Bharat Sanchar Nigam Limited-BSNL has published Tender For Sitc Of 1X500kva Dea Set With Silent Enclosure And Conventional Control Panel At Main Te Building Ambala Cantt. Sh Earthing And Laying Of Cable For Ac Pkg Plant And Power Plant Panel. Submission Date for this Tender is 09-09-2023. Electrification Work Tenders in ambala Haryana. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. |
2 | Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required. |
3 | Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. |
4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
5 | Upto 120 sq. Mm |
6 | Above 185 sq. mm and upto 400 sq. Mm |
7 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
8 | Above 95 sq. mm and upto 185 sq. Mm |
9 | Above 120 sq. mm and upto 400 sq. Mm |
10 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. |
11 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
12 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
13 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. |
14 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
15 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
16 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
17 | 3½ X 300 sq. mm (70mm) |
18 | 3½ X 240 sq. mm (62mm) |
19 | 3½ X 120 sq. mm (45mm) |
20 | Dismantlling of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size from duct/ surface of wall/cable tray as required. |
21 | Above 35 sq. mm and upto 95 sq. mm |
22 | Above 185 sq. mm and upto 400 sq. mm |
23 | Supplying and Fixing of 3 Pole, 400 A MCCB (50 kA) with adjustable ThermalRelease range 320-400Amp in the existing MV panel i/c making modification if required etc complete as required.(Make L&T ModelD-Sine or similar models of other approved Make) |
24 | Supplying and Fixing of 4 Pole on load 630Amp. Changeover switch with sheet steel enclosure suitable for operation on 415Volts,50HZ AC Supply etc complete as required. |
25 | Dismantlling and shifting of existing spared MV Panel (AC PKG Panel) from First Floor PKG RoomMTE Naraingarh to First floor PKG Room MTE Ambala Cantt i/c disconnection of cable termination, loading, transportation and unloading etc complete as required. |
26 | Installtion,Testing and commissioning existing MV Panel etc complete as required. |
27 | S/F of MS angle iron frame of size 50mmx50mmx5mm for fixing of existing Main switch,changeover switch etc i/c cutting,welding painting etc complete as required. |
28 | Supplying and fixing of neutral white/cool day light18wattLED recessedsquare/round panel/ downlighter suitable for operation on 150-300VAC, 50Hz etc complete as required and as per specifications attached.(M/s Wipro/Havells/ Crompton/ Philips/ Syska/Surya) |
29 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
30 | Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. |
31 | 150 mm width X 50 mm depth X 1.6 mm thickness |
32 | Replacement of faulty items in PKG Panel i/c dismantlling the faulty and ITC of new ityems etc complete as required. |
33 | 63 Amp. Open execution Type FN (TPN/FP) S-D-F suitable for DIN fuse link |
34 | 63 Amp. Bolted HRC Fuses |
35 | Wiring for circuit/ submain wiring alongwith earth wire with the 2x1.5Sqmm +1x1.5 Sqmm earth wire size of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required |
36 | Supply Installation Testing and commissioning ofof 50 W LED flood light fitting made up of pressure die cast housingwith toughned glass including high powerLED lamp and all accessories and fixing on the existing bracket includingconnections with 1.5 sq.mm. FRLSPVC insulated copper conductor, single core cable and earthing etc.complete as per specifications attached (Make M/s Wipro /Crompton /Havells / Philips /Surya make). |
37 | Supplying & laying of 2X1.5sqmm size PVC Insulated copper conductor,armoured power cablesuitable for 600/ 1000V rated Ac supply i/c laying, fixing , connection etc. complete as reqd . |