new hinges where old hinge rusted and repairing the door locks / providing new locking arrangementincluding taking out incoming and out going cable burried in undergound cutting and providing new aluminium lugs and reconnected to bus bar/ MCCB`s/MCB`s all as specified and directed by Engr-in-charge. Note :(i) Feeder Pillar boxin which repairing of internal wiring,welding of doors not requiredand not coveredunder respective item here-in-before above shall be measured under this item. (ii) Excavation required and cost of lugs is deem to be included in rate of the item. (iii) Contractor shall arrange the Welding machine on site for welding ofdetached Panel doors by providingMS hinges heavy duty and providing tower bolt for locking arrangement
102Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 160 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting:6-10 x In,complete all as specified and directed.[Schneider Model : Easy Pact CVSCat Part No.LV516343 or equivalent Model of Make Legrand / ABB/Hager.]
103Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 250 Amps and 36 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting:6-10 x In, complete all as specified and directed. [Schneider Model : Easy Pact CVSCat Part No.LV525343 or equivalent Model of Make Legrand / ABB/Hager.] :
104Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 400 Amps and 36 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting:6-10 x In, complete all as specified and directed.[/Schneider Model : Easy Pact CVSCat Part No.LV540309 or equivalent Model of Make Legrand / ABB./Hager] :
105Supply and Fix in repairs,moulded case circuit breakers (MCCBs),conforming to IEC 60947-2& IEC 60947-2, AC 415V, 4 pole, with current rating 125 Amps and 25 KA breaking capacity Icu at 415V, AC, 50Hz, with adjustable Over Load setting: 0.8 - 1.0 x In and adjustable Short Circuit setting:6-10 x In,complete all as specified and directed. [Make Siemens/ Legrand / ABB/Hager.]
106S& F SS enclosure for MCCBof rating 250 Amp In-built neutral Link for TPN system l IK08 and IP30 Protection having Louvers for better heat dissipation Suitable to accommodate upto 185 sq. mm. 3 1/2 core Aluminum armoured cable incl taking down unsv one and fixing serviceable/ new MCCB in enclosure and connectiing existing IC/OG cable with proper dimension lugs all as specified and directed. Make Havells /Hager/ABBNote :New MCCB shall be measured and paid seperately.
107Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 25 sq. mm to 50 sq. mm, complete all as specified and directed. [Kit No.EPKJ 0130 of Make "Raychem" or equivalent Model of Make M-Seal/3M]
108Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 70 sq. mm to 150 sq. mm, complete all as specified and directed. [Kit No.EPKJ 0137 of Make "Raychem" or equivalent Model of Make M-Seal/3M]
109Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 150 sq. mm to 185 sq. mm, complete all as specified and directed.Make "Raychem" or equivalent Model of Make M-Seal/3M]
110Materials and Labour for Straight Through Joints, tubular sleeve type, for 1.1 KV Grade, underground cable including jointing kits and accessories complete for making joints, suitable for 3/3 ½ /4 core XLPE armoured, aluminium conductor cable, of size 240 sq. mm to 300 sq. mm, complete all as specified and directed.[Kit No.EPKJ 0144 of Make "Raychem" or equivalent Model of Make M-Seal/3M]
111Supply and fixing in repaircopper lugsuitable of 25 Sqmmcopper cableall as specified and directed
112Supply installation, testing and commissioning of outdoor Automatic transfer switch of 200 Amp, 4 pole, 415 Volt , 50 HZ, with enclosure and autmatic/manual setting and complete protection, including connection with the existing cables and taking out old ATS completeprewired ll as per Cat No. Havells , Cat Part No. IHYFCDE200” or equivalent Model of Make Hager or equivalent make as catetered in PS, complete all as specified and directed.
113Supply installation, testing and commissioning of outdoor Automatic transfer switch of 250 Amp, 4 pole, 415 Volt , 50 HZ, with enclosure and autmatic/manual setting and complete protection, including connection with the existing cables and taking out old ATS completeprewired ll as per Cat No. Havells , Cat Part No. IHYFCDE250 ” or equivalent Model of Make Hager or equivalent make as catetered in PS, complete all as specified and directed.
114Comprehensive maintenance as per Original Equipment Manufacturer"s (OEMs) reccommendations for a period of ninemonthsinstalled at various locations through OEMs Authorised Service Centre Engineers or through OEMs Certified Agencies as approved by GE, including renewal/replacement of defective parts of all existing 3 Phase servo controlled voltage stabilizer of capacity upto 100 kVAand making the system functional by replacing/ repairing the defected parts to the entire satifcation of the Engineer-in-charge. Note:- (i) Cost of new components shall be paid for separately under relevant item(ii)Worksshall be executed through specialist firm who was sufficient experienced on the scope of work.Before commencement of work, approval shall be obtained from the GE (ii) Service Engineer shall visit minimum once in a month to servo controlled voltage stablizerand take serviceability certificate duly signed by the user.(iii). Each maintenance job shall be covered period of 09 Months
115Supply only electronic circuit board for voltage regulation as per Original Equipment Manufacturer"s (OEMs) reccommendations complete all as specified and directed.
116Supply only rotary switch as per Original Equipment Manufacturer"s (OEMs) reccommendations complete all as specified and directed.
117Supply only control card as per Original Equipment Manufacturer"s (OEMs) reccommendations complete all as specified and directed.
118Supply only micro switch as per Original Equipment Manufacturer"s (OEMs) reccommendations complete all as specified and directed.
119Supply only Trip bypass switch as per Original Equipment Manufacturer"s (OEMs) reccommendations complete all as specified and directed.
120Supply and fixing Aluminium lugsuitable of 50 Sqmm for UG XLPE cableall as specified and directed
121Supply and fixing Aluminium lugsuitable of 70 Sqmm for UG XLPEcableall as specified and directed
122Supply and fixing Aluminium lugsuitable of 95 Sqmm for UG XLPE cableall as specified and directed
123Supply and fixing Aluminium lugsuitable of 120 Sqmm for UG XLPE cableall as specified and directed
124Supply,designing ,install, testing & commission 3 phase and neutral, 415 volts outdoor type, CPRI type tested having certification of IEC-61439 , factory made free standing, floor mounting, dust and vermin proof, cubical type LT panel fabricated from 3.00 mm thick CRCA sheet for outer shell and 2 mm thick for non load bearing with angle iron frame of 50 x 50 x 6 mm, double door, front and back openable type, double door system, hinged opening, rubber lining, locking arrangement, with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade, protection class IP-66 fully compartmentalize design with 4 Nos of bus bar made of copper ETP grade suitable for 375 Amp (size of copper strip should not be less than 30x5 mm for each phase and neutral) pre-wired with suitable size of copper strip/copper wire with colour code for connecting out going MCCB/MCB"s, including suitable aluminium earth strips conforming to IS with danger notice plate, necessary cable glands, cable connection with proper lugs, making electrical connection and circuit wiring for street light auto ON/OFF control timer by using desired electrical parametersPCC foundation and pedestal for fixing pillar feeder box/LT Panel with PCC 1:5:10, 15 cm thick in foundation, brick (Fly ash) / PCC block work in CM 1:6, rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grounting bolts etc for panel. The platform shall be of 450 mm height above ground level all as specified with supply and fixing the following accessories :
125(A) Incoming MCCB250 Amps rating,TPN ,415 V, AC, 50 HZ, thermal release range 200-250 Amp withadjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 KA --- 01 Nos .Make Hager/Legrand / Seimens/ C&S/Schinder. (B) Outgoing (b)MCCB160 Amps rating,TPN ,415 V, AC, 50 HZ, thermal release range up to 160 Amp withadjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity not less than 25 KA --- 01 NosMake Hager/Legrand / Seimens/ Schinde/C&S.(c)MCCB63 Amps rating,TPN ,415 V, AC, 50 HZ, thermal release range up to 63 Amp withadjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity not less than 16 KA --- 04 NosMake Hager/Legrand / Seimens/ Schinder/C&S (d) Rise/lower push button -01 No (e) Digital voltmeter 0-500 volt with selector switch -01 No f) Digital amp meter 0-100 Amp with set of current transformer of suitable rating and selector switch -01 No (g) Indicator lamp (RYB) LED type - 01 set Note:- (i) All MCCB/MCB should be of Make :L&T/ Legrand /Schnider/Seimens/C&S. (ii) Drawing of LT panel and make of items shall be get approved from GE before ordering the panel. (iii) Cost of lugs for cable and cable gland etc also included in unit rate of panel. (iv) Rotary handle to be provided for allMCCB for control and operation of MCCB. (vi) The rating of copperbus bar to out going MCCB / MCB`s shall not be less than 1.5 times the rated current of individual out going feeders/ MCCB. (vii)Independent Amper meterwith CTs to be provided for each out going feeder. (viii) Spreader terminals and Phase barriers to be provided with all MCCB`s (ix) Rate of panel include refixing of all cables in panel which are dismantle & taking out from old unserviceablepanel.
126Supply,install, testing & commission 3 phase and neutral, 415 volts outdoor type, CPRI type tested having certification of IEC-61439 made free standing, floor mounting, dust and vermin proof, cubical type LT panel fabricated from 3.00 mm thick CRCA sheet for outer shell and 2mm thick for non load bearing with angle iron frame of 50 x 50 x 6 mm, double door, front and back openable type, double door system, hinged opening, rubber lining, locking arrangement, with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade, protection class IP-66 fully compartmentalize design with 4 Nos of bus bar made of copper ETP grade suitable for 375 Amp (size of copper strip should not be less than 30x5 mm for each phase and neutral) pre-wired with suitable size of copper strip/copper wire with colour code for connecting out going MCCB/MCB"s, including suitable aluminium earth strips conforming to IS with danger notice plate, necessary cable glands, cable connection with proper lugs, making electrical connection and circuit wiring for street light auto ON/OFF control timer by using desired electrical parametersPCC foundation and pedestal for fixing pillar feeder box/LT Panel with PCC 1:5:10, 15 cm thick in foundation, brick (Fly ash) / PCC block work in CM 1:6, rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grounting bolts etc for panel. The platform shall be of 450 mm height above ground level all as specified with supply and fixing the following accessories :
127(A) Incoming MCCB250 Amps rating,TPN ,415 V, AC, 50 HZ, thermal release range 200-250 Amp withadjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 KA --- 01 Nos .Make Hager/Legrand / Seimens/ Schinder. (B) Outgoing Outgoing : (b) MCCB TPN ,160 Amp,50 HZ , 415 V, 25 KA, adjustable thermal & adjustable magnetic type, Ics = 100% of Icu -02 Nos. (c) MCCB TPN ,63 Amp,50 HZ , 415 V, 16 KA, adjustable thermal & adjustable magnetic type, Ics = 100% of Icu -01 Nos. (d) Rise/lower push button -01 No (e) Digital voltmeter 0-500 volt with selector switch -01 No (f) Digital amp meter 0-100 Amp with set of current transformer of suitable rating and selector switch -01 No (g) Indicator lamp (RYB) LED type - 01 set Note:- (i) All MCCB/MCB should be of Make :L&T/ Legrand /Schnider/Seimens. (ii) Drawing of LT panel and make of items shall be get approved from GE before ordering the panel. (iii) Cost of lugs for cable and cable gland etc also included in unit rate of panel. (iv) Rotary handle to be provided for allMCCB for control and operation of MCCB. (vi) The rating of copperbus bar to out going MCCB / MCB`s shall not be less than 1.5 times the rated current of individual out going feeders/ MCCB. (vii)Independent Amper meterwith CTs to be provided for each out going feeder. (viii) Spreader terminals and Phase barriers to be provided with all MCCB`s (ix) Rate of panel include refixing of all cables in panel which are dismantle & taking out from old unserviceablepanel.
128Supply & fixing wall in repair mounted Busbar chamber TPN (4 bar) 100 Amp rated, 415 volt, 4 way complete all as specified and as directed. Make - Havells, cat No.IHBC010004.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail