| 1 | M&L for removal of existing treatment by taking out loose/spalled out waste material by chiselling chippings etc from beam, wall, columns, band etc. including use and waste of form work and providing steel wire fabric mesh of size 75mm X 75mm of dia 3.15mm fixed by L shaped mild steel shear key welded with existing reinforcement and providing 75mm thick concrete (1:1.5:3) type 0 using graded stone aggregate of 10mm maximum size mixed with polymeric admixture with pressure nozzle (guniting) and finishing the surface in CM (1:3) surface finished even and smooth without using extra cement and removing the debris outside MD land complete all as specified and directed.Note:- Quoted rates shall deemed to be inclusive of all form work and scaffolding or other handy T&P required to make up proper shape and size of columns/ Pillars, beam and wall partition etc. |
| 2 | M&L for preparing surfaces for roof treatment by removing all loose gravel, dirt,oil, grease and foreign matter by jet of dry air and clean the surfaces mechanically or by grinding to make it smooth before application , rerpair all cracks by cutting V groove and fill with PMC mortar ( polymer modified cement mortar ) prepared in ratio as per manufacturers specification provide 75mm x 75mm coving made out of PMC mortar as above on all joints of vertical upstandto ensure that moisture content in the prepared surfaces does not exceed 5% immediately before application of liquidmembrane. Material incorporation & PROTECTION BE PROVIDED AS TERRASHEILD FIRST APPLY WITH WATER ( RATIO TERRASHEILD: WATER will be 4 : 1) as primer with coverage area 0.1kg per Sqm. After 2-3 hours later, second step apply directly first coat of terrasheild 0.30 to 0.40 mm thickness coverage area 0.5 to 0.75 kg per Sqm with roller. spread non woven geo textile of 40/50gsm with overlap of 50mm in both direction when the surface is still tacky. After 4-6 hours later, apply third step apply directly second coat of terrasheild 0.30 to 0.40 mm thicknbess coverage area 0.5 to 0.75 kg per Sqm with roller. Final thickness of complete treatment should be min 1.0mm. water tank and khurra location one additional coat of terasheild .30 to .40 mm thickness coverage area 0.5 to 0.75 kg per Sqm be provideds complete all as specified and directed.Note:- Application will be done authorised applicator from manufacturer and manufacturer\"s application. Make SIKA/FOSROC/STP/Piddilite/. |
| 3 | M&L for screed bed or bedding layer of cemnt mortar 1 : 4, 20mm thick finished even and smooth without using extra cement complete all as specified and directed. |
| 4 | Demolition of cement concrete (un-reinforced) in ground floors and pavings n.exc 15 cm thickness (below or above GL) complete all as specified and as directed. |
| 5 | M&L for Granolithic concrete of 50mm thick (1:1:2) on concrete surface in floor , wall etc. in any position , finished to an even and fair surface complete all as specified and directed. |
| 6 | M&L for 75mm thick Cement concrete type B-1, 1 : 2 : 4 (20mm graded aggregate) as in floors, pavings etc and finishing even and smooth ( without using extra cement ) complete all as specified and as directed. |
| 7 | M&L for greasing and easing of rolling shutter of size not exc 13 Sqm alongwith the guide channel, helical spring, anchoring and all other as to work the shutter in eary way complete all as specified and directed. |
| 8 | M&L for preparation and two coat of synthetic enamel paint over old steel & iron Surfaces of any description, over 10cm in width or girth, complete all as specified and directed. |
| 9 | M&L for rendering 10 mm thick in CM (1:4) on fair faces of brick masonary or concrete surface of wall, finished even & smooth, without using extra cement, including taking down, raking out joints, hacking for key, scrubbing down with water etc of cement plaster, complete all as specified and directed. |
| 10 | M&L for rendering 15 mm thick in CM (1:4) mixed with WPCbut on other than fair faces of brick wall, finished even & smooth, without using extra cement , including taking down, raking out joints, hacking for key, scrubbing down with water etc of cement plaster, complete all as specified and directed.Note:- Water proofing compound shall be measured and paid separately. |
| 11 | Supply only Integral WPC complete all as specified and directed. |
| 12 | Dismantling asbestos cement (corrugated or semi corrugated) sheets in roof coverings complete all as specified and directed. |
| 13 | M&L for 6 mm thick asbestos cement, corrugated or semi-corrugated sheets in roofs, walls etc fixed with \"L\" type or \"J\" type or cranked hook bolts, complete all as specified and as directed. |
| 14 | All as per item No.13 above but except sheets, complete all as specified and as directed. . |
| 15 | S&F rolled mild steel work as in roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections,ms pipe) including distance pieces, cleatsetc. conforming to Fe-410W Gde E-250 quality \"A\"complete all as specified and directed. |
| 16 | M&L for mild steel work as in wind ties for roof covering including securing bolts etc. including all necessary drilling, bolting or riveting etc and similar work conforming to Fe 290 Gde E-165 complete all as specified and directed. |
| 17 | S&F plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment conforming to Fe-410W Gde E-250 quality \"A\" complete all as specified and directed. |
| 18 | S&F in repair for galvanised mild steel wire cloth, 0.56 mm nominal dia of wire and average width of aperture 1.18 mm and fixed with tinned tacks or galvanised wire staples complete all as specified and as directed . |
| 19 | Dismantling wrought iron or mild steel work of any description not otherwise provided for complete all as specified and as directed. |
| 20 | Hacking out old broken glass (any thickness, size, quality or description) from metal frame or stone or concrete or bricks surrounds glazed with putty, taking out old pins punching or drilling out, complete all as specified and as directed. |
| 21 | S & F Sheet glass 3.0 mm thick, ordinary quality & glazing with oil putty in squares n.exc 0.5 sqm in each pane including punching or drilling out old glazing pins/spring clips, and providing & fixing new ones complete all as specified and as directed. |
| 22 | M&L for preparation of new plastered surfaces and applyingthouroughly wetted surface to ensure better stickingincludingsand paper gentle rubbing to obtain smooth surfaces, including all necessary arrangement for execution of workand applying two coats of exteriorweather proof paint in camouflaging patternwith roller application over one coat of water based white pigmented akali resistant priming paint for external wall ,complete all as specified and directed. |
| 23 | Complete removal of existing treatment on Wall including washing rubbing down and stopping of distempered and painted surface and preparing old surfaceapplyingthouroughly wetted surface to ensure better stickingincludingsand paper gentle rubbing to obtain smooth surfaces, including all necessary arrangement for execution of workand applying two coats of exteriorweather proof paint in camouflaging pattern with roller application over one coat of water based white pigmented akali resistant priming paint for external wallover 1mm thick white external wall cementputty ,complete all as specified and directed. |
| 24 | M&L preparation of new plastered surface and applying two coat of distemper oil emulsion over one coat of water based white pigmented alkali resistant priming paint over 1 mm thick internal wall care putty conforming to IS:109-1968 white or tinted on ceiling & wall complete all as specified and directed. |
| 25 | Complete removal of existing treatment on walls including washing rubbing down and stopping of distempered and painted surface and preparing old surface applying two coats of oil bound over one coat of alkali resistant primer over 1 mm thick internal wall care putty incl preparing by rubbing etc complete with roller application complete all as specified and directed. |
| 26 | Complete removal of existing treatment on ceiling including washing rubbing down and stopping of distempered and painted surface and preparing old surface applying two coats of oil bound over one coat of alkali resistant primer over 1 mm thick internal wall care putty incl preparing by rubbing etc complete with roller application complete all as specified and directed. |
| 27 | Excavation in trenches in soft/loose soil not exceeding 1.5m wide and not exceeding 1.5 metre in depth and getting out for laying of cable etc. complete all as specified and as directed. |
| 28 | Returning, filling in soft/loose soil including spreading, levelling, watering and well ramming, in layers not exc 25 cm complete all as specified and as directed. |
| 29 | Removingof surplus soil to a distance not exc. 50 metre and depositing where directed at a level not exc.1.5 metre above the starting point complete all as specified and as directed. |
| 30 | Taking out of old unsv GI plate earthing from existing position , dismantling the same complete all as specified and as directed. Note Only Earthing material goes to schedule of credit except GI strip |
| 31 | Material and labour for bore well earthing with the help of mechanical boring machine of 150mm dia 30mtr depth, supply and fix 150 mm bore , UPVC pipe 6 kg/sqcm rating, 06 mtr long with the help of suitable size clamp with nut bolt and washer -01no including charcoal dust, salt fill in bore well for achieve earth conductivity less than 1 ohm. M&L for covering of bore well mouth with PCC (1:2:4) type B-1/Brick masonry pit of size 45x45x45 cm complete and give the mimimum earth test result below 1 ohm complete all as specified and directed Note :- (i) The earth pit shall be refilled by boulders free from vegetable soil.(ii) Earthing shall be tested by contractor in presence of Engr-in-charge. Record shall be maintained.Payment shall be admissible only after satisfactory test results.(iii) GI pipe electrode and GI strip shall be measured & paid separately. (iv) Item includes cost of 10 metre GI earth strip of size 32x06mm and 10 metre GI pipe 40mm light grade for protection of earth strip. |
| 32 | Material and labour for chemical earthing complete with copper earth plate electrode of size 600mm x 600mm x 3 mm thick buried directly in ground(earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m deep below normal ground connected to and including copper earth strip 25 x 3 mm by means of copper bolts nuts check nuts and washer, returning & filling the pit with excavated soil mixing with charcoal 250 KG , Crystal salt 200KG , magnesium sulphate of 100 KG and vegetable soil all around the plate up to 350mm above from top edge of plate and balance portion filing with excavated soil in layers not exceeding 25mm thick, 25mm bore galvanised iron medium grade watering pipe up to top of plate, 50mmbore galvanisd iron light grade pipe for earth strip protection, including all excavation earth work in any type of soil, PCC 1:3:6 type C1for chamber of internal size 300mm x300 x 300mm with 120mm thick wall and 700 mm x 700mm x 150mm thick, bed concrete, RCC 1:2:4, type B1 for precast chamber cover 50mm thick, reinforced with welded steel wire fabric or XPM jali (weight not less than 4.00 Kg/sqm), funnel, with wire mesh, complete all as specified and directed. Note:- (i) Quoted rates shall be deemed to include for earth strip with protection pipe up to 7.5 M length |
| 33 | Supply & lowering of GI tubing 50mm dia medium grade in incl necessary fittings for lowering in borewell of depth upto 30 mtr and providing necessary holes in pipe to achieve goodearth conductivity complete all as specified and as directed. |
| 34 | Taking down old Unserviceable aluminium strip from roof and wall of ESHs any size and position including making good to disrurbed surface of wall and roof complete all as specified and as directed. |
| 35 | Refixing of serviceable aluminum strip 25x3 mm complete as obtain from above item 34 with on new saddle / insulators, including straightning and fixing screws/accessories for roof and down conductor complete all as specified and directed. |
| 36 | S&F aluminium strip of size 25x3 mm complete with insulator/saddle and fixing with screw/accessories for roof and down conductor complete all as specified and as directed. |
| 37 | Taking out of old unsv GI strip and supply & fix copper strip of size 25 x 3 mm complete with insulator/saddle and fixing with screw/accessories for roof and down conductor complete all as specified and as directed |
| 38 | Taking down old Unserviceable GI strip from wall or buried in ground or any other indicated situation including making good to disrurbed surface complete all as specified and as directed. |
| 39 | Refixing of serviceable GI Strip 32x6mm fixed on wall or buried in ground or any other indicated situation complete all as specified and as directed |
| 40 | S&F GI Strip 32x6mm fixed on wall or buried in ground or any other indicated situation complete all as specified and as directed Note:- Extra GI strip consider for borewell earthing which for existing earthing location |
| 41 | Taking down old Unserviceable air termination rod of any size and capacity complete all as specified and as directed. |
| 42 | Refixing of serviceable Air termination rod as obatin from Item No 14 above including new threading and grinding of tip of air terminationas per site requirnment complete all as specified and as directed. |
| 43 | S&F single pointed air termination aluminium rod12 mm dia and 300 mm long complete all as specified and as directed . |
| 44 | M&L for in repair Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw including necessary protection box suitable size of made out of HDPE material of Make Neptune box/HDPE Sintexbox complete all as specified and as directed. |
| 45 | Taking down old Unserviceable GI pipe of 40mm sizecomplete all as specified and as directed. |
| 46 | S&F GI pipe light grade 40 mm dia for protection of GI strip complete all as specified and as directed. |
| 47 | S&F GI pipe medium grade 40 mm dia for protection of GI stripcomplete all as specified and as directed. |
| 48 | Supplying and stringingAluminium conductor, steel reinforced (ACSR)any type of ACSR conductor for airtermination points supported by GI tubing on the roof of the ESHs to inner connect the all termination points including taking down of existing conductor complete all as specified and as directed.(Notes : (i) The ACSR conductors shall be conforming to IS-398 and as specified in SSR Part-I.(ii) The unit rate quoted shall also be deemed to include for supply & fixing of aluminium binding wire, aluminium tapes etc which shall not be included in the weight of conductors.(iii) Weight of conductors shall be determined by measuring true horizontal distance between centers of two adjacent poles and compoundingthe weight of conductors of that size and length and 3% extra added for sag, jointing, jumpers etc.(iv) Weight of the conductors shall be calculated from the nominal weights given in tables in the relevant IS.) |
| 49 | Demolition of cement concrete (un-reinforced) of any description and any position n.exc 15 cm thickness (below or above GL) complete all as specified and as directed. |
| 50 | M & L for stay assembly to support GI pipe for Air Termination by providing 4mm dia GI wire 15 RM, 16mm MS Rod 1.35 RM and PCC block 1:3:6 size of 0.6x0.6x0.15M including earth work in sof soil including dismantlingold Stay assembly complete all as specified and as directed. |
| 51 | M&L of PCC 1:2:4 type B-1, 20 mm graded aggregate filling and mass concrete, for road finishing, PCC blocks and foundation concrete complete all as specified and directed. |
| 52 | S&F in repair/replacement of old unserviseable porceilin insulator for conductorfor 25 X 3/3.15 mm strip with one meter intervel secured with suitable screw complete all as specified and as directed. |
| 53 | S&F in repair/replacement old unserviseable porceilin insulator for wall down conductorfor 32 X 6 mm strip with one meter intervel secured with suitable screw complete all as specified and as directed. |