Tripura State Electricity Corporation Limited-TSECL has published Tender For Providing Dedicated Power Connection To The Sez Jalefa Sabroom Within The Jurisdiction Sabroom Electrical Division Sabroom South Tripura. Submission Date for this Tender is 05-09-2023. Electrification Work Tenders in sabroom Tripura. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supply of 11 KV Outdoor type Metering Panel made out from 3mm sheet duly painted power quoted floor mounting complete with 1 (one) set 11 KV CT, PT combined, 1 (one) no. MS Box, 1 (one) no 1-15 KV volt meter 96x96 mm, 1 (one) no. 6A ammter selector switch, 3 (three) no 110 volt ASC phase indicating lamp, 1(one) no. 1A 3ph 3 wire Electronic Tri vector Meter, 1 (one) no. 96x96 mm 0-100A Ammeter CTR 100/1, 1(one) coil 2.5 mm CU wire as per TSECL Design & Drawing. |
2 | 9.0 mtr long galvenised steel tubular pole(SP-32) |
3 | 11 mtr. long galvenised Steel Tubular pole(SP-57) |
4 | Stay set complete |
5 | A.C.S.R. conductor (Rabbit 50 sq mm) |
6 | G.I. strainded wire (Stay wire) |
7 | Strain insulator ( H.T). |
8 | 11 KV Disc insulator |
9 | 11 KV disc fittings |
10 | 11 KV Pin insulator with GI pin |
11 | Galvanised Channel (75x40x40x6 mm) |
12 | Galvanised Angle (65x65x6 mm) |
13 | 11 KV G.O. Switch |
14 | 11 KV L.A. |
15 | 11 KV D.O.Fuse Set |
16 | 2.5 mtr. long 40 mm dia. G.I. pipe for earthig of O.H. cable termination point |
17 | 8 SWG G.I. wire (4 mm) for earth connectivity |
18 | ¾ th inch dia. Polythin Pipe |
19 | Cement Concreting of Steel pole |
20 | Erection of 1 (one) no. RCC piler base of size 1.5x2.0x0.75 mtr including supply of all materials |
21 | 120 sqmm bi- metalic lugs |
22 | Galvanised Bkt. Clamp (50x6 mm) |
23 | Galvanised Stay Clamp (50x6 mm) |
24 | Galvanised Nuts & Bolts (assorted size) |
25 | Installation of 11 KV Outdoor type Metering Panel made out from 3mm sheet duly painted power quoted floor mounting complete with 1 (one) set 11 KV CT, PT combined, 1 (one) no. MS Box, 1 (one) no 1-15 KV volt meter 96x96 mm, 1 (one) no. 6A ammter selector switch, 3 (three) no 110 volt ASC phase indicating lamp, 1(one) no. 1A 3ph 3 wire Electronic Tri vector Meter, 1 (one) no. 96x96 mm 0-100A Ammeter CTR 100/1, 1(one) coil 2.5 mm CU wire as per TSECL Design & Drawing. |
26 | Erection of 9.0 mtr long galvenised steel tubular pole |
27 | Erection of 11 mtr. long galvenised Steel Tubular pole |
28 | Erection of Stay set complete |
29 | Erection of A.C.S.R. conductor (Rabbit 50 sq mm) |
30 | Erection of G.I. strainded wire (Stay wire) |
31 | Erection of Strain insulator ( H.T). |
32 | Erection of 11 KV Disc insulator |
33 | Erection of 11 KV disc fittings |
34 | Erection of 11 KV Pin insulator with GI pin |
35 | Erection of Galvanised M.S. Channel (75x40x40x6 mm) |
36 | Erection of Galvanised M.S. Angle (65x65x6 mm) |
37 | Erection of 11 KV G.O.. Set |
38 | Erection of 11 KV L.A. |
39 | Erection of 11 KV D.O.Fuse Set |
40 | Excavation, erection, testing & commissioning of 40mm dia, 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover plates on GI frame, charcoal, salt and other accessories complete. |
41 | Erection of 8 SWG G.I. wire (4 mm) for earth connectivity |
42 | Erection of ¾ th inch dia. Polythin Pipe |
43 | Erection of 1 (one) no. RCC piler base of size 1.5x2.0x0.75 mtr including supply of all materials |
44 | Erection of 120 sqmm bi- metalic lugs |
45 | Erection of Galvanised Bkt. Clamp (50x6 mm) |
46 | Erection of Galvanised Stay Clamp (50x6 mm) |
47 | Supplying of 11 KV U.G.,240 sq. mm. 3C, TR-XLPE insulated conductor and insulation screened Aluminium conductor Power cable as per IS : 7098/II/1985 ans latest amendments incl. taxes , duties,freight & insurance etc as per technical spec of the Bid document. |
48 | Outdoor type Heat Shrink Jointing kit suitable for 240 sq. mm. 3XC, XLPE UG cable |
49 | Indoor type heat shrink cable jointing kit size of 240 sqmm 3XC, XLPE UG cable. |
50 | Supply of HT kiosk/11 Kv outdoor type feeder piller made of 10SWGMS sheet complete with aluminium busbar, HT insulator etc sa required provided with Rocking System with ID marking with G specialUG line and panting to be fitted on structure of M SAngle(65x65x6mm) and flat(50X6 mm) as required and concreting of ratio 1:2:4(0.054cum/leg) with excavation of earth centering shuttering & disposal of excess soil. |
51 | 9.0 mtr long galvenised steel tubular pole |
52 | Galvanised Stay set complete |
53 | Stay Insulator (HT) |
54 | Stander Stay Wire |
55 | 11 KV G.O.. Set |
56 | 11 KV Pin Insulator with GI Pin |
57 | 11 KV Danger Board |
58 | Galvanised 75x40x40x6 mm M.S. Channel |
59 | Galvanised M.S. Angle (65x65x6 mm) |
60 | GI Bkt. Clamp (50x6 mm) |
61 | GI Stay Clamp (50x6 mm) |
62 | GI Nuts & bolts of assorted size |
63 | 2.5 mtr. long 40 mm dia. G.I. pipe for earthig of O.H. cable termination point |
64 | 8 SWG G.I. wire (4 mm) for earth connectivity |
65 | ¾ th inch dia. Polythin Pipe |
66 | 100 mm. dia. TATA/JINDAL/ BANSAL make best quality G.I. pipe as per IS:1239 (as per price list) |
67 | Supply of 11 KV,800 Amps continuos rated current, 350 MVA rupturing capacity Indoor Vaccum Circuit Breaker ( for outgoing feeder), complete with 1 set of CT of ratio 200/1.5 Control & Relay Pannel Simplex type with 110 Volt DC actuated electrical closing/ tripping mechanism and internal wiring , 2-Over current & 1-earth fault combined micom digital relay, 1 no electromechanical AREVA Master Trip Realy auxiliary relays as required, 1 no. L& T / SECURE make "Tri-Vector" Meter (SCADA compatible), 3 Ammeter, 1 Voltmeter, 1 C.T opareted static KW meter, with panel bus mounted C.T and integal earthing facility including inemal arc tested panel Conforming to relevant ISS/IEC as reqd. including standard indication facilities as per reqirment detyailed herein after. |
68 | Supply of 11 kv Ring Main Unit : 12 KV motorrised ringmain unit, self power typewith CPT or by other means, solid or SF6 installation, outdoor enclouser, FPI, battery and charging system, software, all accessories and tools as provided in technical specification 3 way RMU Type SBBBSS. |
69 | Laying & commisioning of 3XC, 240 Sqmm, 6.35/11KV, XLPE insulated armoured HT power cable direct into earth including excavation of earth up-to a depth of 1100 mm (Width of the trench 40 cm) including 1st class brick protection of two layer flat brick soling, 300 mm. sand (river sand) cushoning and refilling and ramming the excavated soil and also make devider by layig of bricks to protect both the cables as per direction of the EIC. |
70 | Erection of HT kiosk/11 Kv outdoor type feeder piller made of 10SWGMS sheet complete with aluminium busbar, HT insulator etc sa required provided with Rocking System with ID marking with G specialUG line and panting to be fitted on structure of M SAngle(65x65x6mm) and flat(50X6 mm) as required and concreting of ratio 1:2:4(0.054cum/leg) with excavation of earth centering shuttering & disposal of excess soil. |
71 | Fitting, fixing of outdoor type Heat Shrink Jointing kit suitable for 240 sq. mm. 3XC, XLPE UG cable |
72 | Earth work in excavation in foundation trenches not exceeding 1.2m in depth. On plan or drains not exceeding 0.5 width . On plan including dressing of sides and ramming of bottoms, lift upto 1.5m including getting out the excavated soil. |
73 | Filling in plinth with sand under floors including watering, ramming , consolidating and dressing complete. |
74 | Fitting, fixing of Indoor type heat shrink cable jointing kit size of 240 sqmm 3XC, XLPE UG cable. |
75 | Erection of 9.0 mtr long galvenised steel tubular pole |
76 | Erection of Stay set complete |
77 | Erection of Stay Insulator (HT) |
78 | Erection of Stander Stay Wire |
79 | Erection of 11 KV G.O.. Set |
80 | Erection of 11 KV Pin Insulator with GI Pin |
81 | Erection of Galvenised 75x40x40x6 mm M.S. Channel |
82 | Erection of Galvenised M.S. Angle (65x65x6 mm) |
83 | Erection of Galvanised Bkt. Clamp (50x6 mm) |
84 | Erection of Galvanised Stay Clamp (50x6 mm) |
85 | Excavation, erection, testing & commissioning of 40mm dia, 3000 mm long GI pipe earth electrode with test link, RCC pit, RCC cover plates on GI frame, charcoal, salt and other accessories complete. |
86 | Erection of 8 SWG G.I. wire (4 mm) for earth connectivity |
87 | Laying of 100 mm. dia. TATA/JINDAL/ BANSAL make best quality G.I. pipe as per IS:1239 (as per price list) |
88 | Erection of 11 KV,800 Amps continuos rated current, 350 MVA rupturing capacity Indoor Vaccum Circuit Breaker ( for outgoing feeder), complete with 1 set of CT of ratio 200/1.5 Control & Relay Pannel Simplex type with 110 Volt DC actuated electrical closing/ tripping mechanism and internal wiring , 2-Over current & 1-earth fault combined micom digital relay, 1 no electromechanical AREVA Master Trip Realy auxiliary relays as required, 1 no. L& T / SECURE make "Tri-Vector" Meter (SCADA compatible), 3 Ammeter, 1 Voltmeter, 1 C.T opareted static KW meter, with panel bus mounted C.T and integal earthing facility including inemal arc tested panel Conforming to relevant ISS/IEC as reqd. including standard indication facilities as per reqirment detyailed herein after. |
89 | Cable identification marker: Providing of pre-cast cement concrete cable identification route marker (1 cement: 2 sand : 4 graded stone aggregrate 6 mm nominal size) reinforced with 1.6 mm dia mild steel wire including centering and shuttering, roughening cleaning, fixing and finishing in cement morter 1:3 (1 cement: 3 fine sand) etc. complete, excluding the plastering of jambs, sills and soffits as per design, drawing and specification of TSECL. The marker shall be embossed " DANGERS: TSECL, 11KV Power cable" with black colour letter (Both side). The vissible part shall be painted with yellow colour Japan Paint. |
90 | Erection, testing & commissioning of 11 kv Ring Main Unit : 12 KV motorrised ringmain unit, self power typewith CPT or by other means, solid or SF6 installation, outdoor enclouser, FPI, battery and charging system, software, all accessories and tools as provided in technical specification 3 way RMU Type SBBBSS with appropriate civil work. |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy