Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2X20 Mva,132Kv/33Kv Substation On Turnkey Basis At Baroud Ocp, Raigarh Area, Secl, raigarh-Chhattisgarh

South Eastern Coalfields Limited-SECL has published Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2X20 Mva,132Kv/33Kv Substation On Turnkey Basis At Baroud Ocp, Raigarh Area, Secl. Submission Date for this Tender is 30-09-2023. Substation Tenders in raigarh Chhattisgarh. Bidders can get complete Tender details and download the document.




Tender Notice

39160986
Corrigendum : Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2X20 Mva,132Kv/33Kv Substation On Turnkey Basis At Baroud Ocp, Raigarh Area, Secl
Open Tender
Indian
Chhattisgarh
raigarh
30-09-2023

Tender Details

Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2X20 Mva, 132Kv / 33Kv Substation On Turnkey Basis At Baroud Ocp, Raigarh Area, Secl

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Sep-2023 ANNEXURE-B Other 30-09-2023

Key Value

Document Fees
Refer document
EMD
INR 2688900.0 /-
Tender Value
INR 32.11 Crore /-

BOQ Items

Name of the Work / Contract No:
Sl. No. Item Description
1DESIGN AND ENGINEERING COST(for2X20MVA 132kV/33kV Substation)
2Design and Engg onPLANT & MACHINERY ( P&M - Electrical) to be supplied by bidder inlcusive of Overhead constuction cost, Contigencices, but excluding GST
3Design and Enggon Civil & Structural work
4CIVIL CONSTRUCTION AND STRUCTURAL WORKSfor 2X20MVA 132kV/33kV Substation on Turnkey Basis at Baroud OCP Raigarh Area inclusive of Insurance,Contingencie but excluding GST
5Sub-station Building
6Outdoor steel structures
7Foundation of outdoor structures including Transformer foundation
8Cable Trench
9Barbed wire fencing
10Boundary wall
11Gate
12Road
13Surface dressing
14Stone laying
15Anti weed treatment
16Bore well with submersible pump
17Path way
18Security Room
19RCC sump and Pump House
20Shed for DG & oil filter unit
21Drain along boundary wall
22Parking Shed
23Oil Overflow Chamber
24Oil Drain Pipe
25Watch Tower
26Survey & Soil testing
27SUPPLY OF PLANT & MACHINERY inclusive of Overhead Construction cost, Insurance, Contingencies, but excluding GST forsubstation ( 2X20MVA 132kV/33kV Substation )
28Lightning Arrestor (LA), Station class,120 kV, 10 kA,with surge monitor/counter suitable for 132 kV solidly earthed supply(Each set consisting of 3 nos.) (Min Qty 6)
29Isolator, ,3 pole outdoor type,31.5 kA, 132 kV,Motorised conforming to IS 1818 (current) With earth switch, 1250 A(nominal) rating (Min Qty 2)
30Isolator, ,3 pole outdoor type,31.5 kA, 132 kV,Motorised conforming to IS 1818 (current) Without earth switch, 1250 A (nominal) rating (Min Qty 10)
31SF6 circuit breaker 132 kV,1250 A, 31.5 kA, outdoor type,gang operated spring charge mechanism. (Min Qty 5)
32Single phase current transformer outdoor type, oil cooledwith CTR 250/1-1-1-1-1 Afor 132 kV system with 5 cores for metering and protection.Each sets consists of 3 nos. (Min Qty 3)
33Single phase current transformer outdoor type, oil cooledwith CTR 100/1-1-1-1-1 Afor 132 kV system with 5 cores for metering and protection.Each sets consists of 3 nos. (Min Qty 2)
34Potential transformer outdoor type 132 /v3 kV/110/v3V for metering and protection ,single phase. Each sets consists of 3 nos. (Min Qty 2)
35Indoor type control & Relay panel including instrumentationfor above incoming132 kV feeders ,132kV side of transformers and Bus Coupler (Min Qty 5)
36Power Transformer, 20 MVA,132kV/33kV YN-yn-0 with on load tap changer, HV and LV neutrals effectively earthed outdoor type conforming to IS 2026 (current) having with all accessories as per IS-3639 (current) (Min Qty 2)
37Control panel Indoor type for On Load Tap Changer (RTCC Panel) for 132/33 kV Transformer (Min Qty 2)
38Isolator, 3 pole, outdoor type 33 kV,1250 A, without earth switch conforming to IS-1818 (current) with cranking type mechanism (Min Qty 10)
39Isolater 3 pole outdoor type,33kV, 800 A (isolators with outgoing feeders are to be fitted with earth blade)conforming to IS-1818 (current) . (Min Qty 34)
40Isolator, 3 pole, outdoor type 33 kV, 800 A with HG fuse conforming to IS-1818 (current) with cranking mechanism (Min Qty 4)
41Single phase current transformer ,outdoor type, oil cooled with required CT ratiofor 33 kV system with 3 cores for metering and protection (Min Qty 14)
42Potential transformer, outdoor type,33 /v3 kV/110/v3V core for metering and protection 100 VA each for 33 kV , 3 phase system (Min Qty 2)
43Vacuum Circuit Breaker(VCB),33 kV ,800/1250 A,25 kA, outdoor type , having IDMT relay for O/L and E/F protection, Ammeter etc with indoor type Control and relay panel with instrumentation.- (Min Qty 14)
44Lightning arrestor , station class, 30 kV,10 kAsuitable for 33 kV solidly earthed supply(Each set consisting of three nos.) (Min Qty 14)
45Transformer outdoor type, plinth mounted, ONAN cooled with off-load tap changer, conforming to IS-2026 (current)200kVA,33kV/415V Dy-11 Group (Min Qty 1)
46Transformer outdoor type, plinth mounted, ONAN cooled with off-load tap changer, conforming to IS-2026 (current)200kVA,33kV/230V(L-L) Dy-11 Group (Min Qty 1)
47Insulators,ACSR zebra conductor,Strung busbar for 132 kV and 33 kV side (Main and Auxiliary) , Steel hardware, clamps ,terminal connectors etc for 132 and 33 kV side
48Mat Earthing system for switchyard including earth pits, galvanised strips/flats for interconnection, GI spikes andpipe electrodes, water pipes, valves & pipe fittingsetc
49Ligtning protection system consisting of spikes, earth pits, galvanised strips/flats, down earth conductors, Shield conductors,saddles, hardware etc including watering arrangement, pipe, valves, pipe fitting etc.
50Power disttribution board, 3 Ph- neutral ,415 V indoor type with required no. of MCCBs/MCBs etc (Min Qty 1)
51110 V Rechargable Battery, Lead acid type 200AH , 2 nos. float cum boost charger (1 working and 1 stand by) , wooden racks etc. (Min Qty 1)
52DCpower distribution board, 110 V with required MCCBs/MCBs etc (Min Qty 1)
53Lighting main distribution board ,230 V(L-L) indoor type with required no. of MCCBs/MCBs etc (Min Qty 1)
54Luminairs
55Lighting of substation building - Energy efficient recessedlight fittings - 1x15/18W,2X15W/18W LED lamps complete with the fittings, DC light fixtures along with 4 Nos 90W(min) LED Lamps fitted on Substation Building.
5611 m height steel tubular poles along with luminaries with 90W LED lamps along with control gear, brackets etc for outdoor yard illumination..
57Lighting mast, 16 m height, along with required nos. luminaries with 200 W LED Lamps, control gear etc. for outdoor yard lighting
58Accessories such as sub distribution boards, junction boxes,200 W LEDflood light fittings with brackets, individual control cables, PVC conduits/casings, back up fuses, switches sockets, ceiling roses, single core PVC cable with copper conductors (for internal connections) , flexible wire etc.
59Inverter cum battery charger along with battery for emergency lighting suitable for operation at 230V AC inside substation building
60Cable and Accessories
61LT Power cable, 3 / 4 core PVCSWA, stranded copper conductors, 1100 V grade of suitable size, (not less than 10 sq mm size)
62Lighting cable, PVCSWA, copper conductors, 1100 V grade of suitable sizes
63Control cable, PVCSWA, copper conductors, 1100 V grade of suitable size (not less than 2.5 sq mm)
64Cables for internal wiring of 1.5 sq mm to 6sq.mm size, PVC insulated copper conductor lighting cables.
65Cable trays, cable racks, binding material, cable glands, cable terminal lugs, nuts, bolts, washer, cable jointing and termination kit etc
66Miscellaneous items
67(i) Split type room air conditioners, 2 ton capacity (5 star/inverter AC) including servo stabiliser of rated capacity with digital indicator for in but and output voltage, industrial type plug sockets, fuses, control MCBs
68(ii) 63 kVA Diesel Generator with 3 ph, 50 hz, 415 V output supply to be installed in the DG room of the substation (Min Qty 1)
69(iii) Exhaust fan 600 mm sweep in battery room, oil filtration unit room, bath room
70(iv) Ceiling fans, 1200 mm sweep 5 star BLDC motor along with electronic regulators in Engineer in charge room, testing room, battery room, control room, Engineer’s room, other rooms etc.
71(v) Supply of Fire fighting equipment system consisting of Nitrogen injection for Transformers 20 MVA Transformers (Min Qty 2)
72(vi) Supply of fire/smoke detection alarming system for switch room , DG room,oil filteration room, oil storage room and Pump and sump house
73(vii) Fire fighting system consisting ofhydrant system (hydrant points, fire hose cabinets along with fire hose, pumps, pipes , pipe fittings etc), portable Co2 and dry type chemical powder fire extinguishers, trolley mounted dry type chemical powder fire extinguishers, sand buckets, power supply arrangement for pumps etc.
74(viii)Two stage high vacuum transformer oil purifier cum filtration M/c , on line, tyre mounted, 2400 lph capacity, heavy duty flexible hose pipe of required length, associated electricals suitable for operation on 415V, 3 phase 50 Hz, required flexible cable of 4 core copper conductors, coupler etc (Min Qty 1)
75(ix)Vacuum cleaner, domestic type, 35 lps, 2100 mm water gauge, wheel mounted, electricals suitable for operation on 230V, 1 Ph, 50 Hz supply, hose pipe, other accessories, suitable flexible cable etc (Min Qty 1)
76Other Miscellaneous item may comprises of i) Insulating Mat for indoor panels ii)Loto station system/kit- 01 no, iii) Electrical layout or single line diagram, iv) Electrical shock treatment chart, v)DO"S and DON"T chart, vi) Earth pit connection diagram in retro refractive radium type display. vii ) Danger plate viii) Furniture & Fittings
77Erection and commissioning of Plant and Machinary for substation to be suplied by bidder as above inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST
78Training of O&M staff
79Store cost for maintenance of P&Mduring Defect Liability Period (DLP) of five years.
80Cost of Maintenace during during Defect Liability Period (DLP) of five years.
81Total impact of GST for the purpose of CTC