Tender For Provision Of Technical Storage Accn At Parma (Chushul), chushul-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Provision Of Technical Storage Accn At Parma (Chushul). Submission Date for this Tender is 23-09-2023. Prime Mover Tenders in chushul Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

39210755
Corrigendum : Tender For Provision Of Technical Storage Accn At Parma (Chushul)
Open Tender
Indian
Jammu And Kashmir
chushul
23-09-2023

Tender Details

Tender For Provision Of Technical Storage Accn At Parma ( Chushul ) ; 1 Note: Schedule ‘A’ Part - I Toixare Prepriced By Mes. Bidders Shall Insert Their Lumpsum Amount In The Green Coloured Field Under Col- 6 Only. 2 Total Amount Of Sch A Part - I ( Buildings ) 3 Total Amount Of Sch A Part - Ii ( Internal Electrification ) 4 Total Amount Of Sch ‘A’ Part - Iii ( Protective Works ) 5 Total Amount Of Sch ‘A’ Part - Iv ( Area Drainage ) 6 Total Amount Of Sch ‘A’ Part - V ( Road ) 7 Total Amount Of Sch ‘A’ Part - Vi ( Hardstanding ) 8 Total Amount Of Sch ‘A’ Part - Vii ( External Electric Supply ) 9 Total Amount Of Sch ‘A’ Part - Viii ( Lightening Protection ) 10 Total Amount Of Sch A Part - Ix ( Site Clearance, Excavation And Earth Work ) 11 Sch A Part - X ( Dg Set ) Note: This Schedule Is Not Pre-Priced By Mes And The Rate Indicated As Rs 0.00 Under Col 5 Signifies This Fact Only 12 Supply & Installation Of Silent Cpcb Approved 10 Kva Tpdiesel Generating Set Having Diesel Engine Liquid Cooled, Electric Start, Four Stroke, Cold Starting, Tci Aspirated, Compression Ignition, Totally Enclosed Diesel Engine With Electronic Governor , Direct Coupled With 10 Kva Three Phase Alternator At 1500 Rpm, 0.8 Lagging Power Factor, Providing Three Phase 415Volts Suitable For 50 Hz, H Class Insulated Winding, Close-Direct-Coupled, Self-Excited And Self-Regulated Type, Screen Protected, Mounted On Rigid Ms Sheet Channel Base-Frame. The Alternator Shall Confirm To Is: 13364, Is: 4722, Bs5000, Iec: 34 And Suitable For Tropical Condition. Having Fitted Inside Canopy, Fabricated Out Of 1.6 Mm Thick Crca Sheet, Cubical Type, Totally Enclosed, Powder Coated, Control Panel And All Accessories In-Housed In A Acoustic Enclosure – Sound Proof Canopy. Make: Cummins / Kirloskar Green / Powerol / Mahindra & Mahindra / Crompton Greaves. 13 ( A ) Diesel Engine: - Adquate Capacity Of Diesel Engine As Accepted By The Accepting Officer Based On Manufacturers Technical Details Water Cooled To Drive Independently Above Alternator And After Considering Derating As Per Site Conditons After Generating And Reducing Power Consumed By Accessories Directly Coupled Through Flexible Coupling Multi Cylinder Multi Stroke Direct Injection, Cold Starting 1500 Rpm, As Per Relevant Isi / Bs - 5514 With An Overload Capacity Of 10% For Half An Hour In 12 Hours Continuous Running Complete With Standard Accessories All As Specified And Required For Safe Handling And Operation Salient Features Of Accessories Shall Be As Under :- 14 I ) Fly Wheel With Housingii ) Cooling System :- Moulded Radiator With Fan & Belts.Iii ) Cooling Water Pump : - Centrifugal Type Belt Driven.Iv ) Exhaust System :- Exhaust System Complete With Exhaust Piping Of 150Mm Dia With Ms Pipe Light Grade Upto & Outside And 1 Meter Away From The Enclosure, Covered With Asbestos Rope And Aluminium Foil Of Complete With In The Enclosure For Safe Exhaust Without Transforming Vibration To The Wall Of The Enclosure:Exhaust Gas Turbo Charger Typeexhaust Manifoldsilencer : Residual Typebellows 15 Iv ) Fuel System :- Fuel Injection System With Fuel Injectors, Fuel Injection Solenoid Switch Controlled By Electronic Governer For 1% Speed / Frequecy Regulation.Fuel Filtersfuel Hosesv ) Lub Oil System :-Lubricating Oil Filterlubricating Oil Pumpvi ) Air Intake System :- Air Intake Manifoldair Cleaner Dry Typevii ) Governer :- Electronic Governerviii ) Starting System :- Electric Self Starter With Maintenace Free Battary Including Battary Charging Alternator. 16 ( B ) Batteries :- Batteries Of Maintainence Free Of Capacity As Recommended By The Manufacturer Complete With Copper Conductor Multistranded Leads Of Suitable Length Fromself Starter To The Battery Terminals Complete With Initial Charge And Initial Fill Of Electrolyte All As Specified Of Make As Per Oem. ( C ) Starter Gear Ringstart And Stop Push Buttonignition Key / Switchhandling And Operation : Salient Features Of Accessories Shall Be As Under:Radiator With Blower Fancorrosion Inhibitor Coolantpaper Element Filters For Fuel, Lub Oil And By Pass.Electronic Governer Controlled Direct Fuel Injection Systemfly Wheel Housing And Fly Wheel. 17 ( D ) Generator Monitoring Control Panel : - Comprising Of All Standard Items As Mentioned Under This Schedule Or As Per Standardpractice Iginiton Key Switch And Start / Stop Arrangement, Indications For Engine Parameters, Hour Run Meter, Rpm Meter, Engine Oil Pressure Indicator, Water / Coolent Temparature Indicator, Battery Volt Display Including Suitable Size Mccbs And Multifuction Meter.Xi ) Safety Controls : - Engine Low Lube Oil Pressure High Water Temperature And Over Speeding Of Engine.Xii ) Coupling Arrangement : - Flexible Coupling, Fly Wheel To Suit Flexible Coupling.Xiii ) Accessories :- Avm Pads Built Or Separetely Mounted To Manufacturer Base Frames.Xiv ) Base Frame : - Made Out Of Ismc 250 Of Sturdy Design Made Of Ms Channel With Necessary Reinforcement And Predetermined Holes.Xv ) Ms Pipe Line To And From The Fuel Tank To The Dg Set. 18 ( E ) Alternator :-Standard Design Alternator Rated At 10 Kva, Net Output At Site After Considering Derating As Per Site Conditions At 0.8 ( Lag ) Power Factor Ac, 3 - Phase 4 - Wire 415 Volts 50 Hz, 1500 Rpm, Self Exicited Self Regulated Screen Protected Drip Proof Ip 23 Enclosure Brushless Design With Widing In Pole Faces, Insulating Class H And Voltage Regulation Of+ / - 1% At Rated Voltage From No Load To Full Load. The Alternator Shall Be Conforming To Bs 2613 / 5000 And Shall Be In Position To Generate Supply With Frequecy Regulation With In + / - 1% Tolerance. The Alternator Will Be Suitable For Tropical Climate And Shall Generally Confirm To Bs - 2613 / 5000 / Is - 4722.I ) Insulation Class - HIi ) Temparature Rise Class - HIii ) Excitation : Self Excitediv ) Regulation Performance: The Voltage Is Kept Constant With + / - 1%, Manual Voltage Adjustment Within + / - 5% .V ) Frequency Regulation + / - 1% 19 ( F ) Civil Works :-All Civil Works Including Pcc Platform As Per ManufactureS Design Also 30 Cm Above The Ground. The Depth Of The Foundation And Pcc As Recommended By The Manufacturer. ( G ) Rubber Mattingof Lv Grade 19Mm Thick Of Suitable Size Chequered Type Isi Marked To Be Laid In Front Of Control Panel Should Be Provided.Note:- The Contractor Shall Arrange For Artificial Load For Testing For Final Testing Of Dg Set At Site And The Cost Is Deemed To Be Included In Quoted Rate ( H ) Accoustic Enclosure:- Manufactured By Oem Suitable For 10 Kva Dg Set. ( I ) Nal Approved As Per Cpcb ( Ii ) It Should Be As Per Latest Rules And Regulations Of Ministry Of Environment And Forest And Pollution Control Board. 20 ( Iii ) The Generating Setbatteries And Control Panel Should Be Inside The Enclosure. ( Iv ) Fuel Tank Should Be Outside The Enclosure In The Sub Station Building.V ) The Accoustic Should Be Composite In Construction And Fully Assembled Integral Unit.Vi ) The Battaries Should Be Placed Inside The Enclosure Beside The Dg Set On A Suitable Insulatedplatform.Vii ) The Dg Set Should Be Provided With External Emergency Stop Push Button.Viii ) The Enclosure Should Be Suitably Illuminated By Suitable Capacity Of Ledfittings.Xi ) The Noise Level Should Be 75 Db At 1M Under Free Field Conditions.Xii ) The Accoustic Enclosure Parts Shall Be Of Powder Coated After Pre Treatment Process. The Powder Coating Shade Should Be Genset Green. The Base Frame Should Be Painted With Epoxy Based Black Shade. 21 Xiii ) Fuel Tank As Per Manufacturer Recommendation With Inlet And Outlet Connections And Fuel Level Indicator.Xiv ) Base Frame Made Out Of Suitable Ms Channel Duly Reinforced And Provided With Adequate Numbers Of Anti-Vibration Pads To Ensure Minimum Vibration As Recommended By Manufacturer.Notes : - ( I ) Thegenerator Set Prime Mover Will Produce At Least 11 Bhp On 10 Kva. ( Ii ) Rate Quoted Shall Be Deemed To Be Inclusive Of Cable And Terminations Form Generator To The Amf Panel, With Necessary Holes To Wall Including Making Good To Disturbed Surfaces So As To Match With The Existing Finishes All As Specified And Directed. ( Iii ) The Quoted Rate Shall Be Deemed To Be Inclusive Of First Filling Of Lubricant Oil. ( Iv ) The Quoted Rate Shall Be Deemed To Be Inclusive Of 12 Hours Test Run At Site Including Of Half An Hour On 10% Overload In Presence Of Representative Detailed By Accepting Officer; Including Fol, All Arrangements Are To Be Made By The Contractor For Tests. 22 Supply & Installation Of Silent Cpcb Approved 5 Kva Tpdiesel Generating Set Having Diesel Engine Liquid Cooled, Electric Start, Four Stroke, Cold Starting, Tci Aspirated, Compression Ignition, Totally Enclosed Diesel Engine With Electronic Governor, Direct Coupled With 10 Kva Three Phase Alternator At 1500 Rpm, 0.8 Lagging Power Factor, Providing Three Phase 415Volts Suitable For 50 Hz, H Class Insulated Winding, Close-Direct-Coupled, Self-Excited And Self-Regulated Type, Screen Protected, Mounted On Rigid Ms Sheet Channel Base-Frame. The Alternator Shall Confirm To Is: 13364, Is: 4722, Bs5000, Iec: 34 And Suitable For Tropical Condition. Having Fitted Inside Canopy, Fabricated Out Of 1.6 Mm Thick Crca Sheet, Cubical Type, Totally Enclosed, Powder Coated, Control Panel And All Accessories In-Housed In A Acoustic Enclosure – Sound Proof Canopy. Make: Cummins / Kirloskar Green / Powerol / Mahindra & Mahindra / Crompton Greaves. 23 ( A ) Diesel Engine: - Adquate Capacity Of Diesel Engine As Accepted By The Accepting Officer Based On Manufacturers Technical Details Water Cooled To Drive Independently Above Alternator And After Considering Derating As Per Site Conditons After Generating And Reducing Power Consumed By Accessories Directly Coupled Through Flexible Coupling Multi Cylinder Multi Stroke Direct Injection, Cold Starting 1500 Rpm, As Per Relevant Isi / Bs - 5514 With An Overload Capacity Of 10% For Half An Hour In 12 Hours Continuous Running Complete With Standard Accessories All As Specified And Required For Safe Handling And Operation Salient Features Of Accessories Shall Be As Under :- 24 I ) Fly Wheel With Housingii ) Cooling System :- Moulded Radiator With Fan & Belts.Iii ) Cooling Water Pump : - Centrifugal Type Belt Driven.Iv ) Exhaust System :- Exhaust System Complete With Exhaust Piping Of 150Mm Dia With Ms Pipe Light Grade Upto & Outside And 1 Meter Away From The Enclosure, Covered With Asbestos Rope And Aluminium Foil Of Complete With In The Enclosure For Safe Exhaust Without Transforming Vibration To The Wall Of The Enclosure:Exhaust Gas Turbo Charger Typeexhaust Manifoldsilencer : Residual Typebellows 25 Iv ) Fuel System :- Fuel Injection System With Fuel Injectors, Fuel Injection Solenoid Switch Controlled By Electronic Governer For 1% Speed / Frequecy Regulation.Fuel Filtersfuel Hosesv ) Lub Oil System :-Lubricating Oil Filterlubricating Oil Pumpvi ) Air Intake System :- Air Intake Manifoldair Cleaner Dry Typevii ) Governer :- Electronic Governerviii ) Starting System :- Electric Self Starter With Maintenace Free Battary Including Battary Charging Alternator. 26 ( B ) Batteries :- Batteries Of Maintainence Free Of Capacity As Recommended By The Manufacturer Complete With Copper Conductor Multistranded Leads Of Suitable Length Fromself Starter To The Battery Terminals Complete With Initial Charge And Initial Fill Of Electrolyte All As Specified Of Make As Per Oem. ( C ) Starter Gear Ringstart And Stop Push Buttonignition Key / Switchhandling And Operation : Salient Features Of Accessories Shall Be As Under:Radiator With Blower Fancorrosion Inhibitor Coolantpaper Element Filters For Fuel, Lub Oil And By Pass.Electronic Governer Controlled Direct Fuel Injection Systemfly Wheel Housing And Fly Wheel. 27 ( D ) Generator Monitoring Control Panel : - Comprising Of All Standard Items As Mentioned Under This Schedule Or As Per Standardpractice Iginiton Key Switch And Start / Stop Arrangement, Indications For Engine Parameters, Hour Run Meter, Rpm Meter, Engine Oil Pressure Indicator, Water / Coolent Temparature Indicator, Battery Volt Display Including Suitable Size Mccbs And Multifuction Meter.Xi ) Safety Controls : - Engine Low Lube Oil Pressure High Water Temperature And Over Speeding Of Engine.Xii ) Coupling Arrangement : - Flexible Coupling, Fly Wheel To Suit Flexible Coupling.Xiii ) Accessories :- Avm Pads Built Or Separetely Mounted To Manufacturer Base Frames.Xiv ) Base Frame : - Made Out Of Ismc 250 Of Sturdy Design Made Of Ms Channel With Necessary Reinforcement And Predetermined Holes.Xv ) Ms Pipe Line To And From The Fuel Tank To The Dg Set. 28 ( E ) Alternator :-Standard Design Alternator Rated At 5 Kva, Net Output At Site After Considering Derating As Per Site Conditions At 0.8 ( Lag ) Power Factor Ac, 3 - Phase 4 - Wire 415 Volts 50 Hz, 1500 Rpm, Self Exicited Self Regulated Screen Protected Drip Proof Ip 23 Enclosure Brushless Design With Widing In Pole Faces, Insulating Class H And Voltage Regulation Of+ / - 1% At Rated Voltage From No Load To Full Load. The Alternator Shall Be Conforming To Bs 2613 / 5000 And Shall Be In Position To Generate Supply With Frequecy Regulation With In + / - 1% Tolerance. The Alternator Will Be Suitable For Tropical Climate And Shall Generally Confirm To Bs - 2613 / 5000 / Is - 4722.I ) Insulation Class - HIi ) Temparature Rise Class - HIii ) Excitation : Self Excitediv ) Regulation Performance: The Voltage Is Kept Constant With + / - 1%, Manual Voltage Adjustment Within + / - 5% .V ) Frequency Regulation + / - 1% 29 ( F ) Civil Works :-All Civil Works Including Pcc Platform As Per ManufactureS Design Also 30 Cm Above The Ground. The Depth Of The Foundation And Pcc As Recommended By The Manufacturer. ( G ) Rubber Mattingof Lv Grade 19Mm Thick Of Suitable Size Chequered Type Isi Marked To Be Laid In Front Of Control Panel Should Be Provided.Note:- The Contractor Shall Arrange For Artificial Load For Testing For Final Testing Of Dg Set At Site And The Cost Is Deemed To Be Included In Quoted Rate ( H ) Accoustic Enclosure:- Manufactured By Oem Suitable For 5 Kva Dg Set. ( I ) Nal Approved As Per Cpcb ( Ii ) It Should Be As Per Latest Rules And Regulations Of Ministry Of Environment And Forest And Pollution Control Board. 30 ( Iii ) The Generating Setbatteries And Control Panel Should Be Inside The Enclosure. ( Iv ) Fuel Tank Should Be Outside The Enclosure In The Sub Station Building.V ) The Accoustic Should Be Composite In Construction And Fully Assembled Integral Unit.Vi ) The Battaries Should Be Placed Inside The Enclosure Beside The Dg Set On A Suitable Insulatedplatform.Vii ) The Dg Set Should Be Provided With External Emergency Stop Push Button.Viii ) The Enclosure Should Be Suitably Illuminated By Suitable Capacity Of Ledfittings.Xi ) The Noise Level Should Be 75 Db At 1M Under Free Field Conditions.Xii ) The Accoustic Enclosure Parts Shall Be Of Powder Coated After Pre Treatment Process. The Powder Coating Shade Should Be Genset Green. The Base Frame Should Be Painted With Epoxy Based Black Shade. 31 Xiii ) Fuel Tank As Per Manufacturer Recommendation With Inlet And Outlet Connections And Fuel Level Indicator.Xiv ) Base Frame Made Out Of Suitable Ms Channel Duly Reinforced And Provided With Adequate Numbers Of Anti-Vibration Pads To Ensure Minimum Vibration As Recommended By Manufacturer.Notes : - ( I ) Thegenerator Set Prime Mover Will Produce At Least 6 Bhp On 5 Kva. ( Ii ) Rate Quoted Shall Be Deemed To Be Inclusive Of Cable And Terminations Form Generator To The Amf Panel, With Necessary Holes To Wall Including Making Good To Disturbed Surfaces So As To Match With The Existing Finishes All As Specified And Directed. ( Iii ) The Quoted Rate Shall Be Deemed To Be Inclusive Of First Filling Of Lubricant Oil. ( Iv ) The Quoted Rate Shall Be Deemed To Be Inclusive Of 12 Hours Test Run At Site Including Of Half An Hour On 10% Overload In Presence Of Representative Detailed By Accepting Officer; Including Fol, All Arrangements Are To Be Made By The Contractor For Tests. 32 Sch A Part - Xi ( Miscellaneous B / R And E / M Works ) Note: This Schedule Is Not Pre-Priced By Mes And The Rate Indicated As Rs 0.00 Under Col 5 Signifies This Fact Only 33 Supply And Fixsign Boards Of Size 1200Mm X 1200Mm Made Out Of 1Mm Thick Plain Black Sheet Fixed Over Ms Angle Iron 25 X 25 X 5Mmframe Work, Height Of Frame 2700 Mmfrom Gl All Duly Painted With Two Coats Of Synthetic Enamel Paint Over A Coat Of Red Oxide Primer, Covering The Board With Reflective Sheet And Writing Letters Over It Of Size As Approved By Gecomplete All As Directed.Note :- Excavation In Post Holes And Pcc 1:2:4 Type B1 For Fixing The Sign Board Is Deemed To Be Inclusive In The Quoted Rate. 34 Supply And Fixunhd Fire Symbols Sign Boards Of Size 1200Mm X 1200Mm Made Out Of 1Mm Thick Plain Black Sheet Fixed Over Ms Angle Iron 25 X 25 X 5Mmframe Work, Height Of Frame 2700 Mmfrom Gl All Duly Painted With Two Coats Of Synthetic Enamel Paint Over A Coat Of Red Oxide Primer, Covering The Board With Reflective Sheet And Writing Letters Over It Of Size As Approved By Ge Complete All As Directed.Note :- Excavation In Post Holes And Pcc 1:2:4 Type B1 For Fixing The Sign Board Is Deemed To Be Inclusive In The Quoted Rate. 35 Supply Only Frgdunnage Blocks Of Size 30Cm X 30Cm X 20Cm All As Specified And As Directed. 36 Supply And Fixing Totally Enclosed Flame Proof, Weather Proof Led Light Fitting 2X20 Watts, 1200Mm With Aluminium Extruded And Aluminium Heat Sink, System Lumen Efficiency =100 Lm / W Operating Voltage Between 140-270 V Ac, Power Factor More Than 0.90%, Led Driving Current < 70% Of Rated Maximum Forward Current, Thd Less Than 20%, Cri More Than 80%, Luminaire Integral Driver With 2Kv Surge Protection, Over Load Protection, No Load Protection And Bis Marking ( R No. For Driver ) , Driver Certification Iec64347-2-13 Is ( 15885 ) , Over All Electrical Efficiency More Than 90%, Driver Electrical Efficiency Will Be > 85%, With 2 Year Warranty All As Specified And Directed. Make : Shyaam, Crompton, Sudhir, Bajaj, Baliganote :- Mounting Of The Bracket For Light Fitting In The Roof Shall Be Done At The Time Casting Of Slab. 37 Supply And Fixing Flame Proof 12 Way Distribution Board For Mounting Mcb / Rcbo / Elcb Etc. As Per Is Specification And Cmri Approved, Factory Made, Fabricated Out Of Cast Aluminium Alloy Lm-06 Grey Epoxy Powder Coated Finish, Fitted With Din Channel Neutral Link, Earth Links And 200 Amps Rated Bus Bar. The Db Shall Be Having Ip-65 Protection. The Dbs Shall Also Be Consisting And Including The Following:- ( A ) Mcb Spn40 Amps, 240 Volts Ac 50 Hz- 01 No. ( B ) Mcb Sp10 Amps, 240 Volts Ac 50 Hz- 10 Nos. Make : Shyaam, Crompton, Sudhir, Bajaj, Baliga 38 Supply And Fix Flame Proof Flexible Metalic Hose Conduit 20 Mm Dia All As Specified And Directed. 39 Supply, Fixing, Installation, Testing And Commissioning Of Lt Panel Of Size 0.9M X 0.9M X 0.6M, Outdoor Type Cubical Shape Made Out Of Crca Sheet 3.15 Mm Thick , Factory Fabricated With Front And Back Openabe Double Door With Locking Arrangement, Cpri Approved, Suitable For 3 Phase, 4 Wire System 415 Volts, 50 Hz, Ac Supply System, Aluminium Bus Bar For Phases And Neutral, Powder Coated, Provided With Suitable Gasket To Make It Dust And Vermin Proof, Provision For Ventilation, M S Angle Iron 50X50x6mm Frame Support And Four Legs All Powder Coated Not Less Than 100 Microns Thickness, Grouting Of Legs In Pcc 1:3:6 Type C1 Foundation Of Suitable Size As Per ManufacturerS Directions And Height Not Less Than 30 Cm From The Ground Level, Panelto Accomodate The Items Mentioned Belowand Having Seperate Compartment / Chambers For Cable Gallery, Busbar, Switch Gear Etc All As Specified And Comprising Of Following Including Necessary Cable Connections To The Mcbs, Mccbs, Voltmeter, Ammeter And Cable Lugs Etc. Complete All As Directed: - 40 ( A ) Aluminium Bus Bar, 3 Phase, 4 Wire, Ac Supply System 50 Hz Mounted On Epoxy Based Post Insulators, Including Drilling Hole For Cable Connection, Rating Of Bus Bar 50 Amps. ( B ) Incoming Mccb 16 Amp, 4Pole 16 Ka, 415 Volt With Adjustable Thermal And Fixed Magnetic Release - 01 No ( C ) Outgoing Mcb Spn 3 Amp 6 Ka C, 240 Volts, - 02 Nos ( 01 Standby ) ( D ) Outgoing Mcb Spn 3 Amp 16 Ka 440 V - 01 Nos ( Timer ) ( E ) Outgoing Mcb Tpn 10 Amp 16 Ka 440 V - 02 Nos ( Siren+Spare ) ( F ) Ammeter Digital Type 0 - 50 Amps, 3 Ph With In Built Selector Switchwith Suitable Rating Cts -01 Setmake: Dip / Ae / Imp / Nsd 41 ( G ) Voltmeter, Digital Type 0 - 500 Volt, 3 Ph With In Built Selector Switchwith Selector Switch -01 Setmake: Dip / Ae / Imp / Nsd ( H ) All Accessories Prewired With Appropriate Size Copper Strip Or Wire Thimbles Etc. ( J ) Phase Indicating Lamps Led Type ( Ryb ) - 01 Set 42 Supply, Fixing, Installation, Testing And Commissioning Of Lt Panel Of Size 0.9M X 0.9M X 0.6M, Outdoor Type Cubical Shape Made Out Of Crca Sheet 3.15 Mm Thick , Factory Fabricated With Front And Back Openabe Double Door With Locking Arrangement, Cpri Approved, Suitable For 3 Phase, 4 Wire System 415 Volts, 50 Hz, Ac Supply System, Aluminium Bus Bar For Phases And Neutral, Powder Coated, Provided With Suitable Gasket To Make It Dust And Vermin Proof, Provision For Ventilation, M S Angle Iron 50X50x6mm Frame Support And Four Legs All Powder Coated Not Less Than 100 Microns Thickness, Grouting Of Legs In Pcc 1:3:6 Type C1 Foundation Of Suitable Size As Per ManufacturerS Directions And Height Not Less Than 30 Cm From The Ground Level, Panelto Accomodate The Items Mentioned Belowand Having Seperate Compartment / Chambers For Cable Gallery, Busbar, Switch Gear Etc All As Specified And Comprising Of Following Including Necessary Cable Connections To The Mcbs, Mccbs, Voltmeter, Ammeter And Cable Lugs Etc. Complete All As Directed: - 43 ( A ) Aluminium Bus Bar, 3 Phase, 4 Wire, Ac Supply System 50 Hz Mounted On Epoxy Based Post Insulators, Including Drilling Hole For Cable Connection, Rating Of Bus Bar 50 Amps. ( B ) Incoming Mccb 6 Amp, 4Pole 16 Ka, 415 Volt With Adjustable Thermal And Fixed Magnetic Release - 01 No ( C ) Outgoing Mcb Spn 3 Amp 6 Ka C, 240 Volts, - 02 Nos ( 01 Standby ) ( D ) Outgoing Mcb Tpn 3 Amp 16 Ka 440 V - 03 Nos ( Timer 2 & 3 +Spare ) ( E ) Ammeter Digital Type 0 - 50 Amps, 3 Ph With In Built Selector Switchwith Suitable Rating Cts -01 Setmake: Dip / Ae / Imp / Nsd 44 ( F ) Voltmeter, Digital Type 0 - 500 Volt, 3 Ph With In Built Selector Switchwith Selector Switch -01 Setmake: Dip / Ae / Imp / Nsd ( G ) All Accessories Prewired With Appropriate Size Copper Strip Or Wire Thimbles Etc. ( H ) Phase Indicating Lamps Led Type ( Ryb ) - 01 Set 45 Supply And Fixing Of 45W Led Street Light With System Lumen Efficacy =120 Lm / W Operating Voltage Between 120-270Vac, Multistage Isolated Potted Driver, Driver Will Comply For 440Vac Operation ( Will Sustain For 4 - 6 Hrs Continuously ) , Driver Will Have Cut Off At > 300 Vac, Ip66 Protection, Power Factor More Than 0.95%, Of Rated Maximum Forward Current, Luminaire Integral Driver With 5Kv Surge Protection, Over Load Protection, No Load Protection And Bis Marking ( R No. For Driver ) , Connecting With Pvc Insulated Copper Cable Of Size 1.5 X 3 Sqmm As Per Is 10322 And With At Least 2 Year On Site Warranty Without Any Condition Complete All As Specified And Directed.Make :- Philips / Wipro / Osram 46 Suppy And Fixing Junction Box Of Size 30Cm X 15 Cm X 8 Cm, Made Out Of 3.15 Mm Thick Ms Sheet Powder Coated With Locking Arrangementincluding One Mcb Sp 6 Amps, 02 Nos Bus Bar Of Suitable Size, With Suitable Number Of Holes And Ms Clamps To Fix On Street Light Pole All As Specified And Directed. 47 Supply And Fixing Street Light Digital Timer Distribution Board With Mcb Tpn 40 Amp -2 Nos, 415 Volt, 3 Phase Contactor 40 Amps, Digital Timercontrolled By Mcb, Time Switch 415V, 3 Phase, 20 Amp Rating With Contactor Complete Fixed Inside Steel Enclosure Withclamps & Brackets, All As Specified And As Directed. 48 Supply And Fix Steel Tublar Swaged Poles Erected Truly Vertical Or Planted As Strut Complete Withcast Iron Base Plate Welded To Pole, Finial Taper Plug, Bolts, Nuts & Screws, Poles Made Out Of Erw Ms Tubing Conforming To Is:1161 & Is:2713, Type 410 Sp- 80 ( 16 M Long ) Including Drilling Of Holes Of Required Size For Fixing Of Cross Arms, Painting The Exposed Surfaces Of Pole With Two Coats Of Aluminium Paint Over A Coat Of Zinc Chrome Primer And Two Coats Of Black Bitumenous Paint Internally & Portion Embedded In Concrete, Making Five Black & White Bands At Lower Portion Of Pole Each 300 Mm Wide Alternatley, And Marking Pole No. With Black Paint At Suitable Height And Painting Of Coping With Two Coats Of Synthetic Enemal Paint Complete All As Specified And Directed.Note :- Excavation And Earth Work, Pcc In Foundation And Coping Shall Be Measured And Paid For Separetely.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Sep-2023 REVISED drawings Other 23-09-2023
2 13-Sep-2023 Revised Prepriced Pages Other 23-09-2023
3 13-Sep-2023 REVISED BOQ and Amendments BOQ 23-09-2023

Key Value

Document Fees
INR 3000 /-
EMD
INR 1165000.0 /-
Tender Value
INR 16.80 Crore /-

BOQ Items

Nature of Work: PROVISION OF TECHNICAL STORAGE ACCNAT PARMA (CHUSHUL)
Sl. No. Item Description
1NOTE: Schedule ‘A’ Part - I toIXare Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col- 6 only.
2Total amount of Sch "A" Part - I (BUILDINGS)
3Total amount of Sch "A" Part - II(INTERNAL ELECTRIFICATION)
4Total amount of Sch ‘A’ Part - III(PROTECTIVE WORKS)
5Total amount of Sch ‘A’ Part - IV (AREA DRAINAGE)
6Total amount of Sch ‘A’ Part - V (ROAD)
7Total amount of Sch ‘A’ Part - VI (HARDSTANDING)
8Total amount of Sch ‘A’ Part - VII ( EXTERNAL ELECTRIC SUPPLY)
9Total amount of Sch ‘A’ Part - VIII(LIGHTENING PROTECTION)
10Total amount of Sch "A" Part - IX(SITE CLEARANCE, EXCAVATION AND EARTH WORK)
11SCH "A PART - X(DG SET) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 5 signifies this fact only
12Supply & installation of silent CPCB approved 10 KVA TPDiesel Generating Set having diesel engine Liquid cooled, Electric start, four stroke, cold starting, TCI Aspirated, compression ignition, totally enclosed diesel engine with electronic governor , direct coupled with 10 KVA Three Phase alternator at 1500 RPM, 0.8 lagging power factor, providing Three Phase 415Volts suitable for 50 Hz, H class insulated winding, Close-direct-coupled, Self-excited and self-regulated type, screen protected, mounted on rigid MS sheet channel base-frame. The alternator shall confirm to IS: 13364, IS: 4722, BS5000, IEC: 34 and suitable for tropical condition. having fitted inside Canopy, fabricated out of 1.6 mm thick CRCA Sheet, cubical type, totally enclosed, Powder Coated, Control Panel and all accessories in-housed in a acoustic enclosure – sound proof canopy. Make: Cummins/ Kirloskar Green/ Powerol/ Mahindra & Mahindra/ Crompton Greaves.
13(A) Diesel Engine: - Adquate capacity of Diesel engine as accepted by the accepting officer based on manufacturers technical details water cooled to drive independently above alternator and after considering derating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection,cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :-
14i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts. iii) Cooling Water pump : - Centrifugal type belt driven. iv) Exhaust System :- Exhaust System complete with exhaust piping of 150mm dia with MS pipe light grade upto & outside and 1 meter away from the enclosure, covered with asbestos rope and aluminium foil of complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure: Exhaust gas turbo charger type Exhaust manifold Silencer : Residual type Bellows
15iv) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governer for 1% speed /frequecy regulation. Fuel filters Fuel hoses v) Lub oil System :- Lubricating oil filter Lubricating oil pump vi) Air Intake System :- Air intake Manifold Air cleaner dry type vii) Governer :- Electronic Governer viii) Starting System :- Electric Self starter with maintenace free battary including battary charging alternator.
16(B) Batteries :- Batteries of maintainence free of capacity as recommended by the manufacturer complete with copper conductor multistranded leads of suitable length fromself starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified of Make as per OEM. (C) Starter gear ring Start and stop push button Ignition key / Switch Handling and operation : Salient features of accessories shall be as under: Radiator with blower fan Corrosion inhibitor coolant Paper element filters for fuel, lub oil and by pass. Electronic governer controlled direct fuel injection system Fly wheel housing and fly wheel.
17(D) Generator Monitoring Control Panel : - Comprising of all standard items as mentioned under this schedule or as per standardpractice iginiton key switch and start / stop arrangement, indications for Engine parameters, hour run meter, RPM meter, Engine oil pressure indicator, water/coolent temparature indicator, Battery volt display including suitable size MCCBs and multifuction meter. xi) Safety Controls : - Engine low lube oil pressure high water temperature and over speeding of engine. xii) Coupling arrangement : - Flexible coupling, fly wheel to suit flexible coupling. xiii) Accessories :- AVM Pads built or separetely mounted to manufacturer base frames. xiv) Base Frame : - Made out of ISMC 250 of sturdy design made of MS channel with necessary reinforcement and predetermined holes. xv) MS pipe line to and from the fuel tank to the DG Set.
18(E) Alternator :-Standard design alternator rated at 10 KVA,net output at site after considering derating as per site conditions at 0.8 (lag) power factor AC,3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self exicited self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class "H" and voltage regulation of+/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequecy regulation with in +/- 1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS - 2613/5000/ IS - 4722. i) Insulation class - "H" ii) Temparature rise Class - "H" iii) Excitation : Self Excited iv) Regulation performance: The voltage is kept constant with +/- 1%, manual voltage adjustment within +/- 5% . v) Frequency regulation +/- 1%
19(F) Civil Works :- All civil works including PCC platform as per manufacture"s design also 30 cm above the ground. The depth of the foundation and PCC as recommended by the manufacturer. (G) Rubber Mattingof LV grade 19mm thick of suitable size chequered type ISI marked to be laid in front of control panel should be provided. Note:- The contractor shall arrange for artificial load for testing for final testing of DG Set at site and the cost is deemed to be included in quoted rate (H) Accoustic Enclosure:- Manufactured by OEM suitable for 10 KVA DG Set. (i) NAL approved as per CPCB (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board.
20(iii) The generating setbatteries and control panel should be inside the enclosure. (iv) Fuel tank should be outside the enclosure in the sub station building. v) The accoustic should be composite in construction and fully assembled integral unit. vi) The battaries should be placed inside the enclosure beside the DG Set on a suitable insulatedplatform. vii) The DG Set should be provided with external Emergency stop push button. viii) The enclosure should be suitably illuminated by suitable capacity of LEDfittings. xi) The noise level should be 75 db at 1m under free field conditions. xii) The accoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Genset Green. The base frame should be painted with epoxy based black shade.
21xiii) Fuel tank as per manufacturer recommendation with inlet and outlet connections and fuel level indicator. xiv)Base frame made out of suitable MS channel duly reinforced and provided with adequate numbers of anti-vibration pads to ensure minimum vibration as recommended by manufacturer. NOTES : - (i) TheGenerator set prime mover will produce at least 11 BHP on 10 KVA. (ii) Rate quoted shall be deemed to be inclusive of cable and terminations form Generator to the AMF Panel, with necessary holes to wall including making good to disturbed surfaces so as to match with the existing finishes all as specified and directed. (iii) The quoted rate shall be deemed to be inclusive of first filling of lubricant oil. (iv) The quoted rate shall be deemed to be inclusive of 12 hours test run at site including of half an hour on 10% overload in presence of representative detailed by Accepting Officer; including FOL, all arrangements are to be made by the contractor for tests.
22Supply & installation of silent CPCB approved 5 KVA TPDiesel Generating Set having diesel engine Liquid cooled, Electric start, four stroke, cold starting, TCI Aspirated, compression ignition, totally enclosed diesel engine with electronic governor, direct coupled with 10 KVA Three Phase alternator at 1500 RPM, 0.8 lagging power factor, providing Three Phase 415Volts suitable for 50 Hz, H class insulated winding, Close-direct-coupled, Self-excited and self-regulated type, screen protected, mounted on rigid MS sheet channel base-frame. The alternator shall confirm to IS: 13364, IS: 4722, BS5000, IEC: 34 and suitable for tropical condition. having fitted inside Canopy, fabricated out of 1.6 mm thick CRCA Sheet, cubical type, totally enclosed, Powder Coated, Control Panel and all accessories in-housed in a acoustic enclosure – sound proof canopy. Make: Cummins/ Kirloskar Green/ Powerol/ Mahindra & Mahindra/ Crompton Greaves.
23(A) Diesel Engine: - Adquate capacity of Diesel engine as accepted by the accepting officer based on manufacturers technical details water cooled to drive independently above alternator and after considering derating as per site conditons after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection,cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :-
24i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts. iii) Cooling Water pump : - Centrifugal type belt driven. iv) Exhaust System :- Exhaust System complete with exhaust piping of 150mm dia with MS pipe light grade upto & outside and 1 meter away from the enclosure, covered with asbestos rope and aluminium foil of complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure: Exhaust gas turbo charger type Exhaust manifold Silencer : Residual type Bellows
25iv) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governer for 1% speed /frequecy regulation. Fuel filters Fuel hoses v) Lub oil System :- Lubricating oil filter Lubricating oil pump vi) Air Intake System :- Air intake Manifold Air cleaner dry type vii) Governer :- Electronic Governer viii) Starting System :- Electric Self starter with maintenace free battary including battary charging alternator.
26(B) Batteries :- Batteries of maintainence free of capacity as recommended by the manufacturer complete with copper conductor multistranded leads of suitable length fromself starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified of Make as per OEM. (C) Starter gear ring Start and stop push button Ignition key / Switch Handling and operation : Salient features of accessories shall be as under: Radiator with blower fan Corrosion inhibitor coolant Paper element filters for fuel, lub oil and by pass. Electronic governer controlled direct fuel injection system Fly wheel housing and fly wheel.
27(D) Generator Monitoring Control Panel : - Comprising of all standard items as mentioned under this schedule or as per standardpractice iginiton key switch and start / stop arrangement, indications for Engine parameters, hour run meter, RPM meter, Engine oil pressure indicator, water/coolent temparature indicator, Battery volt display including suitable size MCCBs and multifuction meter. xi) Safety Controls : - Engine low lube oil pressure high water temperature and over speeding of engine. xii) Coupling arrangement : - Flexible coupling, fly wheel to suit flexible coupling. xiii) Accessories :- AVM Pads built or separetely mounted to manufacturer base frames. xiv) Base Frame : - Made out of ISMC 250 of sturdy design made of MS channel with necessary reinforcement and predetermined holes. xv) MS pipe line to and from the fuel tank to the DG Set.
28(E) Alternator :-Standard design alternator rated at 5 KVA,net output at site after considering derating as per site conditions at 0.8 (lag) power factor AC,3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self exicited self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class "H" and voltage regulation of+/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequecy regulation with in +/- 1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS - 2613/5000/ IS - 4722. i) Insulation class - "H" ii) Temparature rise Class - "H" iii) Excitation : Self Excited iv) Regulation performance: The voltage is kept constant with +/- 1%, manual voltage adjustment within +/- 5% . v) Frequency regulation +/- 1%
29(F) Civil Works :- All civil works including PCC platform as per manufacture"s design also 30 cm above the ground. The depth of the foundation and PCC as recommended by the manufacturer. (G) Rubber Mattingof LV grade 19mm thick of suitable size chequered type ISI marked to be laid in front of control panel should be provided. Note:- The contractor shall arrange for artificial load for testing for final testing of DG Set at site and the cost is deemed to be included in quoted rate (H) Accoustic Enclosure:- Manufactured by OEM suitable for 5 KVA DG Set. (i) NAL approved as per CPCB (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board.
30(iii) The generating setbatteries and control panel should be inside the enclosure. (iv) Fuel tank should be outside the enclosure in the sub station building. v) The accoustic should be composite in construction and fully assembled integral unit. vi) The battaries should be placed inside the enclosure beside the DG Set on a suitable insulatedplatform. vii) The DG Set should be provided with external Emergency stop push button. viii) The enclosure should be suitably illuminated by suitable capacity of LEDfittings. xi) The noise level should be 75 db at 1m under free field conditions. xii) The accoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Genset Green. The base frame should be painted with epoxy based black shade.
31xiii) Fuel tank as per manufacturer recommendation with inlet and outlet connections and fuel level indicator. xiv)Base frame made out of suitable MS channel duly reinforced and provided with adequate numbers of anti-vibration pads to ensure minimum vibration as recommended by manufacturer. NOTES : - (i) TheGenerator set prime mover will produce at least 6 BHP on 5 KVA. (ii) Rate quoted shall be deemed to be inclusive of cable and terminations form Generator to the AMF Panel, with necessary holes to wall including making good to disturbed surfaces so as to match with the existing finishes all as specified and directed. (iii) The quoted rate shall be deemed to be inclusive of first filling of lubricant oil. (iv) The quoted rate shall be deemed to be inclusive of 12 hours test run at site including of half an hour on 10% overload in presence of representative detailed by Accepting Officer; including FOL, all arrangements are to be made by the contractor for tests.
32SCH "A PART - XI(Miscellaneous B/R and E/M Works) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 5 signifies this fact only
33Supply and fixSign Boards of size 1200mm x 1200mm made out of 1mm thick plain black sheet fixed over MS angle iron 25 x 25 x 5mmframe work, height of frame 2700 mmfrom GL all duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, covering the board with reflective sheet and writing letters over it of size as approved by GEcomplete all as directed. Note :- Excavation in post holes and PCC 1:2:4 type B1 for fixing the sign board is deemed to be inclusive in the quoted rate.
34Supply and fixUNHD fire symbols sign Boards of size 1200mm x 1200mm made out of 1mm thick plain black sheet fixed over MS angle iron 25 x 25 x 5mmframe work, height of frame 2700 mmfrom GL all duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, covering the board with reflective sheet and writing letters over it of size as approved by GE complete all as directed. Note :- Excavation in post holes and PCC 1:2:4 type B1 for fixing the sign board is deemed to be inclusive in the quoted rate.
35Supply only FRGdunnage blocks of size 30cm x 30cm x 20cm all as specified and as directed.
36Supply and fixing totally enclosed flame proof, weather proof LED light fitting 2x20 watts, 1200mm with aluminium extruded and aluminium heat sink, System Lumen Efficiency =100 Lm/W operating Voltage between 140-270 V AC,Power Factor more than 0.90%, LED Driving Current < 70% of rated maximum forward current, THD less than 20%, CRI more than 80%, Luminaire integral driver with 2KV surge protection, Over Load Protection, No Load Protection and BIS Marking (R no. for Driver), Driver Certification IEC64347-2-13 IS(15885), Over all electrical efficiency more than 90%, Driver electrical efficiency will be > 85%, with 2 year warranty all as specified and directed. Make : Shyaam, Crompton, Sudhir, Bajaj, Baliga Note :- Mounting of the bracket for light fitting in the roof shall be done at the time casting of slab.
37Supply and fixing Flame proof 12 way distribution board for mounting MCB/ RCBO/ ELCB etc. as per IS specification and CMRI approved,factory made, fabricated out of cast aluminium alloy LM-06 grey epoxy powder coated finish, fitted with DIN Channel neutral link, Earth links and 200 Amps rated bus bar. The DB shall be having IP-65 protection. The DBs shall also be consisting and including the following:- (a) MCB SPN40 Amps, 240 volts AC 50 Hz- 01 No. (b) MCB SP10 Amps, 240 volts AC 50 Hz- 10 Nos. Make : Shyaam, Crompton, Sudhir, Bajaj, Baliga
38Supply and Fix flame proof flexible metalic hose conduit 20 mm dia all as specified and directed.
39Supply,fixing, installation, testing and commissioning of LT Panel of size 0.9m x 0.9m x 0.6m, outdoor type cubical shape made out of CRCA sheet 3.15 mm thick ,factory fabricated with front and back openabe double door with locking arrangement, CPRI approved, suitable for 3 phase, 4 wire system 415 Volts, 50 Hz, AC supply system, aluminium bus bar for phases and neutral, powder coated, provided with suitable gasket to make it dust and vermin proof, provision for ventilation, M S angle iron 50x50x6mm frame support and four legs all powder coated not less than 100 microns thickness, grouting of legs in PCC 1:3:6 type C1 foundation of suitable size as per manufacturer"s directions and height not less than 30 cm from the ground level, panelto accomodate the items mentioned belowand having seperate compartment /chambers for cable gallery, busbar, switch gear etc all as specified and comprising of following including necessary cable connections to the MCBs, MCCBs, voltmeter, Ammeter and cable lugs etc. complete all as directed: -
40(a) Aluminium bus bar, 3 Phase, 4 wire, AC Supply system 50 Hz mounted on epoxy based Post insulators, including drilling hole for cable connection, rating of bus bar 50 Amps. (b) Incoming MCCB 16 Amp, 4pole 16 KA, 415 Volt with adjustable thermal and fixed magnetic release - 01 No (c)Outgoing MCB SPN 3 Amp 6 KA "C", 240 Volts, - 02 Nos (01 standby) (d)Outgoing MCB SPN 3 Amp 16 KA 440 V - 01 Nos (Timer) (e)Outgoing MCB TPN 10 Amp 16 KA 440 V - 02 Nos (Siren+spare) (f) Ammeter digital type 0 - 50 Amps, 3 Ph with in built selector switchwith suitable rating CTs -01 setMake: DIP/AE/IMP/NSD
41(g) Voltmeter, digital type 0 - 500 volt, 3 Ph with in built selector switchwith selector switch -01 setMake: DIP/AE/IMP/NSD (h) All accessories prewired with appropriate size copper strip or wire thimbles etc. (j) Phase indicating lamps LED type ( RYB) - 01 set
42Supply,fixing, installation, testing and commissioning of LT Panel of size 0.9m x 0.9m x 0.6m, outdoor type cubical shape made out of CRCA sheet 3.15 mm thick ,factory fabricated with front and back openabe double door with locking arrangement, CPRI approved, suitable for 3 phase, 4 wire system 415 Volts, 50 Hz, AC supply system, aluminium bus bar for phases and neutral, powder coated, provided with suitable gasket to make it dust and vermin proof, provision for ventilation, M S angle iron 50x50x6mm frame support and four legs all powder coated not less than 100 microns thickness, grouting of legs in PCC 1:3:6 type C1 foundation of suitable size as per manufacturer"s directions and height not less than 30 cm from the ground level, panelto accomodate the items mentioned belowand having seperate compartment /chambers for cable gallery, busbar, switch gear etc all as specified and comprising of following including necessary cable connections to the MCBs, MCCBs, voltmeter, Ammeter and cable lugs etc. complete all as directed: -
43(a) Aluminium bus bar, 3 Phase, 4 wire, AC Supply system 50 Hz mounted on epoxy based Post insulators, including drilling hole for cable connection, rating of bus bar 50 Amps. (b) Incoming MCCB 6 Amp, 4pole 16 KA, 415 Volt with adjustable thermal and fixed magnetic release - 01 No (c)Outgoing MCB SPN 3 Amp 6 KA "C", 240 Volts, - 02 Nos (01 standby) (d)Outgoing MCB TPN 3 Amp 16 KA 440 V - 03 Nos (Timer 2 & 3 +spare) (e) Ammeter digital type 0 - 50 Amps, 3 Ph with in built selector switchwith suitable rating CTs -01 setMake: DIP/AE/IMP/NSD
44(f) Voltmeter, digital type 0 - 500 volt, 3 Ph with in built selector switchwith selector switch -01 setMake: DIP/AE/IMP/NSD (g) All accessories prewired with appropriate size copper strip or wire thimbles etc. (h) Phase indicating lamps LED type ( RYB) - 01 set
45Supply and Fixing of 45W LED Street Light with System Lumen Efficacy =120 Lm/W operating Voltage between 120-270Vac, multistage isolated potted driver, Driver will comply for 440Vac operation ( will sustain for 4 - 6 hrs continuously), Driver will have cut off at > 300 Vac, IP66 Protection, Power Factor more than 0.95%, of rated maximum forward current, Luminaire integral driver with 5KV surge protection, Over Load Protection, No Load Protection and BIS Marking (R no. for Driver), connecting with PVC insulated copper cable of size 1.5 x 3 Sqmm as per IS 10322 and with at least 2 Year on site warranty without any condition complete all as specified and directed. Make :- Philips/ Wipro/ Osram
46Suppy and fixing junction box of size 30cm x 15 cm x 8 cm,made out of 3.15 mm thick MS sheet powder coated with locking arrangementincluding one MCB SP 6 Amps, 02 Nos bus bar of suitable size, with suitable number of holes and MS clamps to fix on street light pole all as specified and directed.
47Supply and Fixing street light digital timer distribution board with MCB TPN 40 Amp -2 Nos, 415 volt, 3 phase contactor 40 Amps, digital timercontrolled by MCB, time switch 415V, 3 phase, 20 Amp rating with contactor complete fixed inside steel enclosure withclamps & brackets,all as specified and as directed.
48Supply and fix Steel tublar swaged poles erected truly vertical or planted as strut complete withcast iron base plate welded to pole, finial taper plug, bolts, nuts & screws, poles made out of ERW MS tubing conforming to IS:1161 & IS:2713, type 410 SP- 80 ( 16 m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminium paint over a coat of zinc chrome primer and two coats of black bitumenous paint internally & portion embedded in concrete, making five black & white bands at lower portion of pole each 300 mm wide alternatley, and marking pole No. with black paint at suitable height and painting of coping with two coats of synthetic enemal paint complete all as specified and directed. Note :- Excavation and earth work, PCC in foundation and coping shall be measured and paid for separetely.
Disclaimer :