Tender For Repair / Replacement Of Dg Sets, Fire Alarm System, Earthing Infrastructure And Misc E/M Nature Of Work At Af Stn Salua Under Ge (Af) Kalalikunda
Tender Overview
Project Description
Tender For Repair / Replacement Of Dg Sets, Fire Alarm System, Earthing Infrastructure And Misc E/M Nature Of Work At Af Stn Salua Under Ge (Af) Kalalikunda
Corrigendum
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 16-Sep-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 23-Sep-2023 |
| 2 | 23-Sep-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 28-Sep-2023 |
| 3 | 29-Sep-2023 | Due Date Extended | Admin Corrigendum Date Extend | 30-Sep-2023 |
BOQ
| Sl. No. | Item Description |
| 1 | Materials and labour for maintenance and servicing of 20 KVA DG Sets of following capacity complete all as specified and as directed.NOTE: (a) Oneservice of DG Set including maintenance shall be termed as ‘EACH JOB’.(b) Minor spare parts shall be replaced as a part of servicing otherwise paid under separate items. |
| 2 | All as per itemNo. 1.00here in beforebut 30 KVA DG set complete all as specified and as directed. |
| 3 | All as per itemNo. 1.00here in beforebut 82.5 KVA DG set complete all as specified and as directed. |
| 4 | All as per itemNo. 1.00here in beforebut 125 KVA DG set complete all as specified and as directed. |
| 5 | All as per itemNo. 1.00here in before but 250 KVA DG set complete all as specified and as directed. |
| 6 | Labour only for overhauling of injector nozzles including replacement of nozzles, washers, etc. and pressure setting as required for 20 / 30 KVA DG Sets of following capacities and replacement of timing shaft with coupling complete all as specified and as directed.NOTE: Spare parts shall be measured and paid separately under seperate items . |
| 7 | All as per itemNo. 6.00here in beforebut 125 / 82.5 KVA DG set complete all as specified and as directed. |
| 8 | All as per itemNo. 6.00here in beforebut 250 KVA DG set complete all as specified and as directed. |
| 9 | Labour for overhauling of injector nozzles including replacement of nozzles, washers, etc. and pressure setting as required for 20 / 30 KVA DG Sets of following capacities and replacement of timing shaft with coupling complete all as specified and as directed.NOTE: Spare parts shall be measured and paid separately under seperate items . |
| 10 | All as per itemNo. 9.00here in beforebut 125 / 82.5 KVA DG set complete all as specified and as directed. |
| 11 | All as per itemNo. 9.00here in beforebut 250 KVA DG set complete all as specified and as directed. |
| 12 | Supply for pouring of coolant suitable for radiator for Kirloskar/Jackson make engine as per the requirement of time to timeas per OEM specificationfor various capacities of DG Set (Make : SERVO/CASTROL/PUROCOOL) |
| 13 | Supply and filling in replacement of Engine oil as per OEM specification to top up/ refilling of DG set as per the direction of Engineer-in-charge.(Make Gulf/Castrol/Volvalin) |
| 14 | Supply onlythe following items in DG set of 250 KVA capacity. |
| 15 | Diesel filter elementas per OEM specification |
| 16 | Oil Filter elementas per OEM specification |
| 17 | Air cleaner hose pipe with clamp as per OEM specification |
| 18 | Radiator hose pipe with clampas per OEM specification |
| 19 | Safety control valve as per OEM specification |
| 20 | Flexible pipe for fuel pump to PT pump with banjo washer , nut boltas per OEM specification |
| 21 | Flexible pipe for Disel tankto filter with banjo washer , nut bolt as per OEM specification |
| 22 | Air cleaner Filteras per OEM specification |
| 23 | Automatic voltage regulatoras per OEM specification |
| 24 | Supply & fixing the following items in DG set of 125/82.5 KVA capacityas per OEM specification |
| 25 | Diesel filter element. |
| 26 | Oil Filter element |
| 27 | Air cleaner hose pipe with clamp |
| 28 | Fuel indicator assembly |
| 29 | Flexible pipe for diesel tank to filter with banjo washer, nut bolt |
| 30 | Radiator hose pipe with clamp |
| 31 | Automatic voltage regulator |
| 32 | Air cleaner Filter |
| 33 | Supply only the following items in DG set of 30/20 KVA capacity.as per OEM specification |
| 34 | Diesel filter element |
| 35 | Oil Filter element |
| 36 | Air cleaner hose pipe with clamp |
| 37 | Radiator hose pipe with clamp |
| 38 | Flexible pipe for fuel pump to PT pump with banjo washer , nut bolt |
| 39 | Flexible pipe for Disel tankto filter with banjo washer, nut bolt |
| 40 | By pass filter |
| 41 | Automatic voltage regulator |
| 42 | Air cleaner Filter |
| 43 | Supply only SMPS for250 KVA DG Set AMF panel as per OEM recommendation/ specfication complete |
| 44 | Supply only Relay / LVMfor 250KVA DGAMF Panel as per OEM recommendation/ specfication complete |
| 45 | Supply onlypower contactor 4 pole for 125/82.5KVA DG AMF Panel as per OEM recommendation/ specfication complete |
| 46 | Supply only SMPS for 125/82.5KVA DG Set AMF panel as per OEM recommendation/ specfication complete |
| 47 | Supply only Battery charger for 125/82.5KVA DGAMF Panelas per OEM recommendation/ specfication complete |
| 48 | Supply only power fuse link with breaking capacity 80 KA for 125/82.5KVA DGAMF Panelas per OEM recommendation/ specfication complete |
| 49 | Supply only relay/LVM for 125/82.5KVA DGAMF Panel as per OEM recommendation/ specfication complete |
| 50 | Supply onlypower contactor 4 pole for 30/20KVA DG AMF Panel as per OEM recommendation/ specfication complete |
| 51 | Supply only SMPS for 30/20 KVA DG Set AMF panel as per OEM recommendation/ specfication complete |
| 52 | Supply only relay/LVM for 30/20KVA DGAMF Panel as per OEM recommendation/ specfication complete |
| 53 | Supply only controller circuit for 30/20 KVA DGAMF Panel as per OEM recommendation/ specfication complete. |
| 54 | S&F in replacement copper strip of size 20 x3.15mm as earth continuity conductor or main earthing lead fixed on \"V\" type porcelain insulator ( ceramic bus bar supportinsulator off whitecolour of min size of 36 mm width x 60 mm length with 36 mmwidth bus bar mounting base) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as requiredincluding copper strip brazingto each joints and connected with by providingbrassnut boltsand washers all as specified and as directed. |
| 55 | S&F in replacementcopper strip of size 32 x 6mm as earth continuity conductor or main earthing lead fixed on \"V\" type porcelain insulator ( ceramic bus bar supportinsulator off whitecolour of min size of 36 mm width x 60 mm length with 36 mmwidth bus bar mounting base) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20 x 3 mm copper strip brazingto each joints and connected with by providingbrassnut boltsand washer all as specified and as directed. |
| 56 | S&F in replacement of Porcelain insulatorofexisting size forisolation of conductor from the building wall by providing 15cm long fastners complete all as specified and as directed. |
| 57 | Material & labour for earthing complete with copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick burried directly in ground (Earth pit not less than 3 mtr deep below ground level) with top edge of the plate not less than 3.25 mtrbelow ground level connected to copper strip 20 x 3 mm as earth lead by brass nut bolts washer including brazing the copper strip with copper plate as shown in electrical plate No 3 connected to earth test point including necessary excavation for earth pitin hard dense soil, rocky / disintergate rock, filling charcoal and salt around the plate in layers , filling the pit with low resistivity agriculture soil free from stones, to be bring from out side defence land and mixed with Bentonite, (3 bags of 25 Kg each ), construction ofinspection pit ( earth pit chamber) of brick work of size 600 x 600 x 600 mmwith PCC copping of (1 :1.5: 3), 12.5 mm aggregate A1 with MS sheet 2.8 mm plate cover on frame ofangle iron of size 40 x 40 x 5 mm with , wire mess, funnel, test point, 40 mm dia GI protection pipelightgrade and20 mm GI peforated pipefor wateringetc complete and testing on completion. The electrode and lead shall be of copper all as specified and as directed. |
| 58 | [NOTE FOR ITEM NO 57.00 : (i) Contractor shall uselow reisistivity fresh agriculture soil , mixed with 3 x Bags of bentoniteclay of 25 Kg each for refillingthe pit to achive the desired resistance.(ii) Copper strip will be laid below 60 cm from ground level and connected to test point through plinth protection(iii) Necessary cost of repair to plinth protection as per existing specification and connected plate and earth continuity conductor by providing 2 x brass nuts bolts and brazing of joints,bringing argiculture soil from out side defence land and cost of 3 x Bags of bentonitedeemed to be included in the item rate.(iv) Contractor has to clear the side and disposed off the excavated soil from pit on completion of work.(v) Contractor have to submit test report of earthing after completing the earthing.(vi) Bentonite clay should be Conf to IS 6186: 1986.(vii) The cost ofCopper strip of size 20X3 mm from top of earth plate upto 7.5 meter above ground level is deemed to be included in the unit rate of above item.and copper strip beyond 7.5 RM will be measured seperately.(viii). All the joints in copper strip and connection with Earth Plate to be welded through brazing and in addition by proving brass nut bolt and washer are deemed to be included in the unit rate. (viiii) Cost of brazing / welding and nut bolts are deemed to be included in the unit rate. (ix) Cost includes removal of excavated soil upto a distance of 1500 mtrs. (x) If the desired earth resistance not obtained the earthing shall be re-done by contractor without any extra cost to Govt . ] |
| 59 | Supply only back filling compound ( Bentoniteclay ) in existing earth pits through G I pipes as per site requirment complete all as directed. |
| 60 | M&L forbrazingof copper earth strip including grinding and prepartion of existing earth strip complete all as specified and as directed. |
| 61 | Supply and fix Detectors Complying with and type certified to EN - 45 Addressable type smoke detector Photoelectric /Optical with base with self built intelligence Addressable type multisensor detector with heat and smoke combination as per IS: 11360 complete all as specified and as directed. |
| 62 | Supply and fix in replacement of Fire alarm control panel complying with BS EN 54 Double loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules complete all as specified and as directed. |
| 63 | Supply and fix in replacement of Mannual Call Box resettable type complete all as specified and as directed. |
| 64 | Supply and fix in replacement of Addressable sounder complete all as specified and as directed. |
| 65 | Supply and fix in replacement of Control Relay Module complete all as specified and as directed. |
| 66 | Supply only Push button switch as per existing complete all as specified and as directed. |
| 67 | Supply and fix in replacement of Isolator Module complete all as specified and as directed. |
| 68 | Supply and fix in replacement of Respons Indicator complete all as specified and as directed. |
| 69 | Supply and fix in replacement of battery suitable for fire alarm control panel complete all as specified and as directed. |
| 70 | Note: Schedule of cedit amount of Rs 4904.00 shall be deducted from the total quoted amount of BOQ. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedCorrigendum-1 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-2 Issued
Clarifications on tender conditions and amendments issued.
CompletedCorrigendum-3 Issued
Clarifications on tender conditions and amendments issued.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender