Tender For Pr# 33380001 Abb Make Acb 1 33380001 00010 00010 300885559 CB,ACB,PN:3WT82066UW375BB2,MN:3WT,4,500 Technical Details Name : Hiren Chavda Contact : 9879102375 Email : hiren.chavda@amns.in 1 NO CIRCUIT-BREAKER,AIR NO. OF POLES:4 , RATED VOLTAGE:500 V , RATED CURRENT:2000 A RATED SHORT CIRCUIT BREAKING CURRENT:66 KA , MAKE MODEL/BRAND:3WT MAKE NAME:SIEMENS , MAKE PART NO:3WT82066UW375BB2 Item Details : ACB Accessories BOM: 1. Withdrawable circuit breaker 4-pole,EDO with Closing Coil-230 V AC, Tripping Coil- 230 V AC, U/V Coil 415 V AC, size 2 In=2000A to 500V, 50/60Hz AC Icu=66kA at 500V with mechanical lockout device with tripped signaling switch with tripped indicators with guide frame Overcurrent release ETU37WT LSING Setting range according to FS with display With manual operating mechanism with memory with mechanical calling without 1st auxiliary release without 2nd auxiliary release 2- piece shutter with sealing cap against unauthorized switching off with door sealing frame. (Make: Siemens, Qty-1) 2. Breaker Control Switch(16A),Non Lockable,4 Way, Spring Return type, Three Position, Pistol Grip Handle, Inscription Trip-Neutral- Close,2 NO in Trip,2 NO in Close, Mounting: On LT Chamber Door (Make: Kaycee, Qty-1) 3. R-Ph ON Indication with Tag (Make: Siemens, Qty-1) 4. Y-Ph ON Indication with Tag (Make: Siemens, Qty-1) 5. B-Ph ON Indication with Tag (Make: Siemens, Qty-1) 6. White Indication for Service Position (Make: Siemens, Qty-1) 7. Yellow Indication for Test Position (Make: Siemens, Qty:1) 8. Clear Indication Ready to Close Indication (Make: Siemens, Qty-1) 9. Blue Indication for Sp. Charge Indication (Make: Siemens, Qty-1) 10. ON Indication Lamp with Tag (Make: Siemens, Qty-1) 11. OFF Indication with Tag (Make: Siemens, Qty-1) 12. TRIP Indication with Tag (Make: Siemens, Qty-1) 13. Multifunction Meter, Class 1.0 ,Model : 7KT with RS 485 (Make: Reputed, Qty-1) 14. 2000/1 Amp, Class:1,0, 5 VA Current Transformer for Multifunction Meter (Make: Reputed, Qty-3) 15. 10 A,2P MCB for AC main (Make: Siemens, Qty-1) 16. 6A,2P MCB for Closing/Tripping/Sp.Charge Motor Ckt.(Make: Siemens, Qty-3) 17. Wiring Material (Wires, Lugs, Ferrules, TBs, MCB Channel, Cable Duct etc.) (Make: Reputed, Qty-1 LOT) 18. Busbar if required (Qty-LOT) 19. Installation and commissioning are within vendor scope (QTY-LOT) 20. To and fro charges in vendor scope. (QTY-LOT) ------------------------------------------------------------------- 1. THE VENDOR IS REQUIRED TO SUBMIT GA DRAWINGS, QAP, TECHNICAL DATASHEETS, DEALERSHIP CERTIFICATES ALONG WITH THEIR OFFER/QUOTATION FOR NECESSARY TECHNICAL EVALUATION PURPOSES, WHEREVER APPLICABLE. 2. IN CASE OF ANY QUERIES, THE VENDOR MUST DISCUSS WITH THE SITE OR MAY VISIT THE SITE FOR TECHNICAL DISCUSSIONS BEFORE SUBMITTING THEIR OFFER. 3. THE VENDOR MUST SUBMIT ALL INTERNAL INSPECTION REPORTS AND MOC TEST CERTIFICATES FOR APPROVAL BEFORE DISPATCHING THE MATERIAL AND TO ISSUE DCC FROM THE SITE 4. IN CASE OF ANY FAILURES OR DEFECTS, THE VENDOR MUST TAKE CARE OF NECESSARY REPLACEMENTS AT THEIR OWN COST ON AN IMMEDIATE BASIS. 5. THE MATERIAL REQUIRED MUST BE AS PER THE PO ONLY. ANY DEVIATION IN THE SUPPLY WITH RESPECT TO THE PO SHALL LEAD TO REJECTION OF THE MATERIAL.