| 7 | Fabrication, supplying, installation, testing and commissioning of suitable size outdoor type feeder pillar ( Protection Index IP-54) (1000MM(height)X1300MM(Width)X 300 MM deep)(front area not less than 1.3 sq. mtr.) made of 2 mm thick CRCA sheet steel, dust & vermin proof ,having rain protection shade, compartmentalised & seggregated for each circuit, having double door in the fronts, locking arrangement, openable hinged type door (double leaf ), suitable for 415V, 3 pahse, 4 Wire 50 Hz AC supply system , having seperate chamber with 4 strip aluminium busbar of 200 Amps. capacity, GI earth bar at the full width of rear, earth stud, cable entry through gland plate of 3 mm thick, i/c cleaning & finishing complete with powder coating in approved shade, 40 mm x40 mm x 5 mm M S angle iron base and 4 legs of length 600 mm,& grouting the same in suitable cement concrete foundation,civil foundation etc complete as required &ncluding supply and fixing the following swich gears and accessories includingincoming and out going connections with suitable busbar/pvc copper wire, inter connections, with suitable size copper FRLS wire Thimble / lugs gland plate, earthing the boards as required Including dismantling of old existing panel at site. (CPRI Approved)i)160 Amps, 4 pole, 415 volts, 50 Hz MCCB 36 KA (Icu=ICS100%) make L&T/ Havells/ Standard/ Indoasian/HPL - 1 Noii)63 Amps, 4 pole,MCCB415 volts, 50 Hz27 KA (Icu=ICS100%) make L&T/ Havells/ Standard/ Indoasian/HPL - 08 Nosiii)32 Amp, DP, MCB, 10 KA, C curve, 240 V, 50 Hz make L&T/ Havells/ Standard/ Indoasian/HPL - 02 Nosiv)Digital multifunction meter L&T/ AE make compatible to L&T Cat. No. WC411011OOOO ( 1No) - and CT\"s class 1 - 1 set, LED indication lamps -03 Nos(R,Y,B |