National Security Guard-NSG has published Tender For Maintenance Of Security And Street Light Including Cables And Distribution Panels In Mmc-1 For The Year 2023 24 Sh Repair And Maintenance Of Distribution Panels Lt Feeders Junction Boxes 11 Kv 1.1 Kv Grade Cable Power Distribution Network. Submission Date for this Tender is 31-08-2023. Distribution Box Tenders in manesar Haryana. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
2 | 2 x 16 sq mm |
3 | 2 x 25 sq mm |
4 | 3.5 x 35 sq mm |
5 | 3.5 x 70 sq mm |
6 | 3.5 x 120 sq mm |
7 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing RCC/ HUME/ METAL/ DWC/PVC pipe as required. |
8 | 2 x 16 sq mm |
9 | 2 x 25 sq mm |
10 | 3.5 x 35 sq mm |
11 | 3.5 x 70 sq mm |
12 | 3.5 x 120 sq mm |
13 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size in the existing masonry open duct / along pole / loose /loop/ in panel for connections etc as required. |
14 | 2 x 16 sq mm |
15 | 2 x 25 sq mm |
16 | 3.5 x 35 sq mm |
17 | 3.5 x 70 sq mm |
18 | 3.5 x 120 sq mm |
19 | 3.5 x 300 sq mm |
20 | 3.5 x 400 sq mm |
21 | Supplying, Laying and fixing of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 1.1 kV grade , confirming to IS : 7098 (Part-1) 1988 of following size on wall surface as required. |
22 | 2 x 16 sq mm |
23 | 2 x 25 sq mm |
24 | 3.5 x 35 sq mm |
25 | 3.5 x 70 sq mm |
26 | 3.5 x 120 sq mm |
27 | Providing and fixing following rating and breaking capacity and pole MCCB with Microprocessor release with overload, short circuit and earth fault protection and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
28 | 250 A, 36 KA, FP MCCB, Ics= 100% of Icu |
29 | 250 A, 50 KA, FP MCCB,Ics= 100% of Icu |
30 | 400 A, 50KA, FP MCCB,Ics= 100% of Icu |
31 | 630 A, 50KA, FP MCCB,Ics= 100% of Icu |
32 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
33 | 100A, 16 KA/18KA, TP MCCB |
34 | 250 A, 35 KA, TP MCCB, Ics= 100% of Icu |
35 | 400 A, 35 KA, TP MCCB, Ics= 100% of Icu |
36 | 125 A, 36KA, FP MCCB,Ics= 100% of Icu |
37 | 250 A, 36KA, FP MCCB,Ics= 100% of Icu |
38 | 400 A, 50KA, FP MCCB,Ics= 100% of Icu |
39 | 630 A, 50KA, FP MCCB,Ics= 100% of Icu |
40 | Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required. |
41 | Providing and laying in position cement concrete 1:2:4 (1cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) for the repair of the road after cutting of road for cable repair and laying. |
42 | Providing and making steel pole collar with cement concrete (1 cement : 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to be deducted) |
43 | Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required. [Make-Zenith/TATA/Jindal-hisar/Prakash- Surya] |
44 | 32 mm dia |
45 | 40 mm dia |
46 | Dismantling of metallic junction box of street/outdoor light poles fixed with nut bolts, clamps including credit for same etc as complete as required. |
47 | Dismantling of non-metallic junction box of street/outdoor light poles fixed with nut bolts, clamps including credit for same etc as complete as required. |
48 | Supplying and fixing of 32 mm dia X 2.00 metres long G.I. pipe (medium class) bracket for mounting of fluorescent / HPMV / HPSV street light fitting on pole/ wall including bending the pipe to the required shape, 2 nos 40 mm X 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc. as required. |
49 | Supplying and fixing sheet steel Enclosure suitable for125A TP&N MCCB , on surface/ recess, complete with neutral Link,powder painted including earthing etc. as required. (But without MCCB) |
50 | Supplying, installation, testing, commissioning & erection of 6 metres longcontinously tapered Hot-dip Galvanized octagonal street light poles with top dia. 70 mm and bottom dia. 130 mm made of 3 mm thick sheet steel with a base plate of size not less than 200 x 200 x 12 mm, including 4 Nos. 20 mm dia, 600 mm long G.I. foundation bolts with the nuts,with supply and embedding2 Nos. 50 mm dia DWC HDPE pipe sleeve for cable entry, with inbuilt cable end box, supplying fixing 1 nos "C" series 6 amp, 10 KA, SP MCB, including providing fixing DIN rail, 60 amps connectors for termination of2x 25 sq mm incoming and outgoing cables mounted on bakelite sheet, |
51 | including providing foundation of cement concrete 1:1.5:3 (1cement: 1.5 coarse sand: 3 graded stone aggregate 20 mm nominal size) pedestal of size 400 mm x 400 mm x 1400 mm (200mm above ground and 1200 mm below ground) with steel reinforcement(Thermo-Mechanically Treated bars of grade Fe-500D or more) of horizontal tor bar stirrup 8mm dia @150c/c, verticle bars 4 nos, 12 mm dia including excavation as required, including all necessary lugs, earthing terminal etc., complete as required. (Without street light bracket) |
52 | Supplying, installation, testing, commissioning & erection of 7 metres longcontinously tapered Hot-dip Galvanized octagonal street light poles with top dia. 70 mm and bottom dia. 130 mm made of 3 mm thick sheet steel with a base plate of size not less than 200 x 200 x 12 mm, including 4 Nos. 20 mm dia, 600 mm long G.I. foundation bolts with the nuts,with supply and embedding2 Nos. 50 mm dia DWC HDPE pipe sleeve for cable entry, with inbuilt cable end box, supplying fixing 3 nos "C" series 6 amp, 10 KA, SP MCB, including providing fixing DIN rail, 60 amps connectors for termination of2x 25 sq mm incoming and outgoing cables mounted on bakelite sheet, |
53 | including providing foundation of cement concrete 1:1.5:3 (1cement: 1.5 coarse sand: 3 graded stone aggregate 20 mm nominal size) pedestal of size 450 mm x 450 mm x 1700 mm (200mm above ground and 1500 mm below ground) with steel reinforcement of (Thermo-Mechanically Treated bars of grade Fe-500D or more)horizontal tor bar stirrup 8mm dia @190c/c, verticle bars 4 nos, 12 mm dia including excavation as required, including all necessary lugs, earthing terminal etc., complete as required. (Without street light bracket) |
54 | Supplying and fixing of hot-dipped1 metre galvanised M.S. single arm bracket made of 40 mm NB dia. GI pipe with a cap of 300 mm length and of suitable dia to mount on octagonal pole having a top of 70 mm A/F with nut bolts, etc., as required. |
55 | Supplying and fixing of hot-dipped1 metre galvanised M.S. double arm bracket made of 40 mm NB dia. GI pipe with a cap of 300 mm length and of suitable dia to mount on octagonal pole having a top of 70 mm A/F with nut bolts, etc., as required. |
56 | Supply and installation of round bracket (ring type) suitable for mounting four floodlights. The round bracket should be made of 40 dia. (nominal bore) B-Class G.I. pipe on the periphery and four supports (spokes) of 40 mm B-Class G.I. pipe duly welded with a pole cap of 300 mm length at the centre. The pole cap should be of suitable dia for mounting on an existing polygonal pole with a top dia. of 70 mm. The dia. of the round bracket should not be less than 120 cm. The bracket pipes should be suitable for acting as conduits for wires for the wiring of floodlights. The pole cap should have four holes and four numbers of G.I. nuts and bolts for fixing the bracket on the top of the polygonal pole.(drawing will be get approved before fabrication ) |
57 | Supply and drawing of following size PVC insulated, FRLS PVC sheathed copper conductor multi-core flexible cable into the existing street light pole/ PVC / DWC/ steel conduit, making connections, etc. as required, including drawing out the burnt-out wires from the pole if required, etc. as required. |
58 | 3 x 1.5 sq.mm |
59 | 3 x 2.5 sq.mm |
60 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required. |
61 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
62 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
63 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. |
64 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling etc as required. |
65 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required. |
66 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. confirming to IS 14930, part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. |
67 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
68 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
69 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. |
70 | 40 mm dia (OD-40 mm & ID-32 mm nominal) |
71 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
72 | 90 mm dia (OD-90 mm & ID-76 mm nominal) |
73 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. |
74 | Upto 35 sq. mm |
75 | Above 35 sq. mm and upto 95 sq. mm |
76 | Above 95 sq. mm and upto 185 sq. mm |
77 | Above 185 sq. mm and upto 400 sq. mm |
78 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. |
79 | Upto 35 sq. mm |
80 | Above 35 sq. mm and upto 95 sq. mm |
81 | Above 95 sq. mm and upto 185 sq. mm |
82 | Above 185 sq. mm and upto 400 sq. mm |
83 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required |
84 | Upto 35 sq. mm |
85 | Above 35 sq. mm and upto 95 sq. mm |
86 | Above 95 sq. mm and upto 185 sq. mm |
87 | Above 185 sq. mm and upto 400 sq. mm |
88 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. |
89 | Upto 35 sq. mm (clamped with 1mm thick saddle) |
90 | Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) |
91 | Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp) |
92 | Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) |
93 | Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required. |
94 | The road crossings of power cablethrough trenchless boring. Trenchless horizontal boring using Manual/ Machine Moling techniqueat 0.75 metre below the ground level for following size pipes,including survey of under ground utilities,excavation of pits,moling with the hole size not exceeding 20% of the pipe dia,backfilling, compaction and restoration of the pits to original condition etc. as required. The rates for moling, as indicated are inclusive of excavation of pits, backfilling, compaction andrestoration of the pits to original condition. Any damages occurred to other utilities during the Moling operation shall be immediately notified and rectified by the contractor without any cost implication to the Department. The length of the Hole (excluding the sizes of the pits on both ends) shall be considered for the measurement of Moling length. However, intermediate pits will consider in the moling length. i)Upto 200 mm dia DWC HDPE / G.I. /PVC |
95 | The road crossings of power cablethrough trenchless boring. Trenchless horizontal boring using Manual/ Machine Moling techniqueat 1.20 metre below the ground level for following size pipes,including survey of under ground utilities,excavation of pits,moling with the hole size not exceeding 20% of the pipe dia,backfilling, compaction and restoration of the pits to original condition etc. as required. The rates for moling, as indicated are inclusive of excavation of pits, backfilling, compaction andrestoration of the pits to original condition. Any damages occurred to other utilities during the Moling operation shall be immediately notified and rectified by the contractor without any cost implication to the Department. The length of the Hole (excluding the sizes of the pits on both ends) shall be considered for the measurement of Moling length. However, intermediate pits will consider in the moling length. i)Upto 200 mm dia DWC HDPE / G.I. /PVC |
96 | Painting of a street light pole following height including brackets, metal looping box, clamps, etc., fixed on the pole with two or more coats of aluminium paint of an approved brand and manufacture of the required color to give an even shade, including scraping, finishing the surface, applying a coat of red oxide, and finally numbering the pole with black and yellow synthetic enamel paint as per directions of the engineer-in-charge, etc., complete as required. (Primer: Asian Paints, Berger, and Nerolac make Asian Paints 3 Mangoes Aluminium Paint or a similar from Berger or Nerolac.) |
97 | Pole height above ground above 5 metre and upto 7 metre. |
98 | Pole height above ground above 7 metre and upto 10 metre. |
99 | Painting of panel boards, feeder pillars, junction box and cubical panel with 2 or more coats of synthetic enamel paint of an approved brand and manufacture of the required colour to give an even shade, including scrapping, finishing the surface etc., complete as required. ( Apcolite premium enamel paintof Asian paint or a similar of Berger or Nerolac). |
100 | Supply, installation, testing, and commissioning of a double door type, outdoor type, totally enclosed IP54, dust and vermin proof, powder-coated in an approved Siemens grey shade after 7 tank treatment processes, pedestal-mounted cubical type LT panel. The panel with the required front area (but not less than 1.08 sqm) and a depth of 400 mm, fabricated in a compartmentalised design from 2 mm CRCA sheet steel with fully openable front and back doors with locking arrangements and required gaskets, and a tapered top (roof). The feeder pillar should be complete with 200 amps, 4 strip copper bus bars with heat-shrinkable coloured sleeves, bus bar support at required intervals, control terminals and suitably sized terminal blocks for incoming and outgoing cables,including providing interconnections / power wiring with 16 sq.mm copper flexible cable., the wiring for the control circuit shall be carried out using 1.5 sq.mm flexible copper cable, |
101 | the entire panel shall have one common copper bar of size 20 mm x 5 mm at the rear with 2 earth studs/terminals,including detachable cable gland plates made of 3 mm thick CRCA sheet, suitable for operation on a 433 volt, 50 Hz, 3 phase, 4 wire A. C. supply system complete as required. and suitable size M.V. Danger Boards shall be fixed on the panel. The feeder pillar should be complete with a mounting frame made of 50 mm x 50 mm x 6 mm angle iron with 900 mm long legs. The 4 legs of the feeder pillar shall be erected on a suitable size of 1:3:6 cement concrete (1:3:6 cement; 3 sand; 6 graded stones of 20 mm size) pedestal having 900mm of depth (600mm below ground and 300mm above ground). The feeder pillar shall have provision to accommodate the following switch gears, as mentioned below in Item No. 39 (The drawing will be approved before the fabrication of the panel.) |
102 | Providing and fixing following switch gears, meters and accessoriesin existing cubicle panel board including drilling holes in cubicle panel, making connections, testing etc. as required. |
103 | 63 Amps , FP, MCCB, 25 KA breaking capacity , Ics = 100% Icu with Adjustable overloadand fixedshort-circuit protection, Spreaders Terminals and Direct Rotary handle. (Incomer) |
104 | 3Ph LED Ammeter Cl 1 with Inbuilt selector switch for 3 phases. |
105 | 3Ph LED Voltmeter Cl 1 (0-500V) with Inbuilt selector switch for 3 phases. |
106 | CTs 100/ 5 amps, 5VA with class 1.0 accuracy. |
107 | LED Indicator Red, 240V AC. |
108 | LED Indicator Yellow, 240V AC. |
109 | LED Indicator Blue, 240V AC. |
110 | 240 VAC Astronomical digital time switchDIN Mountingtype |
111 | 6 amps, 10 KA,240 V,"C" curveSPMCB |
112 | 3 Pole, 415 V,Power Contactor AC3 dutyRating40 A. |
113 | Auto manual switch . |
114 | 5 A to 32 A,10 KA,240 V, "C" curveDPMCB. (OUTGOING) |
115 | Supply, Installation, Testing and commissioning of outdoor type totally enclosed, dust and vermin proof, pedestal mounted INSPECTION BOX / JUNCTION BOX of a suitable size but not less than 600 mm wide X 450 mm height X 450 mm (deep) fabricated from 2 mm thick CRCA sheet steel having front and back openable doors with locking arrangement on both sides, tapered top (roof), including detachable cable gland plates made of 3 mm thick CRCA sheet, including pre-paint treatment, phosphating and powder coating by approved Siemens grey paint, consisting of 300 Amps 4 strip aluminium bus bars with heat-shrinkable coloured sleeves and including DMC / SMC bus bar supports at required intervals, etc. as required, |
116 | suitable for operation on 433 volts, 50 Hz, 3-phase, 4-wire A.C. supply system, the entire panel shall have one common G.I. bar of size 25 mm x 5 mm at the rear with 2 earth studs or terminals, a danger notice plate fixed, etc., complete as required. The feeder pillar should be complete with a mounting frame made of 50 mm x 50 mm x 6 mm angle iron with 900 mm long legs. The 4 legs of the feeder pillar shall be erected on a suitable size 1:3:6 cement concrete (1:3:6 cement; 3 sand; 6 graded stones of 20 mm size) pedestal having 900mm of depth (600mm below ground and 300mm above ground). |
117 | Supply, Installation, Testing and commissioning of outdoor type totally enclosed, dust and vermin proof, pedestal mounted INSPECTION BOX / JUNCTION BOX of a suitable size but not less than 600 mm wide X 600 mm height X 450 mm (deep) fabricated from 2 mm thick CRCA sheet steel having front and back openable doors with locking arrangement on both sides, tapered top (roof), including detachable cable gland plates made of 3 mm thick CRCA sheet, including pre-paint treatment, phosphating and powder coating by approved Siemens grey paint, consisting of 500 Amps 4 strip aluminium bus bars with heat-shrinkable coloured sleeves and including DMC / SMC bus bar supports at required intervals, etc. as required, |
118 | suitable for operation on 433 volts, 50 Hz, 3-phase, 4-wire A.C. supply system, the entire panel shall have one common G.I. bar of size 25 mm x 5 mm at the rear with 2 earth studs or terminals, a danger notice plate fixed, etc., complete as required. The feeder pillar should be complete with a mounting frame made of 50 mm x 50 mm x 6 mm angle iron with 900 mm long legs. The 4 legs of the feeder pillar shall be erected on a suitable size 1:3:6 cement concrete (1:3:6 cement; 3 sand; 6 graded stones of 20 mm size) pedestal having 900mm of depth (600mm below ground and 300mm above ground). |
119 | Supplying and fixing polycarbonate weatherproof, IP66 outdoor type cable junction box with minimum dimensions of205 mm x 255 mm x 112 mm on a pole, complete with the following accessories fixed in, and two sets of 25 mm x 3 mm GI clamps with G. I. bolts, nuts and washers, for mounting on a street light pole, including connections etc., complete as required. i) Din-rail suitable for fixing the following accessories-1 Nos. ii) Feedthrough terminals 100 A-4 Nos with endplate as required. iii) shorting link -2 Nos. v) End Clamps -2 Nos vi) SP MCB"C" curve, 10KA, 6 A - 1Nos. v) PVC Cable Gland- 2 Nos Junction box make: (MakeHensel KF 2500G/ Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO) Terminal Bock: Connect well/Elmex/ Phoenix/ Wago/ Essen Cable Gland : Hensel/ Dowells/ Barco/ Connectwell/ Elmex /Eaton/ Legrand /Trinity Touch |
120 | Providing and fixing following capacity4 pole, 415 V, category AC-23A. On Load Change Over Switch,in sheet steel enclosure in existingpanel board /wall including drilling holes, making connections, etc. as required. ( Make:-L& T /Socomec / Legrand /ABB /Schneider/ Siemen) |
121 | 125 A,four Pole. |
122 | Providing and fixing following capacity 4 pole, 415 V, category AC-23A. On Load Change Over Switch,in open execution in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. ( Make:-L& T /Socomec / Legrand /ABB /Schneider/ Siemen) |
123 | 315 A,four Pole. |
124 | 400 A, four Pole. |
125 | 630 A, four pole. |
126 | Supplying and fixing PVCweatherproof20 A, 240 V,Switchbox, IP66,complete with one 20 A switch on surface or in recess, complete with connections, testing and commissioning etc. as required. (Crabtree ACWCDIW201 /Hensel/ Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO) |
127 | Supplying and fixing PVCWeatherproofIP65, 4 module MCB distribution board, 240 volts, on surface/ recess, complete with din bar etc. as required. (But without MCB/RCCB/Isolator) ( Legrand Plexo³ boxes for DX³ 4 Module 601994 /Hensel / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO) |
128 | Supplying and fixing PVCweatherproof, IP66, 16 A, 240 V,switch and Socketbox, IP66,complete with one 16 A switch and socket on surface or in recess, complete with connections, testing and commissioning etc. as required. (Crabtree ACWCKXW163/ Hensel/ Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO) |
129 | Supplying and fixing polycarbonate weatherproof, IP66 outdoor type cable junction box with minimum dimensions of 155 mm x 210 mm x 92 mm on surface or recess, including connections etc., complete as required. ( Hensel KF 1600G/Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO) |
130 | Supplying and fixing polycarbonate weatherproof, IP66 outdoor type cable junction box with minimum dimensions of 205 mm x 255 mm x 112 mm on surface or recess,including connections etc., complete as required. (Hensel KF 2500G / Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO) |
131 | Supplying and fixing Cable Junction Boxes, IP 66 weatherproof, size 155 mm x 210 mm x 92 mm with 5 Nos two-way terminals mounted on DIN rail suitable for termination of 16 sq mm cable, on the surface or in recess, complete, etc. as required.) (MakeHensel KF 1616G/ Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO/SCHNEIDER ) |
132 | Supplying and fixing Cable Junction Boxes, IP 66 weatherproof, with 5 Nos two-way terminals mounted on DIN rail suitable for termination of 4 sq mm cable, on the surface or in recess, complete, etc. as required.) (MakeHensel KF 0404G/ Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON/OBO/SCHNEIDER ) |
133 | Supplying and fixing feed through terminal 100 A in the existing looping box/junction box, including connection, etc., as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
134 | Supplying and fixing feed through terminal 75 A in the existing looping box/junction box, including connection, etc., as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
135 | Supplying and fixingshorting link suitable for 75 A feed through terminals in existing looping box/junction box, etc. as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
136 | Supplying and fixingshorting link suitable for 100 A feed through terminals in existing looping box/junction box, etc. as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
137 | Supplying and fixing end plates for 75A feed through terminals in existing looping boxes/ junction boxes, etc. as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
138 | Supplying and fixing end plates for 100A feed through terminals in existing looping boxes/ junction boxes, etc. as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
139 | Supplying and fixing End Clamps for feed-through terminals on the existing DIN rail in the existing looping box/ junction boxes, etc. as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
140 | Supplying and fixing din rail mounted earth terminal suitable for 4 sq mm wire in the existing looping box/junction box, including connection, etc., as required. (Connect well/Elmex/ Phoenix/ Wago/ Essen) |
141 | Supplying and fixing a PVC cable gland suitable for up to 6 sq mm of copper conductor cable in the existing polycarbonate cable junction box, including connections, etc. as required.(Hensel/ Dowells/ Barco/ Connectwell/ Elmex /Eaton/ Legrand) |
142 | Supplying and fixing a PVC cable gland suitable for 2 x 10/ 16 sq mm armoured XLPE cable in the existing polycarbonate cable junction box, including connections, etc. as required.(Hensel/ Dowells/ Barco/ Connectwell/ Elmex /Eaton/ Legrand/Trinity Touch) |
143 | Supplying and fixing a PVC cable gland suitable for 2 x 25 sq mm armoured XLPE cablein the existing polycarbonate cable junction box, including connections, etc. as required. (Hensel/ Dowells/ Barco/ Connectwell/ Elmex /Eaton/ Legrand/Trinity Touch) |
144 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
145 | 63 A |
146 | Location, tracing and pin-pointing of faults in existing 1.1 KV and 11KV grade underground cables, including disconnection of the cable at both ends, finding the route of the cable, excavation at the fault point to make the fault point visible, making temporary joints ( in case of LT cable), testing the cable on load for three hours, including refilling the excavated trench and cleaning the site, etc. as required. [Permanent joints are paid separately ]. |
147 | Removing of following size old defective armouredPVC insulated and PVC sheathed / XLPE power cable from exisitng RCC/ HUME/METAL/ cable entry pipe of thepole collar/ foundation etc. as required. i) upto 35 sq mm |
148 | Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc. as required ( Zenith/TATA/Jindal-hisar/Prakash- Surya make) |
149 | 50 mm dianominal bore |
150 | 80 mm dia nominal bore |
151 | 100 mm dia |
152 | 150 mm dia nominal bore |
153 | Supplying and laying of G.I. pipe of 50 mm dia.(nominal),medium class, ISI markedinwall / floorincluding cuttingchase, and making good the wall/ floor and finishing with matching surface after housing G.I. pipe in chase. ( for protection of UG cable) |
154 | Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. |
155 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
156 | Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge. |
157 | Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix) |
158 | Nominal concrete 1:4:8 or leaner mix (i/c equivalent design mix) |
159 | Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set, panel etc including form work etc as required. |
160 | Providing and laying cement concrete in kerbs, steps and the like at or near ground level excluding the cost of centering, shuttering and finishing. |
161 | 1:1½:3 (1 Cement: 1½ coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources) |
162 | Supplying and fixing din rail mounted disconnecting Terminal with end palte suitable for 6 sq mm wire in the existing looping box/junction box, including connection, etc., as required. |
163 | Cutting road and making good the same including supply of extra quantities of materials i.e. aggregate, moorum screening, red bajri and labour required. |
164 | Bituminous portion |
165 | Excavation for cable trenches in soft soil, depth upto 1.2 m including dressing of sides lift upto 1.5 m, including getting out the excavated soil, refilling with sand and or good soil after laying of cable/ pipe etc in layers of 20 cm, ramming, watering and disposal of surplus excavated soil as directed, within a lead of 50 metres. |
166 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. direct in the ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering, including dismantling of the existing underground cable of size 2 x 16 sq mm cable laid in the trench and credit for same etc., complete as required. |
167 | 63 mm dia (OD-63 mm & ID-51 mm nominal) |
168 | Supplying and Laying of one number aluminium conductor, XLPE Insulated, PVC sheathed, armoured power cable of 11 KV (Earthed) grade Conforming to IS 7098 (Part-2) with upto date amendments of following size in the existing masonry open duct as required. |
169 | 3 x 120 sq. mm |
170 | 3 x 150 sq. mm |
171 | 3 x 185 sq. mm |
172 | 3 x 240 sq. mm |
173 | 3 x 300 sq. mm |
174 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. [Make-Raychem/3M/M-seal] |
175 | 2 X 16 sq. mm |
176 | 2 X 25 sq. mm |
177 | 3½ X 35 sq. mm |
178 | 3½ X 50 sq. mm |
179 | 3½ X 70 sq. mm |
180 | 3½ X 95 sq. mm |
181 | 3½ X 120 sq. mm |
182 | 3½ X 150 sq. mm |
183 | 3½ X 185 sq. mm |
184 | 3½ X 240 sq. mm |
185 | 3½ X 300 sq. mm |
186 | 3½ X 400 sq. mm |
187 | Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
188 | 240 sq. mm |
189 | 300 sq. mm |
190 | Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required |
191 | 240 sq. mm |
192 | 300 sq. mm |
193 | Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : |
194 | 240 sq. mm |
195 | 300 sq. mm |
196 | Fabrications, supplying and fixing of covers of the required shape and size in the existing electrical cubical panel boards/distribution boards/ feeder pillars /pole box at different locations made out from 2 mm thick CRCA sheet with locking arrangement, hinges and matching with the existing doors of the panel including painting with an approved shade of two coats of synthetic enamel paint over an undercoat of steel primer etc., complete as required. |
197 | Providing and installing a heavy-duty 3-inch weld on Barrel metal Hinge on the doors of existing Indoor/Outdoor LT-panel/Feeder Doors by means of welding and painting the entire weld-affected surface with 2 or more coats of synthetic enamel paint after 1 coat of red oxide to match the finishing of the weld-affected area to the adjacent surface, etc., as required. |
198 | Providing and fixing universal type SS door lock mechanism for existing Indoor/Outdoor LT-panel/Feeder Doors including making holes, ensuring its tight placement without any free-play by way of suitable rubber/solvent seals etc as required |
199 | Providing & fixing 3 mm thick CRCA gland plate of required size, duly treated and painted, in existing indoor/outdoor LT panel/feeder/Junction feeder box and making necessary holes in the gland plate for management of the existing cables in the panel/feeder, including taking out the existing gland, lugs, cables and re-fixing etc., as required. [Lugs/Thimbles or glands, if required, will be paid separately] |
200 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. [Make-Comet/Hex/Dowells/Jainson] |
201 | 2 X 16 sq. mm (22mm) |
202 | 2 X 25 sq. mm (22mm) |
203 | 3½ X 35 sq. mm (32mm) |
204 | 3½ X 50 sq. mm (35mm) |
205 | 3½ X 70 sq. mm (38mm) |
206 | 3½ X 95 sq. mm (45mm) |
207 | 3½ X 120 sq. mm (45mm) |
208 | 3½ X 150 sq. mm (50mm) |
209 | 3½ X 185 sq. mm (57mm) |
210 | 3½ X 240 sq. mm (62mm) |
211 | 3½ X 300 sq. mm (70mm) |
212 | 3½ X 400 sq. mm (82mm) |
213 | Supplying and embedding following sizePVC conduit (medium class)in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required. |
214 | 32 mm dia. |
215 | 50 mm dia. |
216 | Providing and erection of G.I. pipe medium class of the following diameter in the existing gate pillar for fixing the post-top lantern, including making holes and embedding the required length of the pipe in the pillar top, and making good the damage with matching concrete, plastering, and painting after the erection of the pipe, etc., complete as per the direction of the engineer-in-charge. |
217 | G.I. pipe 50 mm dia |
218 | G.I. pipe 65 mm dia |
219 | Supply, installation, testing and commissioning of 25 watts LED-based post top luminaires, IP 65, with Die-cast aluminium spigot housing and complete with diffuser, LED module, electronic driver and all other accessories, having minimum system luminous efficacy of 95 lm/W, on existing street light pole/gate including connection etc. as required. Make :CORAL (Opal)or RUBY (Clear) of Havells similarin Philips / Havells/ Wipro/ Bajaj |
220 | Supply, installation, testing and commissioning of 40 watts /45 watts LED-based post top luminaires, IP 65, with Die-cast aluminium spigot housing and complete with diffuser, LED module, electronic driver and all other accessories, having minimum system luminous efficacy of 95 lm/W, on existing street light pole/gate including connection etc. as required. Make :CORAL (Opal)or RUBY (Clear) of Havells similarin Philips / Havells/ Wipro/ Bajaj |
221 | Supplying, installation, testing, and commissioning of 10 to 11 Watt, 600 mm (nominal size) LED Bollard Light fitting complete with LED module, electronic driver, diffuser, and all other accessories, minimum system luminous efficacy of 80 lm/W,the bollard housing should be made up of metallic pipe duly powder coated with the mounting flange at the bottom, including providing3 nos M10 foundation bolts, two numbers 32 mm. dia PVC pipe for cable entry (from the bottom of the foundation to the top of the foundation for cable entry),and providing the foundation of Cement concrete 1:3:6 (1 cement : 3 coarse sand: 6 graded stone aggregate 20 mm nominal size ) of size 0.3-metre dia and750 mm height (250mm above ground and 500 mm below ground) including excavation as required and complete with connections, lugs, terminals, connectors for the connection of cable and wires in the fitting etc., complete as required. |
222 | Supplying, installation testing, and commissioning100 W highbay LED luminaire, complete with driver, LEDs with optical lenses, toughened glass cover, mounting bracket, and pressure-die-cast aluminium alloy housing, including installation of luminaire on the ceiling, including connections, earthing, providing fixing fasteners, etc., as required. The fixture should have a minimum system efficacy of 140 lumens per watt, ingress protection of IP66, and a mechanical impact resistance rating of IK >= 7. The fixture driver should have an operating voltage range of 140–270 V, surge protection of = 10 KV, and a PF of > 0.9. The fixture shall be designed for a system life of 50,000 hours at 70% lumen maintenance. LM 79 and LM 80 reports need to be submitted from a NABL or UL-accredited lab to verify the above parameters. The contractor shall provide a warranty for the above-LED light fixtures for five years. (Approved Manufacturers: Phillips, Havells, Wipro, and Bajaj, TRILUX) |
223 | Supplying, installation, testing and commissioning of 45 Watt LED street light luminaire made up of die-cast aluminium housing, with IP66 degree of protection, complete with the driver, LEDs with optical lens, toughened glass cover, etc. The luminaire should have suitable for operation on voltage range 140-270V, 1F, 50Hz AC supply system, and a mechanical impact resistance rating of lk>=07. surge protection of = 10KV, PF= 0.90 and minimum system luminous efficacy of 120 lm/W. The luminaire shall be designed for an average system life L70B50: 50000 hours and suitable for mounting on the pole bracket up to outer dia 50 mm, including installation on existing street light pole bracket connections and earthing etc., as required. LM 79 and LM 80 reports need to be submitted from a NABL/UL accredited lab to verify the above parameters. |
224 | Supplying, installation, testing and commissioning of 70 Watt LED street light luminaire made up of die-cast aluminium housing, with IP66 degree of protection, complete with the driver, LEDs with optical lens, toughened glass cover, etc. The luminaire should have suitable for operation on voltage range 140-270V, 1F, 50Hz AC supply system, and a mechanical impact resistance rating of lk>=07. surge protection of = 10KV, PF= 0.90 and minimum system luminous efficacy of 120 lm/W. The luminaire shall be designed for an average system life L70B50: 50000 hours and suitable for mounting on the pole bracket up to outer dia 50 mm, including installation on existing street light pole bracket connections and earthing etc., as required. LM 79 and LM 80 reports need to be submitted from a NABL/UL accredited lab to verify the above parameters. |
225 | Supplying, installation, testing and commissioning of 90 Watt LED street light luminaire made up of die-cast aluminium housing, with IP66 degree of protection, complete with the driver, LEDs with optical lens, toughened glass cover, etc. The luminaire should have suitable for operation on voltage range 140-270V, 1F, 50Hz AC supply system, and a mechanical impact resistance rating of lk>=07. surge protection of = 10KV, PF= 0.90 and minimum system luminous efficacy of 120 lm/W. The luminaire shall be designed for an average system life L70B50: 50000 hours and suitable for mounting on the pole bracket up to outer dia 54 mm, including installation on existing street light pole bracket connections and earthing etc., as required. LM 79 and LM 80 reports need to be submitted from a NABL/UL accredited lab to verify the above parameters. |
226 | Supplying, installation, testing and commissioning of 150 Watt LED street light luminaire made up of die-cast aluminium housing, with IP66 degree of protection, complete with the driver, LEDs with optical lens, toughened glass cover, etc. The luminaire should have suitable for operation on voltage range 140-270V, 1F, 50Hz AC supply system, and a mechanical impact resistance rating of lk>=07. surge protection of = 10KV, PF= 0.90 and minimum system luminous efficacy of 120 lm/W. The luminaire shall be designed for an average system life L70B50: 50000 hours and suitable for mounting on the pole bracket up to outer dia 54 mm, including installation on existing street light pole bracket connections and earthing etc., as required. LM 79 and LM 80 reports need to be submitted from a NABL/UL accredited lab to verify the above parameters. |
227 | Supplying, installation, testing, and commissioning following rating LED floodlight luminaire, complete with driver, LEDs with optical lenses, toughened glass cover, mounting bracket, and pressure-die-cast aluminium housing, including installation of floodlight, on-wall or existing street light pole bracket and connections, earthing, including providing fixing bolts, nuts, and washers, etc., as required. The fixture should have a minimum system efficacy of 120 lumens per watt, ingress protection of IP66, and a mechanical impact resistance rating of IK >=07. The fixture driver should have an operating voltage range of 140–270 V, surge protection of = 10 KV, and a PF of > 0.9. The fixture shall be designed for a system life of 50,000 hours at 70% lumen maintenance. LM 79 and LM 80 reports need to be submitted from a NABL or UL-accredited lab to verify the above parameters. The contractor shall provide a warranty for the above-LED light fixtures for five years. (Approved Manufacturers: Phillips, Havells, Lighting Technology, TRILUX and Bajaj) |
228 | 100 watt flood light |
229 | 150 watt flood light |
230 | 200 watt flood light |
231 | Supply, installation, testing, and commissioning of 5-watt IP 66 LED spike light (red, green, or blue colour) with driver inaluminium housing, complete with connection, etc., as required. |
232 | Supply, installation, testing, and commissioning of 5-watt IP 66 LED spike light (Warm White colour) with driver inaluminium housing, complete with connection, etc., as required. |
233 | Supply, installation, testing, and commissioning of 15-watt IP 66 LED UP-down wall Luminaire with driver in aluminium housing, complete with connection, etc., as required |
234 | Supply, installation, testing, and commissioning of 6-watt IP 67 GROUND BURIAL luminaire in diecast aluminium housing and stainless steel trim, driver,complete with connection, etc., as required. (Philips / Jaquar /Wipro /LT/ Havells) |
235 | Supply, installation, testing, and commissioning of outdoortype3-watt IP 65 LED foot light/ step light inDie cast aluminium housing and Polycarbonate diffuser, complete with connection, etc., as required. (Jaquar LFTL01S003XWor similar in Philips /Wipro /LT/ Havells |
236 | Supplying and fixing following rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB/Panel board complete with connections, testing and commissioning etc. as required |
237 | 40 amps, DP MCB |
238 | 63 amps, DPMCB |
239 | 40 amps, TP&N MCB |
240 | 63 amps, TP&N MCB |
241 | Providing and fixing Din-rail 35 mm on existing paneletc., as require |
242 | Supplying and fixing 2 way, 60 Amp, two way connectorson the existing looping box / Panel board including connection etc as required. |
243 | Providing and fixingG.I. reducer on existing street light pole bracket of size 60 mm x 50 mm with nut and bolts for fixing.(As per sample provided by the department) |
244 | Supplying and fixingBakelite Sheetof following size with screw in the existing looping box/ Panel boardincluding cutting the sheet to required shape and size complete etc as reqd. |
245 | 6 mm thick |
246 | 12 mm thick |
247 | Supplying and fixing 300 Amps capacity aluminium bus bar having nominal current density 130 Amp/sq. cm in the existing panel complete with bus bar supports andinsulated by means of PVC sleeves and holes for connections etc as required. |
248 | Supplying, installation, testing and commissioning of Astronomical time switch of following configuration to be mounted in feeder pillars / Lighting DBs for automatic switching On & OFF of street lights at sun set & sun rise or twilight(Auto ON, Auto OFF, Auto modes) with manual override facility with 12/24 hour display format with suitable battery and indication for relay status i/c programming at site complete as required. |
249 | 1 output per phase and suitable for single phase supply |
250 | 3 output (1output per phase) and suitable for three phase supply |
251 | Providing and fixing 63 Amps , TP, MCCB, 35 KA breaking capacity , Ics = 100% Icu withAdjustable overloadand Adjustable short-circuit protection, Spreaders Terminals in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
252 | Providing and fixing 3 Pole, 415 V,Power Contactor AC3 dutyRating40 A. in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
253 | Supplying and fixing following way, single pole and neutral, PVCWeatherproofIP65, MCB distribution board, 240 volts, on surface/ recess, complete with din bar etc. as required. (But without MCB/RCCB/Isolator). (Make Hensel /Legrand / CAPE/ ELM / GEWISS/ SPELSBERG / RITTAL/ EATON / OBO /SCHNEIDER) |
254 | 4 module MCB DB |
255 | 8 module MCB DB |
256 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
257 | Single pole |
258 | Double pole |
259 | Credit for dismantled aluminium conductor XLPE insulated and PVC sheathed UG cable of 1.1KV grade and 6 SWG G.I.wires laid along the cable of following sizes. |
260 | 2 x 16 sq. mm |
261 | 2 x 25 sq. mm |
262 | 3.5 x 35 sq. mm |
263 | 3.5 x 50 sq. mm |
264 | 3.5 x 70 sq. mm |
265 | 3.5 x 95 sq. mm |
266 | 3.5 x 120 sq. mm |
267 | 3.5 x 150 sq. mm |
268 | 3.5 x 185 sq. mm |
269 | 3.5 x 240 sq. mm |
270 | 3.5 x 300 sq. mm |
271 | 3.5 x 400 sq. mm |
272 | Credit for unserviceable damaged street light pole and fitting MS/ G.I. pipes dismantled during the execution of the work. |