| 1 | Replacement ofExisting Old L&T make 800 Amp 3 Pole ACB (Model No: CN-CS 800) from the LT Panel. |
| 2 | Supply, installation, testing and commissioning of Supply of ABB make 1000 Amp, 4 Pole, Electrically Drawout, SACE Emax2 series ACB with Icw = 50KA for 1 sec along withEkip LSIG release, Shunt release @220-240V AC/DC, Undervoltage release @220-240V AC/DC, Geared motor 220-250VAC/DC, E1.2N 1000 Ekip Dip LSIG 4p WMP andE1.2 W FP Iu=1600 4P HR HR |
| 3 | Busbar Modification Job for Installation of New ACBs along with CTs in replacement of old ACBs |
| 4 | Dismantling of existing 265.5 KVAR APFC Panel with Capacitor Bank including removing the existing termination. |
| 5 | Design, supply, installation, testing and commissioning of 270KVAR @ 440V, 3Ph, 50Hz, Auto Switched (Contactor LVAS-C) Shunt Capacitor System along with Main Incomer – MCCB : - 630A, 3P, 50KA,TM Release With Adj. OL & SC Protection. C.T. - 600/5A CLASS 1.0, 5VA, Power Factor Controller consisting of [30kx5+25Kx3+15Kx3] steps of APP Capacitors confirming to IS-13585-2012 /IEC60931-1-1996, Reactor Standards – IS-5553 /IEC-60076, Metering: - Multifunction Meter with RS485, with it’s latest amendments as per attached Technical Specification. APFC panel must be manufactured by Capacitor OEM. (Make – Siemens , Hitachi ,Schneider.)Incomer –630A TPN MCCB 50KA - 1setOUTGOING :Stages for APFC1. 30KVAr Heavy duty Capacitor Bank , APP type - 5 set2. 25KVAr Heavy duty Capacitor Bank , APP type -3set3. 15 KVAr Heavy duty Capacitor Bank APP type - 3set4. BUSBARS : AL5. RATING : 630 A TPN |
| 6 | Servicing & Rectification of Existing 200 KVAR APFC Panel. |
| 7 | Dismantling of existing PDB Panel from Sub-Station including removing the existing termination. (Ground Floor- Substation Room). |
| 8 | Supply, installation, testing and commissioning of8 Way VTPN DB including all incoming- 125A MCCB, Outgoing - MCBs (6A-20A SP) (10A-20A DP) (40A-63A FP) |
| 9 | Supply & Installation of Ammeter (Flush Mounting 96X96mm, input Voltage - 50-520VAC, Auxiliary Supply 230VAC) in place of defective Ammeter. |
| 10 | Supply & Installation of LED Indication Lamps (R/Y/B/G/W) of in replacement of defective Indication Lamps. |
| 11 | Supply & Fixing of aluminium engraved cable tags for identification of cable at both ends for all the Cables for all equipments, panels, subpanels. |
| 12 | Supply of Class – B rubber mat as per IS-15652. Size: 2 M X 1 M X 2.5 mm thick |
| 13 | Supply of Class – C rubber mat as per IS-15652. Size: 2 M X 1 M X 3 mm thick |
| 14 | Charges for preparation of full Electrical Single Line Diagram, Separate Single Line Diagram for each Floor power distribution. The contractor shall have to be submitted 05 sets of as built drawings. |
| 15 | Servicing of floor PDB panels including repair of damage, painting, cleaning and replacement of minor accessories such as gaskets, nuts, bolts, etc., installation of ammeters and CT in incoming circuit |
| 16 | Providing and laying 6mm thick cement plaster of mix 1:3 (1 cement: 3 fine sand) on surfaces with fine sand including curing etc. |
| 17 | Providing and laying in position cement concrete of specified grade excluding cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement :2 Fine Sand : 4 Graded stone aggregate of 20 mm) |
| 18 | Buyback of Existing APFC Panel, Existing PDB Panel, 6nos Old L&T make 800 Amps ACBs. |