Tender For Providing Dedicated Power Connection To The Sez Jalefa Sabroom Within The Jurisdiction Sabroom Electrical Division Sabroom South Tripura, sabroom-Tripura

Tripura State Electricity Corporation Limited-TSECL has published Tender For Providing Dedicated Power Connection To The Sez Jalefa Sabroom Within The Jurisdiction Sabroom Electrical Division Sabroom South Tripura. Submission Date for this Tender is 05-09-2023. Electrification Work Tenders in sabroom Tripura. Bidders can get complete Tender details and download the document.




Tender Notice

39319608
Tender For Providing Dedicated Power Connection To The Sez Jalefa Sabroom Within The Jurisdiction Sabroom Electrical Division Sabroom South Tripura
Open Tender
Indian
Tripura
sabroom
05-09-2023

Tender Details

Providing Dedicated Power Connection To The Sez Jalefa Sabroom Within The Jurisdiction Sabroom Electrical Division Sabroom South Tripura Electrification Of Special Economic Zone Jalefa Sabroom South Tripura

Key Value

Document Fees
INR 10000 /-
EMD
INR 214902.0 /-
Tender Value
INR 1.07 Crore /-

BOQ Items

Name of Work: Providing dedicated power connection to the the SEZ, Jalefa, Sabroom within the jurisdiction Sabroom Electrical Division, Sabroom South Tripura.
Sl. No. Item Description
1Supply of 11 KV Outdoor type Metering Panel made out from 3mm sheet duly painted power quoted floor mounting complete with 1 (one) set 11 KV CT, PT combined, 1 (one) no. MS Box, 1 (one) no 1-15 KV volt meter 96x96 mm, 1 (one) no. 6A ammter selector switch, 3 (three) no 110 volt ASC phase indicating lamp, 1(one) no. 1A 3ph 3 wire Electronic Tri vector Meter, 1 (one) no. 96x96 mm 0-100A Ammeter CTR 100/1, 1(one) coil 2.5 mm CU wire as per TSECL Design & Drawing.
29.0 mtr long galvenised steel tubular pole(SP-32)
311 mtr. long galvenised Steel Tubular pole(SP-57)
4Stay set complete
5A.C.S.R. conductor (Rabbit 50 sq mm)
6G.I. strainded wire (Stay wire)
7Strain insulator ( H.T).
811 KV Disc insulator
911 KV disc fittings
1011 KV Pin insulator with GI pin
11Galvanised Channel (75x40x40x6 mm)
12Galvanised Angle (65x65x6 mm)
1311 KV G.O. Switch
1411 KV L.A.
1511 KV D.O.Fuse Set
162.5 mtr. long 40 mm dia. G.I. pipe for earthig of O.H. cable termination point
178 SWG G.I. wire (4 mm) for earth connectivity
18¾ th inch dia. Polythin Pipe
19Cement Concreting of Steel pole
20Erection of 1 (one) no. RCC piler base of size 1.5x2.0x0.75 mtr including supply of all materials
21120 sqmm bi- metalic lugs
22Galvanised Bkt. Clamp (50x6 mm)
23Galvanised Stay Clamp (50x6 mm)
24Galvanised Nuts & Bolts (assorted size)
25Installation of 11 KV Outdoor type Metering Panel made out from 3mm sheet duly painted power quoted floor mounting complete with 1 (one) set 11 KV CT, PT combined, 1 (one) no. MS Box, 1 (one) no 1-15 KV volt meter 96x96 mm, 1 (one) no. 6A ammter selector switch, 3 (three) no 110 volt ASC phase indicating lamp, 1(one) no. 1A 3ph 3 wire Electronic Tri vector Meter, 1 (one) no. 96x96 mm 0-100A Ammeter CTR 100/1, 1(one) coil 2.5 mm CU wire as per TSECL Design & Drawing.
26Erection of 9.0 mtr long galvenised steel tubular pole
27Erection of 11 mtr. long galvenised Steel Tubular pole
28Erection of Stay set complete
29Erection of A.C.S.R. conductor (Rabbit 50 sq mm)
30Erection of G.I. strainded wire (Stay wire)
31Erection of Strain insulator ( H.T).
32Erection of 11 KV Disc insulator
33Erection of 11 KV disc fittings
34Erection of 11 KV Pin insulator with GI pin
35Erection of Galvanised M.S. Channel (75x40x40x6 mm)
36Erection of Galvanised M.S. Angle (65x65x6 mm)
37Erection of 11 KV G.O.. Set
38Erection of 11 KV L.A.
39Erection of 11 KV D.O.Fuse Set
40Excavation, erection, testing & commissioning of 40mm dia, 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover plates on GI frame, charcoal, salt and other accessories complete.
41Erection of 8 SWG G.I. wire (4 mm) for earth connectivity
42Erection of ¾ th inch dia. Polythin Pipe
43Erection of 1 (one) no. RCC piler base of size 1.5x2.0x0.75 mtr including supply of all materials
44Erection of 120 sqmm bi- metalic lugs
45Erection of Galvanised Bkt. Clamp (50x6 mm)
46Erection of Galvanised Stay Clamp (50x6 mm)
47Supplying of 11 KV U.G.,240 sq. mm. 3C, TR-XLPE insulated conductor and insulation screened Aluminium conductor Power cable as per IS : 7098/II/1985 ans latest amendments incl. taxes , duties,freight & insurance etc as per technical spec of the Bid document.
48Outdoor type Heat Shrink Jointing kit suitable for 240 sq. mm. 3XC, XLPE UG cable
49Indoor type heat shrink cable jointing kit size of 240 sqmm 3XC, XLPE UG cable.
50Supply of HT kiosk/11 Kv outdoor type feeder piller made of 10SWGMS sheet complete with aluminium busbar, HT insulator etc sa required provided with Rocking System with ID marking with G specialUG line and panting to be fitted on structure of M SAngle(65x65x6mm) and flat(50X6 mm) as required and concreting of ratio 1:2:4(0.054cum/leg) with excavation of earth centering shuttering & disposal of excess soil.
519.0 mtr long galvenised steel tubular pole
52Galvanised Stay set complete
53Stay Insulator (HT)
54Stander Stay Wire
5511 KV G.O.. Set
5611 KV Pin Insulator with GI Pin
5711 KV Danger Board
58Galvanised 75x40x40x6 mm M.S. Channel
59Galvanised M.S. Angle (65x65x6 mm)
60GI Bkt. Clamp (50x6 mm)
61GI Stay Clamp (50x6 mm)
62GI Nuts & bolts of assorted size
632.5 mtr. long 40 mm dia. G.I. pipe for earthig of O.H. cable termination point
648 SWG G.I. wire (4 mm) for earth connectivity
65¾ th inch dia. Polythin Pipe
66100 mm. dia. TATA/JINDAL/ BANSAL make best quality G.I. pipe as per IS:1239 (as per price list)
67Supply of 11 KV,800 Amps continuos rated current, 350 MVA rupturing capacity Indoor Vaccum Circuit Breaker ( for outgoing feeder), complete with 1 set of CT of ratio 200/1.5 Control & Relay Pannel Simplex type with 110 Volt DC actuated electrical closing/ tripping mechanism and internal wiring , 2-Over current & 1-earth fault combined micom digital relay, 1 no electromechanical AREVA Master Trip Realy auxiliary relays as required, 1 no. L& T / SECURE make "Tri-Vector" Meter (SCADA compatible), 3 Ammeter, 1 Voltmeter, 1 C.T opareted static KW meter, with panel bus mounted C.T and integal earthing facility including inemal arc tested panel Conforming to relevant ISS/IEC as reqd. including standard indication facilities as per reqirment detyailed herein after.
68Supply of 11 kv Ring Main Unit : 12 KV motorrised ringmain unit, self power typewith CPT or by other means, solid or SF6 installation, outdoor enclouser, FPI, battery and charging system, software, all accessories and tools as provided in technical specification 3 way RMU Type SBBBSS.
69Laying & commisioning of 3XC, 240 Sqmm, 6.35/11KV, XLPE insulated armoured HT power cable direct into earth including excavation of earth up-to a depth of 1100 mm (Width of the trench 40 cm) including 1st class brick protection of two layer flat brick soling, 300 mm. sand (river sand) cushoning and refilling and ramming the excavated soil and also make devider by layig of bricks to protect both the cables as per direction of the EIC.
70Erection of HT kiosk/11 Kv outdoor type feeder piller made of 10SWGMS sheet complete with aluminium busbar, HT insulator etc sa required provided with Rocking System with ID marking with G specialUG line and panting to be fitted on structure of M SAngle(65x65x6mm) and flat(50X6 mm) as required and concreting of ratio 1:2:4(0.054cum/leg) with excavation of earth centering shuttering & disposal of excess soil.
71Fitting, fixing of outdoor type Heat Shrink Jointing kit suitable for 240 sq. mm. 3XC, XLPE UG cable
72Earth work in excavation in foundation trenches not exceeding 1.2m in depth. On plan or drains not exceeding 0.5 width . On plan including dressing of sides and ramming of bottoms, lift upto 1.5m including getting out the excavated soil.
73Filling in plinth with sand under floors including watering, ramming , consolidating and dressing complete.
74Fitting, fixing of Indoor type heat shrink cable jointing kit size of 240 sqmm 3XC, XLPE UG cable.
75Erection of 9.0 mtr long galvenised steel tubular pole
76Erection of Stay set complete
77Erection of Stay Insulator (HT)
78Erection of Stander Stay Wire
79Erection of 11 KV G.O.. Set
80Erection of 11 KV Pin Insulator with GI Pin
81Erection of Galvenised 75x40x40x6 mm M.S. Channel
82Erection of Galvenised M.S. Angle (65x65x6 mm)
83Erection of Galvanised Bkt. Clamp (50x6 mm)
84Erection of Galvanised Stay Clamp (50x6 mm)
85Excavation, erection, testing & commissioning of 40mm dia, 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover plates on GI frame, charcoal, salt and other accessories complete.
86Erection of 8 SWG G.I. wire (4 mm) for earth connectivity
87Laying of 100 mm. dia. TATA/JINDAL/ BANSAL make best quality G.I. pipe as per IS:1239 (as per price list)
88Erection of 11 KV,800 Amps continuos rated current, 350 MVA rupturing capacity Indoor Vaccum Circuit Breaker ( for outgoing feeder), complete with 1 set of CT of ratio 200/1.5 Control & Relay Pannel Simplex type with 110 Volt DC actuated electrical closing/ tripping mechanism and internal wiring , 2-Over current & 1-earth fault combined micom digital relay, 1 no electromechanical AREVA Master Trip Realy auxiliary relays as required, 1 no. L& T / SECURE make "Tri-Vector" Meter (SCADA compatible), 3 Ammeter, 1 Voltmeter, 1 C.T opareted static KW meter, with panel bus mounted C.T and integal earthing facility including inemal arc tested panel Conforming to relevant ISS/IEC as reqd. including standard indication facilities as per reqirment detyailed herein after.
89Cable identification marker: Providing of pre-cast cement concrete cable identification route marker (1 cement: 2 sand : 4 graded stone aggregrate 6 mm nominal size) reinforced with 1.6 mm dia mild steel wire including centering and shuttering, roughening cleaning, fixing and finishing in cement morter 1:3 (1 cement: 3 fine sand) etc. complete, excluding the plastering of jambs, sills and soffits as per design, drawing and specification of TSECL. The marker shall be embossed " DANGERS: TSECL, 11KV Power cable" with black colour letter (Both side). The vissible part shall be painted with yellow colour Japan Paint.
90Erection, testing & commissioning of 11 kv Ring Main Unit : 12 KV motorrised ringmain unit, self power typewith CPT or by other means, solid or SF6 installation, outdoor enclouser, FPI, battery and charging system, software, all accessories and tools as provided in technical specification 3 way RMU Type SBBBSS with appropriate civil work.
Disclaimer :