Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33/11Kv Receiving Station At Dali- Udhyanpur Including 33 Kv Line (From Receiving Station Bheli-Ghat To Dali-Udhyanpur) And Singlebus -Out A, doda-Jammu And Kashmir

Jammu And Kashmir Power Development Department-PDDJK has published Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33/11Kv Receiving Station At Dali- Udhyanpur Including 33 Kv Line (From Receiving Station Bheli-Ghat To Dali-Udhyanpur) And Singlebus -Out A. Submission Date for this Tender is 23-09-2023. Wall Construction Tenders in doda Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

39232386
Corrigendum : Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33/11Kv Receiving Station At Dali- Udhyanpur Including 33 Kv Line (From Receiving Station Bheli-Ghat To Dali-Udhyanpur) And Singlebus -Out A
Open Tender
Indian
Jammu And Kashmir
doda
23-09-2023

Tender Details

Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning Of 1X3.15 Mva, 33 / 11Kv Receiving Station At Dali- Udhyanpur Including 33 Kv Line ( From Receiving Station Bheli-Ghat To Dali-Udhyanpur ) And Singlebus -Out At Receiving Station Bheli-Ghat , In District Doda Under The Jurisdiction Of Sub Transmission Division Doda , Jpdcl , Jammu- 1 A-Supply Part 2 33 Kvline Bay 3 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 4 33 Kv Isolatorwith Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 5 33 Kv Isolatorwithout Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 6 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 7 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 8 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 9 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 10 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 11 Steel Structures 12 Pipe Nominal Bore 200, 5.9 Mm Thick 13 Galvanised Steel Structures 14 Galvanized Nuts And Bolts 15 Control Cables 16 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 17 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 18 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 19 Lugs & Ferrules Etc. 20 Conductor And Hardware 21 Acsr Conductor Panther ( 200Sqmm ) 22 T-Clamp 23 Single Tension Fitting 24 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 25 Earth Wire 7 / 4 Sqmm 26 G.I Flat 50*6 Mm 27 Sub-Station Main Equipment Transformer Bay 28 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 29 33 Kv Isolatorwithout Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 30 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 31 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 32 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 33 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 34 Steel Structures 35 Pipe Nominal Bore 200, 5.9 Mm Thick 36 Galvanised Steel Structures 37 Galvanized Nuts And Bolts 38 Control Cables 39 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 40 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 41 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 42 Lugs & Ferrules Etc. 43 Conductor And Hardware 44 Acsr Conductor Panther 45 T-Clamp 46 Single Tension Fitting 47 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 48 Earth Wire 7 / 4 Sqmm 49 G.I Flat 50*6 Mm 50 33 / 11 Kv, 3.15 Mva Power Transformer 51 33 / 11Kv Onan, Copper Wound, Outdoor Type, 3.15 Mva Conventional Power Transformer, Oil Filled With Oltc And All Accessories Including Ht And Lt Terminal Connections 52 10 / 12 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 53 6 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 54 2 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 55 Lugs & Ferrules Etc. 56 Single Bus System 11 Kv ( Transformer Bay Scheme ) 57 11 Kv Vcb Panel Board ( 12Kv, 1250A, 25Ka, Outdoor ) With Over Current, Earth Fault Relays ( Iec 61850 ) , Mimic Diagram, Voltmeter, Ammeter, Annuniaciation Windows With Annunciation Relays, 3-Phase Tri Vector Meter-5A, Dlms Compliant With Rs-485 Port1 Incoming & 3 Outgoings 58 11Kv Gapless Surge Arrestor, 9Kv, 10Ka La With Polymer Housingstation Type 59 11Kv ( Ue ) Xlpe Power Cable 3 Core Armoured 60 Ii. 185Mm Square Three Core 61 Ii. 120Mm Square Three Core 62 11Kvheat Shrink Termination Cable Kits ( Indoor ) 185 Mm Square ( 3-Core ) 63 11Kv Heat Shrink Termination Cable Kits ( Outdoor ) 185 Mm Square ( 3-Core ) 64 11Kv Heat Shrink Termination Cable Kits ( Indoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 65 11Kv Heat Shrink Terminationcable Kits ( Outdoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 66 11 Kv Isolator, Double Break, 3 Pole, 600 Amp. Horizental Mounting Type With Earth Switch 67 11Kv Link Set ( Go Set ) , Ab Switch 3 Phase, 3 Pole, 400 Amps. 68 100 Kva, 11 / .433 Kv, Auxiliary Transformer, 3 Phase Distribution Transformer With Bimetallic Terminal Connectors , Energy Level -2, Al Wound. 69 St Poles 9 Mtrs Long 70 Galvanised Iron Of Sorts 71 120 Mm2 Pvc 4 Core Cable, Armoured Frls 72 Mccb 200 Amp 73 Cement Bottomng 1:2:4 Mix As Per Rec Standards 0.5Cum Per Pole 74 Earthing Of 100 Kva Sub Structure As Per Standard 75 Earthing Complete Gi Pipe 400 Mm Or Gi Rod 20Mm 2.5 Mtr Long 76 Common Miscellaneous Equipments 77 A ) Battery Bank 30 V, 100 Ah, Of 15 No. Cells Of 2 V Each, Sealed Maintenance Free Vrla Type, High Impact Polyprophelene Copolymer Container, Flame Retardant With Stand 78 B ) 30 V, 100 Ah, Float-Cum-Boost Charger With Full Wave Rectification For 220 V, 1 Phase, 50 Hz Ac Input Supply. 79 Distribution Panel ( 30V, Dc ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 For Two Number Battery Incoming Supplywith 2No. 63 Amp. Dp Mcb For Incoming Supplydouble Bus Bar Of Adequate Size, Twelve Number Dp Dc Mcb ( 0-32A ) Including Indication Lamp And Cables And Other Accessories 80 Distribution Panel ( 415 V, Ac ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 200A Switch Fuse Disconnector For Incoming Supply And Five Numbers Tpn Mcbs ( 16-125A ) And Five Number Dp Mcb ( 0-32A ) , Rectangular Bus Bar Suitable For 200 A Continous Supply Including Indication Lamp Cables And Other Accessories. 81 Telecommunication Facilities 82 Civil Works 83 Compound Walling Of Identified Land By Way Of Mass Concrete In Foundation And 228Mm Bricks Of 2M Height 84 Chain-Link Fencing Of 33Kv Yard Of Substation By Way Of Mass Concrete In Foundations And Chain-Link Fencing Of 6 Ft Height. 85 Provision For Water Supply By Way Of Laying Of Service Line From The Nearest Source , Construction Of Underground Tank ( 3000 Ltr ) And Fixing Of Water Lifting Motor ( 1Hp ) 86 33 / 11Kv Power Transformer Foundation 87 33Kv Equipment Foundation And Gantry Foundation 88 Earthing Mat Complete Job Gi Flat 50X8 Mm 89 Earthing Electrode ( 3 Meters Long, 40 Mm Dia Gi Pipe ) Through Gi Strips 90 33Kv Yard Concreting / Metalling 91 Water Tank 1000 Ltrs. ( Overhead ) 92 Control Room Building Including With Internal Wiring Complete Job 93 Shift Quarters For Je And Sba Including Internal Wiring Complete Job 94 Truss For Control Room Building 1.3Xplinth Area .Providing And Fixing Of Steel Truss Including Provision For Colur Coated Roofing 95 Development Of Land ( A Per Available At Site ) By Way Of Removing Weeds, Wild Grass And Undulation If Any, Ornamental Land Scraping And Growing Of Ornamental Trees In Un Built Areas And Road Sides And Development Of Road Along With Surface Drain. Including Construction Of Protection Walls ( R / B Walls ) As Per Site Requirement. ( The Participating Bidders Must Visit The Site Before Quoting The Rates ) 96 Yard Lighting ( 4 Nos Yard And 02 Nos Cr Back Side ) 97 Single Bus Out At R / Stn Beli Ghat 98 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 99 33 Kv Isolatorwith Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 100 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 101 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 102 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 103 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 104 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 105 Steel Structures 106 Pipe Nominal Bore 200, 5.9 Mm Thick 107 Galvanised Steel Structures 108 Galvanized Nuts And Bolts 109 Control Cables 110 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 111 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 112 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 113 Lugs & Ferrules Etc. 114 Conductor And Hardware 115 Acsr Conductor Panther 116 T-Clamp 117 Single Tension Fitting 118 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 119 Earth Wire 7 / 4 Sqmm 120 G.I Flat 50*06 Mm 121 Erection Of 33 Kv Line From Receiving Station Beli Ghat ( 7 Km ) 122 11 Mtr. Long St Pole ( For New Line ) St-410 Sp56 123 Gi Channel X-Arm Including Clamps And Braces 124 100 Mm² Acsrdogconductor 125 Pg Clamps For 100 Mm² Acsr Conductor 126 33Kv Polymeric Composite Pin Insulator 36Kv, 10Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 127 33Kv Polymeric Composite Disc Insulator 36Kv, Min Failing Load 70Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 128 Galvinized Nuts And Bolts. 129 Danger Plates With Clamps 130 Anti-Climbing Device With Clamps 131 Earthing Complete By Gi Pipe 40 Mm Or Gi Rod 20Mm 2.5 Mtr Long Through Gi Strip. 132 Red Oxide 133 Aluminium Paint 134 Cement Bottoming 1:2:4 Mix As Per Rec Standards .6Cum / Pole 135 Stone Pad ( 300 Mm X 300 Mmx 75 Mm ) 136 Aluminium Jointing Sleeves 137 Galvanised Stay Set With 50 X 8 Mm Stay Clamp, Guy Insulator ( 2Nos. ) , Anchor Plate ( 300X 300 X 8 Mm ) , Nut-Bolts, 2 Nos Turn-Buckles, 1.8M Long, 20 Mm Diameter Solid Gs Stay Rod & 7 / 4.00 Mm Dia Gi Stranded Wire Complete 138 Guard Netting 139 Safety Items 140 Rubber Mat 1M*2M ( 19Mm Thick ) 141 Fire Extinguisher Co2 Type Of 4.5 Kg Capacity For Control Room 142 3-Sand Bucket Fire Extinguisher 143 Helmet With Led Torch 144 Rubber Gloves For 33 Kv Level 145 Rubber Gloves For 11 Kv Level 146 Safetybelt 147 Safety Shoes 148 Earthing Rod ( Set Of 3 Rods ) 149 Hv Detector All Voltages 150 B- Erection Part 151 33 Kvline Bay 152 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 153 33 Kv Isolatorwith Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 154 33 Kv Isolatorwithout Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 155 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 156 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 157 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 158 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 159 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 160 Steel Structures 161 Pipe Nominal Bore 200, 5.9 Mm Thick 162 Galvanised Steel Structures 163 Galvanized Nuts And Bolts 164 Control Cables 165 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 166 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 167 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 168 Lugs & Ferrules Etc. 169 Conductor And Hardware 170 Acsr Conductor Panther ( 200Sqmm ) 171 T-Clamp 172 Single Tension Fitting 173 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 174 Earth Wire 7 / 4 Sqmm 175 G.I Flat 50*6 Mm 176 Sub-Station Main Equipment Transformer Bay 177 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 178 33 Kv Isolatorwithout Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 179 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 180 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 181 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 182 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 183 Steel Structures 184 Pipe Nominal Bore 200, 5.9 Mm Thick 185 Galvanised Steel Structures 186 Galvanized Nuts And Bolts 187 Control Cables 188 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 189 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 190 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 191 Lugs & Ferrules Etc. 192 Conductor And Hardware 193 Acsr Conductor Panther 194 T-Clamp 195 Single Tension Fitting 196 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 197 Earth Wire 7 / 4 Sqmm 198 G.I Flat 50*6 Mm 199 33 / 11 Kv, 3.15 Mva Power Transformer 200 33 / 11Kv Onan, Copper Wound, Outdoor Type, 3.15 Mva Conventional Power Transformer, Oil Filled With Oltc And All Accessories Including Ht And Lt Terminal Connections 201 10 / 12 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 202 6 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 203 2 Core 2.5Mmsq Control Cable Copper Armoured, 1.1Kv Grade .Isi .Frls 204 Lugs & Ferrules Etc. 205 Single Bus System 11 Kv ( Transformer Bay Scheme ) 206 11 Kv Vcb Panel Board ( 12Kv, 1250A, 25Ka, Outdoor ) With Over Current, Earth Fault Relays ( Iec 61850 ) , Mimic Diagram, Voltmeter, Ammeter, Annuniaciation Windows With Annunciation Relays, 3-Phase Tri Vector Meter-5A, Dlms Compliant With Rs-485 Port1 Incoming & 3 Outgoings 207 11Kv Gapless Surge Arrestor, 9Kv, 10Ka La With Polymer Housingstation Type 208 11Kv ( Ue ) Xlpe Power Cable 3 Core Armoured 209 Ii. 185Mm Square Three Core 210 Ii. 120Mm Square Three Core 211 11Kvheat Shrink Termination Cable Kits ( Indoor ) 185 Mm Square ( 3-Core ) 212 11Kv Heat Shrink Termination Cable Kits ( Outdoor ) 185 Mm Square ( 3-Core ) 213 11Kv Heat Shrink Termination Cable Kits ( Indoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 214 11Kv Heat Shrink Terminationcable Kits ( Outdoor ) 120 Mm Square ( One Spare ) ( 3-Core ) 215 11 Kv Isolator, Double Break, 3 Pole, 600 Amp. Horizental Mounting Type With Earth Switch 216 11Kv Link Set ( Go Set ) , Ab Switch 3 Phase, 3 Pole, 400 Amps. 217 100 Kva, 11 / .433 Kv, Auxiliary Transformer, 3 Phase Distribution Transformer With Bimetallic Terminal Connectors , Energy Level -2, Al Wound. 218 St Poles 9 Mtrs Long 219 Galvanised Iron Of Sorts 220 120 Mm2 Pvc 4 Core Cable, Armoured Frls 221 Mccb 200 Amp 222 Cement Bottomng 1:2:4 Mix As Per Rec Standards 0.5Cum Per Pole 223 Earthing Of 100 Kva Sub Structure As Per Standard 224 Earthing Complete Gi Pipe 400 Mm Or Gi Rod 20Mm 2.5 Mtr Long 225 Common Miscellaneous Equipments 226 A ) Battery Bank 30 V, 100 Ah, Of 15 No. Cells Of 2 V Each, Sealed Maintenance Free Vrla Type, High Impact Polyprophelene Copolymer Container, Flame Retardant With Stand 227 B ) 30 V, 100 Ah, Float-Cum-Boost Charger With Full Wave Rectification For 220 V, 1 Phase, 50 Hz Ac Input Supply. 228 Distribution Panel ( 30V, Dc ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 For Two Number Battery Incoming Supplywith 2No. 63 Amp. Dp Mcb For Incoming Supplydouble Bus Bar Of Adequate Size, Twelve Number Dp Dc Mcb ( 0-32A ) Including Indication Lamp And Cables And Other Accessories 229 Distribution Panel ( 415 V, Ac ) Made Of Crca Thickness Not Less Than 2 Mm , Powder Coated Degree Of Protection Ip 43 200A Switch Fuse Disconnector For Incoming Supply And Five Numbers Tpn Mcbs ( 16-125A ) And Five Number Dp Mcb ( 0-32A ) , Rectangular Bus Bar Suitable For 200 A Continous Supply Including Indication Lamp Cables And Other Accessories. 230 Telecommunication Facilities 231 Civil Works 232 Compound Walling Of Identified Land By Way Of Mass Concrete In Foundation And 228Mm Bricks Of 2M Height 233 Chain-Link Fencing Of 33Kv Yard Of Substation By Way Of Mass Concrete In Foundations And Chain-Link Fencing Of 6 Ft Height. 234 Provision For Water Supply By Way Of Laying Of Service Line From The Nearest Source , Construction Of Underground Tank ( 3000 Ltr ) And Fixing Of Water Lifting Motor ( 1Hp ) 235 33 / 11Kv Power Transformer Foundation 236 33Kv Equipment Foundation And Gantry Foundation 237 Earthing Mat Complete Job Gi Flat 50X8 Mm 238 Earthing Electrode ( 3 Meters Long, 40 Mm Dia Gi Pipe ) Through Gi Strips 239 33Kv Yard Concreting / Metalling 240 Water Tank 1000 Ltrs. ( Overhead ) 241 Control Room Building Including With Internal Wiring Complete Job 242 Shift Quarters For Je And Sba Including Internal Wiring Complete Job 243 Truss For Control Room Building 1.3Xplinth Area .Providing And Fixing Of Steel Truss Including Provision For Colur Coated Roofing 244 Development Of Land ( As Per Available At Site ) By Way Of Removing Weeds, Wild Grass And Undulation If Any, Ornamental Land Scraping And Growing Of Ornamental Trees In Un Built Areas And Road Sides And Development Of Road Along With Surface Drain. Including Construction Of Protection Walls ( R / B Walls ) As Per Site Requirement. ( The Participating Bidders Must Visit The Site Before Quoting The Rates ) 245 Yard Lighting ( 4 Nos Yard And 02 Nos Cr Back Side ) 246 Single Bus Out At R / Stn Beli Ghat 247 33 Kvvcb ( 36 Kv, 1250 A, 26.2 Ka, Outdoor Type ) 248 33 Kv Isolatorwith Earthing Blade ( 36 Kv , 1250A.Outdoor.3 Pole, 25Ka ) 249 33 Kv Current Transformer ( Single Phase, Multi Ratio, Multi Core , Outdoor ) 250 30 Kv Lightening Arrestor ( 30Kv, 10Ka, Station Class.Zno.Polymer ) Gapless 251 33 Kv C&R Panel Along With O / C, E / F And Differential Relay ( Iec 61850 ) Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows With Annunciation Relays, 3 Phase Trivector Meter Dlms Compliant Rs 485 Port 252 33 Kv Post Insulators Polymer Type , 36 Kv, 235 Kv Impulse, Creepage Distance 1224 Mm 253 33 Kv Pt ( 33Kv / 110V, 1Phase, Multicore, Outdoor ) ( 1No Per Phase ) 254 Steel Structures 255 Pipe Nominal Bore 200, 5.9 Mm Thick 256 Galvanised Steel Structures 257 Galvanized Nuts And Bolts 258 Control Cables 259 10 / 12 Core 2.5 Mm2, Copper Armoured, 1.1 Kv Grade, Isi Frls 260 8 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 261 2 Core 2.5 Mm2copper Armoured, 1.1 Kv Grade, Isi Frls 262 Lugs & Ferrules Etc. 263 Conductor And Hardware 264 Acsr Conductor Panther 265 T-Clamp 266 Single Tension Fitting 267 Polymercomposit Type Disc Insulators.36Kv Lighting Bimpulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm, Minimum Failing Load70 Kn 268 Earth Wire 7 / 4 Sqmm 269 G.I Flat 50*06 Mm 270 Erection Of 33 Kv Line From Receiving Station Bheli Ghat ( 7 Km ) 271 11 Mtr. Long St Pole ( For New Line ) St-410 Sp56 272 Gi Channel X-Arm Including Clamps And Braces 273 100 Mm² Acsrdogconductor 274 Pg Clamps For 100 Mm² Acsr Conductor 275 33Kv Polymeric Composite Pin Insulator 36Kv, 10Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 276 33Kv Polymeric Composite Disc Insulator 36Kv, Min Failing Load 70Kn, Lighting Impulse 170Kv Positive And 180Kv Negative, Creepage Distance 900Mm 277 Galvinized Nuts And Bolts. 278 Danger Plates With Clamps 279 Anti-Climbing Device With Clamps 280 Earthing Complete By Gi Pipe 40 Mm Or Gi Rod 20Mm 2.5 Mtr Long Through Gi Strip. 281 Red Oxide 282 Aluminium Paint 283 Cement Bottoming 1:2:4 Mix As Per Rec Standards .6Cum / Pole 284 Stone Pad ( 300 Mm X 300 Mmx 75 Mm ) 285 Aluminium Jointing Sleeves 286 Galvanised Stay Set With 50 X 8 Mm Stay Clamp, Guy Insulator ( 2Nos. ) , Anchor Plate ( 300X 300 X 8 Mm ) , Nut-Bolts, 2 Nos Turn-Buckles, 1.8M Long, 20 Mm Diameter Solid Gs Stay Rod & 7 / 4.00 Mm Dia Gi Stranded Wire Complete 287 Guard Netting

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 11-Sep-2023 EXTENSION OF DATES Date 16-09-2023
2 18-Sep-2023 EXTENSION Date 23-09-2023

Key Value

Document Fees
INR 4000 /-
EMD
INR 660000.0 /-
Tender Value
INR 3.30 Crore /-

BOQ Items

Name of Work: <“Design, Engineering, Manufacture, Survey, Supply, Transportation, Erection, Testing & Commissioning of 1x3.15 MVA, 33/11KV Receiving Station at Dali- Udhyanpur including 33 KV Line (from receiving station Bheli-Ghat to Dali-Udhyanpur) and SingleBus -out at Receiving Station Bheli-Ghat , in District Doda under the jurisdiction of Sub Transmission Division Doda ,JPDCL ,Jammu.” .>
Sl. No. Item Description
1A-SUPPLY PART
233 KVLINE BAY
333 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
433 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
533 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
633 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
730 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
833 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
933 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
1033 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
11STEEL STRUCTURES
12Pipe Nominal bore 200, 5.9 mm thick
13Galvanised steel structures
14Galvanized nuts and bolts
15CONTROL CABLES
1610 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
178 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
182 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
19Lugs & Ferrules etc.
20CONDUCTOR AND HARDWARE
21ACSR Conductor Panther (200sqmm)
22T-Clamp
23Single Tension fitting
24PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
25Earth Wire 7/4 sqmm
26G.I Flat 50*6 mm
27SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY
2833 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
2933 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
3033 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
3130 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
3233 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
3333 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
34STEEL STRUCTURES
35Pipe Nominal bore 200, 5.9 mm thick
36Galvanised steel structures
37Galvanized nuts and bolts
38CONTROL CABLES
3910 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
408 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
412 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
42Lugs & Ferrules etc.
43CONDUCTOR AND HARDWARE
44ACSR Conductor Panther
45T-Clamp
46Single Tension fitting
47PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
48Earth Wire 7/4 sqmm
49G.I Flat 50*6 mm
5033/11 KV, 3.15 MVA Power Transformer
5133/11KV ONAN,Copper wound,outdoor type,3.15 MVA Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections
5210 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
536 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
542 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
55Lugs & Ferrules etc.
56Single Bus system 11 KV(Transformer Bay Scheme)
5711 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector meter-5A,DLMS Compliant with RS-485 Port1 Incoming & 3 outgoings
5811KV Gapless Surge Arrestor,9KV,10KA LA With polymer HousingStation Type
5911KV (UE)XLPE Power Cable 3 core armoured
60II.  185mm square three core
61II.  120mm square three core
6211KVHeat shrink termination Cable Kits (Indoor) 185 mm square (3-core)
6311KV Heat shrink termination Cable Kits (Outdoor)185 mm square (3-core)
6411KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core)
6511KV Heat shrink terminationCable Kits (Outdoor) 120 mm square (one spare)(3-core)
6611 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch
6711KV Link Set (Go Set), AB switch 3 phase, 3 pole, 400 Amps.
68100 KVA, 11/.433 KV,Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound.
69St Poles 9 mtrs long
70Galvanised iron of sorts
71120 mm2 PVC 4 core cable,Armoured FRLS
72MCCB 200 Amp
73Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole
74Earthing of 100 KVA Sub structure As per Standard
75Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long
76COMMON MISCELLANEOUS EQUIPMENTS
77a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand
78b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply.
79Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supplywith 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories
80Distribution panel (415 V, AC)made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories.
81Telecommunication facilities
82Civil Works
83Compound walling of identified land by way of Mass Concrete in Foundation and 228mm bricks of 2M height
84Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height.
85Provision for water supply by way of laying of service line from the nearest source ,construction of underground tank (3000 ltr) and fixing of water lifting motor (1HP)
8633/11kv power Transformer Foundation
8733kv Equipment Foundation and gantry foundation
88Earthing Mat complete job GI flat 50x8 mm
89Earthing electrode ( 3 meters long, 40 mm dia GI pipe) through GI strips
9033kv Yard Concreting / Metalling
91Water tank 1000 Ltrs.( overhead)
92Control room Building including with internal wiring complete job
93Shift Quarters for Je and SBA including internal wiring complete job
94Truss for control room building 1.3xPlinth area .Providing and fixing of Steel Truss including provision for colur coated Roofing
95Development of land (a per available at site ) by way of removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain. Including Construction of Protection walls(R/B Walls)as per site requirement.( The participating bidders must visit the site before quoting the rates)
96Yard Lighting ( 4 Nos yard and 02 Nos CR back side)
97SINGLE BUS OUT AT R/STN BELI GHAT
9833 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
9933 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
10033 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
10130 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
10233 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
10333 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
10433 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
105STEEL STRUCTURES
106Pipe Nominal bore 200, 5.9 mm thick
107Galvanised steel structures
108Galvanized nuts and bolts
109CONTROL CABLES
11010 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
1118 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
1122 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
113Lugs & Ferrules etc.
114CONDUCTOR AND HARDWARE
115ACSR Conductor Panther
116T-Clamp
117Single Tension fitting
118PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
119Earth Wire 7/4 sqmm
120G.I Flat 50*06 mm
121ERECTION OF 33 KV LINE FROM RECEIVING STATION BELI GHAT(7 km)
12211 Mtr. Long ST Pole(For new line) ST-410 SP56
123GI Channel X-arm including clamps and braces
124100 mm² ACSRDogConductor
125PG Clamps for 100 mm² ACSR Conductor
12633kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
12733kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
128Galvinized Nuts and Bolts.
129Danger Plates with Clamps
130Anti-Climbing Device with Clamps
131Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
132Red Oxide
133Aluminium Paint
134Cement bottoming 1:2:4 mix as per REC standards .6cum /pole
135Stone Pad (300 mm x 300 mmx 75 mm)
136Aluminium Jointing Sleeves
137Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
138Guard netting
139SAFETY ITEMS
140Rubber Mat 1m*2m (19mm thick)
141Fire Extinguisher CO2 type of 4.5 Kg capacity for control room
1423-Sand Bucket Fire Extinguisher
143Helmet with LED torch
144Rubber Gloves for 33 KV Level
145Rubber Gloves for 11 KV Level
146SafetyBelt
147Safety Shoes
148Earthing rod (set of 3 rods)
149HV Detector all Voltages
150B- ERECTION PART
15133 KVLINE BAY
15233 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
15333 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
15433 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
15533 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
15630 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
15733 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
15833 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
15933 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
160STEEL STRUCTURES
161Pipe Nominal bore 200, 5.9 mm thick
162Galvanised steel structures
163Galvanized nuts and bolts
164CONTROL CABLES
16510 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
1668 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
1672 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
168Lugs & Ferrules etc.
169CONDUCTOR AND HARDWARE
170ACSR Conductor Panther (200sqmm)
171T-Clamp
172Single Tension fitting
173PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
174Earth Wire 7/4 sqmm
175G.I Flat 50*6 mm
176SUB-STATION MAIN EQUIPMENT TRANSFORMER BAY
17733 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
17833 KV Isolatorwithout earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
17933 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
18030 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
18133 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
18233 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
183STEEL STRUCTURES
184Pipe Nominal bore 200, 5.9 mm thick
185Galvanised steel structures
186Galvanized nuts and bolts
187CONTROL CABLES
18810 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
1898 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
1902 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
191Lugs & Ferrules etc.
192CONDUCTOR AND HARDWARE
193ACSR Conductor Panther
194T-Clamp
195Single Tension fitting
196PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
197Earth Wire 7/4 sqmm
198G.I Flat 50*6 mm
19933/11 KV, 3.15 MVA Power Transformer
20033/11KV ONAN,Copper wound,outdoor type,3.15 MVA Conventional Power transformer,Oil filled with OLTC and all accessories including HT and LT Terminal connections
20110 /12 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
2026 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
2032 Core 2.5mmsq Control Cable Copper Armoured,1.1KV Grade .ISI .FRLS
204Lugs & Ferrules etc.
205Single Bus system 11 KV(Transformer Bay Scheme)
20611 KV VCB Panel Board ( 12KV,1250A,25KA, Outdoor ) With over current,earth fault relays (IEC 61850),MIMIC diagram,Voltmeter,Ammeter,annuniaciation windows with annunciation relays,3-phase tri vector meter-5A,DLMS Compliant with RS-485 Port1 Incoming & 3 outgoings
20711KV Gapless Surge Arrestor,9KV,10KA LA With polymer HousingStation Type
20811KV (UE)XLPE Power Cable 3 core armoured
209II.  185mm square three core
210II.  120mm square three core
21111KVHeat shrink termination Cable Kits (Indoor) 185 mm square (3-core)
21211KV Heat shrink termination Cable Kits (Outdoor)185 mm square (3-core)
21311KV Heat shrink termination Cable Kits (Indoor) 120 mm square(one spare)(3-core)
21411KV Heat shrink terminationCable Kits (Outdoor) 120 mm square (one spare)(3-core)
21511 KV isolator, double break, 3 pole, 600 Amp. Horizental mounting type with earth switch
21611KV Link Set (Go Set), AB switch 3 phase, 3 pole, 400 Amps.
217100 KVA, 11/.433 KV,Auxiliary Transformer,3 Phase Distribution Transformer with bimetallic terminal connectors ,energy level -2,Al Wound.
218St Poles 9 mtrs long
219Galvanised iron of sorts
220120 mm2 PVC 4 core cable,Armoured FRLS
221MCCB 200 Amp
222Cement bottomng 1:2:4 mix as per REC standards 0.5cum per pole
223Earthing of 100 KVA Sub structure As per Standard
224Earthing complete GI pipe 400 mm or GI rod 20mm 2.5 mtr long
225COMMON MISCELLANEOUS EQUIPMENTS
226a) Battery Bank 30 V, 100 AH, of 15 No. cells of 2 V each, sealed maintenance free VRLA type, high impact Polyprophelene copolymer container, flame retardant with stand
227b) 30 V, 100 AH, float-cum-boost charger with full wave rectification for 220 V, 1 phase, 50 HZ AC input supply.
228Distribution panel (30V, DC) made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 for two number battery incoming supplywith 2No. 63 Amp. DP MCB for incoming supplydouble bus bar of adequate size,twelve number DP DC MCB(0-32A) including indication lamp and cables and other accessories
229Distribution panel (415 V, AC)made of CRCA thickness not less than 2 mm ,Powder coated degree of protection IP 43 200A Switch fuse disconnector for incoming supply and five numbers TPN MCBs(16-125A) and five number DP MCB(0-32A),rectangular bus bar suitable for 200 A continous supply including indication lamp cables and other accessories.
230Telecommunication facilities
231Civil Works
232Compound walling of identified land by way of Mass Concrete in Foundation and 228mm bricks of 2M height
233Chain-link Fencing of 33kv Yard of Substation by way of Mass Concrete in Foundations and chain-link fencing of 6 ft height.
234Provision for water supply by way of laying of service line from the nearest source ,construction of underground tank (3000 ltr) and fixing of water lifting motor (1HP)
23533/11kv power Transformer Foundation
23633kv Equipment Foundation and gantry foundation
237Earthing Mat complete job GI flat 50x8 mm
238Earthing electrode ( 3 meters long, 40 mm dia GI pipe) through GI strips
23933kv Yard Concreting / Metalling
240Water tank 1000 Ltrs.( overhead)
241Control room Building including with internal wiring complete job
242Shift Quarters for Je and SBA including internal wiring complete job
243Truss for control room building 1.3xPlinth area .Providing and fixing of Steel Truss including provision for colur coated Roofing
244Development of land ( as per available at site) by way of removing weeds, wild grass and undulation if any, ornamental land scraping and growing of ornamental trees in un built areas and road sides and development of road along with surface drain. Including Construction of Protection walls(R/B Walls)as per site requirement.( The participating bidders must visit the site before quoting the rates)
245Yard Lighting ( 4 Nos yard and 02 Nos CR back side)
246SINGLE BUS OUT AT R/STN BELI GHAT
24733 KVVCB (36 KV, 1250 A, 26.2 KA, outdoor type)
24833 KV Isolatorwith earthing blade(36 KV ,1250A.Outdoor.3 pole,25KA)
24933 KV Current Transformer (Single Phase,Multi ratio,multi core ,Outdoor)
25030 KV Lightening Arrestor (30KV,10KA,Station Class.ZNO.Polymer) Gapless
25133 KV C&R panel along with O/C, E/F and differential relay (IEC 61850) Mimic diagram, voltmeter, ammeter, annunciation windows with annunciation relays, 3 PHASE Trivector meter DLMS compliant RS 485 port
25233 kv Post Insulators polymer type , 36 kv, 235 kv impulse, creepage distance 1224 mm
25333 KV PT (33KV/110V,1phase,multicore,Outdoor)(1No per phase)
254STEEL STRUCTURES
255Pipe Nominal bore 200, 5.9 mm thick
256Galvanised steel structures
257Galvanized nuts and bolts
258CONTROL CABLES
25910 /12 core 2.5 mm2, copper armoured, 1.1 kv grade, ISI FRLS
2608 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
2612 core 2.5 mm2copper armoured, 1.1 kv grade, ISI FRLS
262Lugs & Ferrules etc.
263CONDUCTOR AND HARDWARE
264ACSR Conductor Panther
265T-Clamp
266Single Tension fitting
267PolymerComposit type Disc Insulators.36KV Lighting bimpulse 170KV Positive and 180KV Negative,Creepage distance 900mm,Minimum failing load70 KN
268Earth Wire 7/4 sqmm
269G.I Flat 50*06 mm
270ERECTION OF 33 KV LINE FROM RECEIVING STATION BHELI GHAT(7 km)
27111 Mtr. Long ST Pole(For new line) ST-410 SP56
272GI Channel X-arm including clamps and braces
273100 mm² ACSRDogConductor
274PG Clamps for 100 mm² ACSR Conductor
27533kV Polymeric composite Pin Insulator 36kV, 10kN,Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
27633kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
277Galvinized Nuts and Bolts.
278Danger Plates with Clamps
279Anti-Climbing Device with Clamps
280Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
281Red Oxide
282Aluminium Paint
283Cement bottoming 1:2:4 mix as per REC standards .6cum /pole
284Stone Pad (300 mm x 300 mmx 75 mm)
285Aluminium Jointing Sleeves
286Galvanised Stay Set with 50 x 8 mm stay clamp, guy insulator(2Nos.), anchor plate (300x 300 x 8 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 20 mm diameter solid GS stay rod & 7/4.00 mm dia GI stranded wire complete
287Guard netting
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.