Tender For Augmentation Of Water Supply Scheme Of Village Gangwa District Hisar. “Construction Of Raw Water Pumping Station Comprising Rcc S/S Tank, Sump Well, Pump Chamber, Inlet Channel, Boundary Wall, Rising Main Lines, Raw Water Pumping Machinery,, Hisar-Haryana

Public Health Engineering Department-PHED has published Tender For Augmentation Of Water Supply Scheme Of Village Gangwa District Hisar. “Construction Of Raw Water Pumping Station Comprising Rcc S/S Tank, Sump Well, Pump Chamber, Inlet Channel, Boundary Wall, Rising Main Lines, Raw Water Pumping Machinery,. Submission Date for this Tender is 14-09-2023. Diesel Generators Tenders in Hisar Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

39330220
Corrigendum : Tender For Augmentation Of Water Supply Scheme Of Village Gangwa District Hisar. “Construction Of Raw Water Pumping Station Comprising Rcc S/S Tank, Sump Well, Pump Chamber, Inlet Channel, Boundary Wall, Rising Main Lines, Raw Water Pumping Machinery,
Open Tender
Indian
Haryana
Hisar
14-09-2023

Tender Details

Tender For Augmentation Of Water Supply Scheme Of Village Gangwa District Hisar. “Construction Of Raw Water Pumping Station Comprising Rcc S / S Tank, Sump Well, Pump Chamber, Inlet Channel, Boundary Wall, Rising Main Lines, Raw Water Pumping Machinery, Dg Set, Electric Transformers Etc. Operation And Maintenance During Defect Liability Period Of 12 Months After Successful Completion Of 3 Months Trial Run And Thereafter For 5 Years Complete In All Respect.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Sep-2023 The time limit for completion of work Other 14-09-2023

Key Value

Document Fees
INR 20000 /-
EMD
INR 2477360.0 /-
Tender Value
INR 12.38 Crore /-

BOQ Items

Name of Work
Sl. No. Item Description
1H.T. METERING PANEL: Supply, erection, testing and commissioning of 11KV Indoor H.T Metering Panel complete with suitable CTs, PTs and 3 phase, 4 wire Digital Electronic KWH Meter with accuracy class of 0.5 as per requirement and approval of DHBVN, consisting of the Cubical Panel Box of minimum size 700mm x700mm x1500mm free standing, floor mounting type made out of 14 SWG CRCA sheet steel powder coated with epoxy coated channel iron base frame (150 KVA LOAD)
2Provision for providing and fixing flow meter with electronic display on delivery pipe inside pump chamber complete in all respects.
3Provision for lighting fittings at pumping stationcomplete in all respect
4PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electricalLT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following itemsfor 1Pumping set a) Main switch suitable ampere 1 No. (LandT Siemens, ABB) b) CT 100/3 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No(LandT Siemens, ABB) f) VSS 1 No.and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp= One Set i) Change over switch of suitable Amp = 1 No. (Each) Panel Board for motors having capacity of 150 BHP
5COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd 25 mm2 3core
6COPPER CABLE: Supply, erection, testing and commissioning of IS marked 3 core Copper Cables, Solid Copper conductor up to 6sqmm and balance Stranded Copper, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Glavanised wire for cables up to 10x1.5sqmm, 8x2.5sqmm, 2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip), extruded PVC type ST2 Outer Sheathed, /1100 V grade as per IS 7098 (Part 1) 1988 with up to date amendments along with all accessories like thimble lugs etc for motors as per entire satisfaction of Engineer-in-charge complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd 120 mm2 3core
7HT. ALLUMINIUM CABLE: Supply erection testing of standard make XLPE 3 core HT / 11 KV grade ISI marked Stranded compact circular aluminium conductor, conductor screen with extruded semi conducting compound, XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, cores laid up, innersheath of PVC, galvanised steel flat strip armoured, and overall PVC sheathed cable conforming to is 7098 (part-2) 2011 with up to date amendments for making following connectiona) from G.O switch to metering equipment . b) from metering equipment to transformer complete in all respect. Make: Indian Cables Ltd./ Polycab / RR Cables / CAPP / Finolex / Havells / Gloster / Universal / Fort Gloster Industries Ltd./ Indian Cable Co. / Asian Cables Corporation Ltd 35 Sqmm size
8LT CABLE ALLUMINIUM: Supply, erection, testing and commissioning of IS marked 3.5 core Cables, Solid Aluminum conductor up to 10sqmm and balance stranded conductor, XLPE Insulated, cores laid up, PVC Inner sheathed, Armoured (Aluminium wire for single core up to 70sqmm and balance Aluminium strip, Glavanised wire for cables up to2x10sqmm, 3x10sqmm, 4x6sqmm and balance all galvanized steel strip) extruded PVC type ST2 Outer sheathed, 650/1100V grade as per IS7098 (Part-1) 1988 with up to date amendments along with all accessories complete in all respect. Make: Indian Cables Ltd./ Finolex / Havells / Polycab / RR Cables / CAPP / Gloster / Universal / Fort Gloster Industries Ltd./ Asian Cables Corporation Ltd. 185 Sqmm size
9Sluice valves: Extra for fixing sluice valves/flap valves socketed or flanged including cartage from stores or nearest Railway Station to site of works (700 mm i/d)
10C.I DOUBLE FLANGED PIPE:Providing and laying Double Flanged (screwed / welded) Centrifugally (Spun) Cast Iron, Class B (IS : 1536). 700 mm dia.
11C.I DOUBLE FLANGED PIPE:Providing and laying Double Flanged (screwed / welded) Centrifugally (Spun) Cast Iron, Class B (IS : 1536). 600 mm dia.
12`RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked 19000 LPM x 12.50 m x 90.00 BHP
13`RAW WATER PUMP: Supplying, erection, testing and commissioning of Horizontal motor pumping set for Raw water having head as per the indicated requirements of discharge in LPM and power capacity in BHP as per IS marked 11400 LPM x 35.00 m x 150.00 BHP
14PANEL BOARDS FOR MOTORS: Supply, erection, testing and commissioning of wall mounted electricalLT Panel board, fabricated from 16 SWG CRCA sheet duly stouten with suitable angle iron frame work and completely powder coated of suitable size deep having following itemsfor 1Pumping set a) Main switch suitable ampere 1 No. (LandT Siemens, ABB) b) CT 100/3 = 1 Nos. (AE/ KAPPA/ LandT) c) Digital Multi function meter = 1 No. d) SPP = 1 No. of approved make e) Motor starter, star delta 1 No(LandT Siemens, ABB) f) VSS 1 No.and ASS 1 Nos. of approved make. g) Capacitor KVAR as per site requirement = 1 No. h) Indicating Lamp= One Set i) Change over switch of suitable Amp = 1 No. (Each) Panel Board for motors having capacity of 90 BHP
15Operation and Maintenance for complete scope of work covered under this contract as per OandM schedule for a period of 5 year after successful completion of 12 month`s defect liability period and 3 Months trial run complete in all respect as per approved NIT. The amount will be charged to the A/Mtc. estimate. (Disinfection material will be supplied by PHED)
161st year Operation and maintenance after defect liability period
172nd year Operation and maintenance after defect liability period
183rd year Operation and maintenance after defect liability period
194th year Operation and maintenance after defect liability period
205th year Operation and maintenance after defect liability period