Tender For Repair/Maintenance Of Central Ac Plants At Tech Bldg 1 2 3 And 4 At Military Station Kanasar, kanasar-Rajasthan

Military Engineer Services-MES has published Tender For Repair/Maintenance Of Central Ac Plants At Tech Bldg 1 2 3 And 4 At Military Station Kanasar. Submission Date for this Tender is 06-09-2023. AMC of Air Condition Tenders in kanasar Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

39115484
Corrigendum : Tender For Repair/Maintenance Of Central Ac Plants At Tech Bldg 1 2 3 And 4 At Military Station Kanasar
Open Tender
Indian
Rajasthan
kanasar
06-09-2023

Tender Details

Tender For Repair/Maintenance Of Central Ac Plants At Tech Bldg 1 2 3 And 4 At Military Station Kanasar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 30-Aug-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 06-09-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 29980.0 /-
Tender Value
INR 14.99 Lakhs /-

BOQ Items

Name of Work : Repair/maintenance of Central AC Plants at Tech Bldg 1, 2, 3 & 4 at Military Station Kanasar
Sl. No. Item Description
1M&L for comprehensive maintenance, periodical inspection, servicing / calibration of 01 Nos Air conditioning plants having 03x80 TR Air cooled chiller (02 Working and 01 stand by) and AHU of capacity 80 TR, 36000 CFM and serviceability of cooling tower fan etc installed at Kanasar Mil Stn, by OEM service professional and calibration of all the sensor, gauges/valve connected to the system, lathe / filing work for proper alignment of pulley / shaft, greasing to all moving parts including all minor spare parts for smooth and efficient functioning complete all as specified and as directed. Note:- Contractor will submit the serviceability report.
2Supply and fixing in replacement PVC fills of suitable sizes for cooling towers of capacity 100 TR complete all as specified and as directed.
3Supply and fix in replacement microprocessor based PLC power supply card / compressor card with RAM (control system with mother board) including display with suitable cord installed in 80 TR chiller unit having screw compressor of Make : Carrier Model 30HXY100A for commanding compressor, valves, controlling temperature, compressor cut off/on, sensor input-output interface, solenoid valve & expansion valve controller as per installed on site complete all as specified and as directed.
4Supply and fixing in replacement electronic expansion valve card (EXV) with display and manual / auto operation function installed in 80 TR chiller unit having compressor of make Carrier Model 30HXY100A as per installed on site complete all as specified and as directed.
5Supply and fixing in replacement Electronic type Expansion valve installed in 80 TR chiller unit having screw compressor of make Carrier model 30HXY100A as per installed on site complete all as specified and as directed.
6M&L for overhauling and rewinding of 80 TR screw compressor motor with super quality copper conductor of suitable size, replacing all type of bearings, seals, bushes shafts from authorised service station complete all as specified and directed.
7M&L for following works :- (a) Disconnection of defective compressor from base including removing the suction valve, discharge valve / liquid injection line, oil valve, refrigerant piping. (b) Defective compressor - loading / unloading from base to ground and lifting/ shifting/ loading of compressor in vehicle and transportation from site to authorised workshop for repair. (c) After repairing of compressor - collection of compressor, transport to original installed on site. (d) Fixing of compressor on base, fixing of suction valve, discharge valve, NRV, liquid line injection valve, vapor injection valve oil & refrigerant piping connection installation & testing complete all as specified and as directed. (e) Pressure testing, leakage testing in all system and rectification of leakage, if any. (f) Dismantling and removing of chiller, both side end, and MS pipe line and again taking the leak test of the chillers tubes after fixing the cork and repairing of leak tube through dead plug. (g) Taking the hydraulic test of the chiller and taking the leak test after replacing Copper tube all as directed and specified by Engineer-in-Charge. (h) Cleaning / flushing the chillers shell with CTC chemical, cleaning/flushing the condenser shell with CTC chemical, flushing the system of suction, discharge, liquid line, oil separator tank, NRV by using nitrogen and CTC chemical. (j) Vaccumising / dehydration of the system upto 10 days with cold trap/ice/salt complete.
8Description of serial item No. 7.00 contd… (k) Pressure testing in the system, taking/ rectifying the leaks and holding the pressure including of nitrogen gas cylinder, vaccumising the system and holding of 24 Hrs, break the vaccum with R-134 and revaccum the system. (l) Servicing of electrical panel, compressor, contactor, checked and set right, control wiring/inter locking, safety controls complete. (m) Filling the refrigerant gas with R134a upto suitable pressure and testing the chiller to the entire satisfaction of AGE. Note :- Refrigerant gas R134a shall be measured and paid for separately under respective item of Sch "A".
9Supply and fixing in replacement of very efficient copper tubing of length 10.5 feet,16mm dia having pressure bearing capacity 80 Kg/sqcm, ASTM B280 standard or AS1571 standard complete of 80 TR cooling capacity complete all as specified and directed.
10Supply and fixing in replacement three way solenoid valve along with operating coil 220 Volt as per installed in 80 TR chiller unit as per existing installed complete all as specified and as directed.
11Supply and fixing in replacement two way solenoid valve along with operating coil 220 Volt as per installed in 80 TR chiller unit as per existing installed complete all as specified and as directed.
12Supply and fixing in replacement water pressure gauge meter stainless steel body 63 mm dia, including syphon its fitting having upto 7 bar range to be fix in 80mm/ 100mm /125mm bore MS pipe complete all as specified and as directed. Make :- Baumer or equivalent as approved by AGE. Note :- Welding / drilling / threading work for fixing of meter is included in he unit quoted rate of this item.
13Supply and fixing in replacement water temp gauge meter stainless steel body 63 mm dia, including syphon its fitting having upto 7 bar range to be fix in 80mm/ 100mm/ 125mm bore MS pipe complete all as specified and as directed. Make :- Baumer or equivalent as approved by GE. Note :- Welding / drilling / threading work for fixing of meter is included in he unit quoted rate of this item.
14Supply and fixing in replacement water temperature sensor immersion & thermoelectric type compatible with electronic control motherboard of central AC plant as per existing installed on site complete all as specified and as directed.
15Supply and fixing in replacement High Pressure and Low Pressure transducer with thermoelectric sensor and operating switch as per installed in 80TR chiller unit as per existing installed complete all as specified and as directed.
16Supply and fixing in replacement Electromechanical adjustable Differential Pressure Switch of range 1.3 bar to 12 bar with glanded cable upto 5 metre as per installed in 80 TR chiller unit complete all as specified and as directed.
17Supply and fixing in replacement water flow switch with brass body 1 inch BSP suitable for more than 1000 LPM flow rate along with 220 Volt AC 10 Amp sensor (water/ liquid flow switch) for 80 TR AC plant complete as per existing installed complete all as specified and as directed.
18Supply and fixing in replacement Differential Pressure Switch for fan complete as per existing installed complete all as specified and as directed.
19Supply and charging of refrigerant R134a including transportation of accessories complete all as specified and as directed.
20Supply and filling screw type compressor oil (refrigerant lubricant) for top up purpose including transportation complete all as specified and as directed.
21Supply and fixing in replacement CT card along with CTs set of three of 250 / 5 Amp type BPL as per installed in 80 TR control panel as per existing installed complete all as specified and as directed.
22Supply and fixing in replacement liquid line filter and core drier filter as per installed in 80 TR chiller unit as per existing installed complete all as specified and as directed.
23Supply and fix in replacement all filter of AHU capacity 80 TR, 36000 CFM as per existing installed at site complete all as specified and as directed.
24M&L for De-scaling of condenser (Heat exchanger) of capacity 80 TR installed in central AC plant by cleaning choked pipe, water circulating lines including service valves, condenser (heat exchanger to cooling tower) circulating concentrated de-scalingsolution (concentrated hydrochloric acid or any other suitable descaling chemical) mixed with water in suitable proportion till the complete deposited scale is removed or 24 hours whichever is later & ordered, circulating through pump, servicing of valve, cooling tower, water spray assembly, cleaning with suitable size of drill rod, wire brush including dismantling and connection all dismantled components in proper position after servicing / overhauling etc. replacement of packing gasket 3mm thick, necessary welding / filling and lathe work, nuts, bolts, with washers, testing of water lines for leakage. The condenser unit including civil work in both side of AC plant room wall and cutting of water pipe line and fixing valve / flange with dummy plate, cleaning of condenser pipe line for smooth functioning of other two unit complete all as specified and as directed.
25Supply and laying in replacement MS pipe of 150mm bore Heavy Class (ISI marked) with all fittings including necessary cutting, bending in required shape, welding work, etc, laid in floors or fixed to walls and ceiling etc. complete all as specified and as directed. Note :- Flange, gasket, nut, bolts & washers shall be measured and paid for separately as “Supply only” under respective items of this Schedule.
26Supply and laying in replacement MS pipe of 125mm bore Heavy Class (ISI marked) with all fittings including necessary cutting, bending in required shape, welding work, etc, laid in floors or fixed to walls and ceiling etc. complete all as specified and as directed. Note :- Flange, gasket, nut, bolts & washers shall be measured and paid for separately as “Supply only” under respective items of this Schedule.
27Supply and laying in replacement MS pipe of 100mm bore Heavy Class (ISI marked) with all fittings including necessary cutting, bending in required shape, welding work, etc, laid in floors or fixed to walls and ceiling etc. complete all as specified and as directed. Note :- Flange, gasket, nut, bolts & washers shall be measured and paid for separately as “Supply only” under respective items of this Schedule.
28Supply only MS flange of thickness 16mm for MS pipe of size 150 mm bore including nut, bolts, wasters & 3mm thick rubber gasket.
29Supply only MS flange of thickness 14mm for MS pipe of size 125 mm bore including nut, bolts, wasters & 3mm thick rubber gasket.
30Supply only MS flange of thickness 14mm for MS pipe of size 100 mm bore including nut, bolts, wasters & 3mm thick rubber gasket.
31Supply and fixing Cast Iron butterfly valve of size 150mm dia, Class PN 1.6, stainless steel disc, wafer type, lever operated, ISI marked, with flanges, nuts, bolts, gasket and washers, suitable for flanged pipe connection including taking down existing unserviceable valve, complete all as specified and as directed.
32Supply and fixing Cast Iron butterfly valve of size 125mm dia, Class PN 1.6, stainless steel disc, wafer type, lever operated, ISI marked, with flanges, nuts, bolts, gasket and washers, suitable for flanged pipe connection including taking down existing unserviceable valve, complete all as specified and as directed.
33Supply and fixing Cast Iron butterfly valve of size 100mm dia, Class PN 1.6, stainless steel disc, wafer type, lever operated, ISI marked, with flanges, nuts, bolts, gasket and washers, suitable for flanged pipe connection including taking down existing unserviceable valve, complete all as specified and as directed.
34Supply and fixing Non Return Valve (NRV) of size 100mm bore, cast iron body, as per IS 5312 (ISI marked), heavy duty, class ‘PN-1.6’, gun metal seat, both ends flanged and drilled, including nuts, bolts, washer and neoprene rubber gasket joint complete all as specified and as directed including dismantling & taking out old unserviceable non return valve of 80mm bore.
35S&F cast iron "Y" strainer with SS-304 grade screen of size 125mm bore, pressure rating PN 1.6, fixed in between MS flanged pipe, fixed in repairs, complete all as specified and as directed.
36S&F cast iron "Y" strainer with SS-304 grade screen of size 100mm bore, pressure rating PN 1.6, fixed in between MS flanged pipe, fixed in repairs, complete all as specified and as directed.
37M&L for taking down pump & motor of capacity 7.5 HP to 10 HP,demolition of existing PCC foundation and making new PCC foundation of size 1.5m x 0.6m x 100mm thick in PCC 1:2:4 Type B1 using 20mm graded crushed stone aggregate, along with grouting of new MS bolts of suitable size and fixing new chassis for pump & motor complete all as specified and as directed. Note :- Chassis made of MS iron will be measured and paid for separately.
38M&L for mild steel frame work of angle iron, channels, etc for mounting of pump & motor, made of C / U / L section MS iron of required size and shape including necessary cutting, bending, welding, etc, with and including painting to all steel surfaces with two coats of synthetic enamel paint of approved tint over a coat of red oxide zinc chrome primer complete all as specified and as directed including dismantling and taking down old frame work. Notes :-(i) Size, section and shape of steel sections shall be as directed. (ii) Weight of paint & primer shall not be considered for payment purpose and quoted rate shall deemed to be included this aspect.
39M&L for taking down / disconnecting of motor of capacity 2 HP to 3 HP by removing all electrical connection from panel/ starter/ foundation and cooling tower fan, transport from site to workshop and back after repairing including all required material such as bearings, terminals, rewinding with super enameled copper wire of existing gauge, varnishing etc, re-installing the same and testing including painting and writing of MES /SM No complete all as specified and as directed.
40M&L for taking down / disconnecting of motor of capacity 7.5 HP by removing all electrical connection from panel/ starter/ foundation and coupling, transport from site to workshop and back after repairing including all required material such as bearings, terminals, rewinding with super enameled copper wire of existing gauge, varnishing etc, re-installing the same and testing including painting and writing of MES /SM No complete all as specified and as directed.
41M&L for taking down / disconnecting of motor of capacity 10 HP by removing all electrical connection from panel/ starter/ foundation and coupling, transport from site to workshop and back after repairing including all required material such as bearings, terminals, rewinding with super enameled copper wire of existing gauge, varnishing etc, re-installing the same and testing including painting and writing of MES /SM No complete all as specified and as directed.
42M&L for taking down / disconnecting of motor of capacity 20 HP by removing all electrical connection from panel/ starter/ foundation and AHU Fan, transport from site to workshop and back after repairing including all required material such as bearings, terminals, rewinding with super enameled copper wire of existing gauge, varnishing etc, re-installing the same and testing including painting and writing of MES /SM No complete all as specified and as directed.
43M&L for dismantling of 20 HP motor electric from AHU and opening the same for only servicing of motor by cleaning internally and externally, varnishing of stator, greasing of bearing, fittings alignment, connecting electrically, re-fixing the same position and testing etc complete all as specified and as directed. Note : The job shall be done at plant only.
44M&L for dismantlingof 7.5 HP/10 HP motor electric from foundation and pump opening the same and only servicing of motor by cleaning internally and externally, varnishing of stator, greasing of bearing, fittings alignment, connecting electrically, re-fixing with pump after greasing & refilling gland packing of pump and testing etc complete all as specified and as directed. Note : The job shall be done at plant only.
45M&L for dismantlingof 2 HP to 3 HP motor electric from Cooling tower and opening the same and only servicing of motor by cleaninginternally and externally, varnishing of stator, greasing of bearing, fittings alignment, connecting electrically, re-fixing the same position and testing etc complete all as specified and as directed. Note :The job shall be done at plant only.
46M&L for replacement flange/Disc coupling between pump and motor into flexible flange tyre coupling to minimize vibration of metal part and also changing seal type to gland plate type of pump complete all as specified and as directed. Note : The job shall be done at plant only.
47Dismantling and strip opening of unserviceable centrifugal pump set of capacity 7.5 HP to 10 HP, segregating of serviceable/ unserviceable parts, cleaning of serviceable parts, making necessary modification/ lathe work for converting seal packing into gland packing, replacing old seal cap by new Cast Iron gland cap, assembling of pump carefully including replacement of worn-out parts grinding and polishing of shaft for fixing of bushes necking bushes nut and bolts etc. Making proper size of keys for fixing of impeller etc, getting coupled to the pump with motor, testing for rated discharge of water including transportation to the site for installing complete all as specified and as directed. Notes :- (i) Spare parts shall be measured and paid for separately as “Supply only” under relevant items of this Schedule. (ii) The rate quoted shall include the minor extras. In case of any dispute between contractor & GE regarding this aspect, the decision of Accepting Officer shall be final & binding. (iii) Spare parts for repair shall be procured from manufacturer’s authorised dealer only. (iv) All tools, testing instruments shall be arranged by the contractor including necessary transport. (v) The fixing/labour element for spare parts catered here-in-after as “Supply only” shall be deemed to be included in the quoted rate of this item.
48Supply only following spare parts for centrifugal pump set 7.5 HP to 10 HP required to be replaced under item No 46.00 here-in-before :-
49Ball bearing. Make : SKF/NBC
50Gun metal bush.
51Neck ring for impeller.
52Gun metal impeller with key.
53Supply and fixing in replacement 3 Pole contactor, AC3 rating, 415 Volts, NO/NC type of capacity 110 Amps or 75 HP, Model No A110-30 of Make : ABB or equivalent in makes mentioned in Appendix ‘B’ here-in-after as per existing specification complete all as specified and as directed.
54Supply and fixing in replacement 3 Pole contactor, AC3 rating, 415 Volts, NO/NC type of capacity 65 Amps or 50 HP, Model No A63-30 of Make ABB or equivalent in makes mentioned in Appendix ‘B’ here-in-after as per existing specification complete all as specified and as directed.
55Supply and fixing in replacement Power contactor 3 Pole NO/NC type of capacity 32 Amps as per existing specification complete all as specified and as directed.
56Supply and fixing in replacement Power contactor 3 Pole NO/NC type of capacity 25 Amps as per existing specification complete all as specified and as directed.
57Supply and fixing in replacement Power contactor 3 Pole NO/NC type of capacity 18 Amps as per existing specification complete all as specified and as directed.
58Supply and fixing in replacement auxiliary Power contactor 3 Pole NO/ NC type to be mounted on power contactor of capacity 18/ 25/ 32 Amps as per existing specification complete all as specified and as directed.
59Supply and fixing in replacement of single phase preventor 380-440 Volt +/-20% with trip setting and trip time delay model VSP-02 suitable for motor/pump set protection complete all as specified and as directed.
60Supply and fixing in replacement of electronic timer suitable for star delta starter with opertaing range 3 to 30 sec complete all as specified and as directed.
61Supply and fixing in replacement Ammeter selector switch showing line currents with OFF with CT complete all as specified and as directed.
62Supply and fixing in replacement Voltmeter selector switch showing voltage between phase& individual phase to neutral with OFF complete all as specified and as directed.
63Supply and fixing in replacement break control switch (TNC) 25 Amps with 1 Trip + 1 Close complete all as specified and as directed.
64Supply and fixing in replacement of MCCB 3 Pole, 125 Amps, thermal magnetic having, breaking capacity 16 KA, 415 Volt, 50 Hz complete all as specified and directed.
65Supply and fixing in replacement of MCCB 3 Pole, 200 Amps, thermal magnetic having, breaking capacity 25 KA, 415 Volt, 50 Hz complete all as specified and directed.
66Supply and fix in replacement Current transformer ABS CT 100/ 5A 5VA Class 1.0 single phase having 220 Volt AC input having inner dia 30mm and outer dia 75mm as per existing installed on site complete all as specified and as directed.
67Supply and fixing in replacement Manual motor starter with thermal and electromagnetic protection with rated power 0.55 KW at 415 Volt, Ie current setting range 1.00-1.60 Amp with breaking capacity 50 kA as existing Make ABB & Model MS 116 QF3 specification complete all as specified and as directed.
68Supply and fixing in replacement OS switch disconnector fuse, DIN type having rated current 315 Amp, 3 Pole with fuse size 0-2 as existing Make ABB & Model CF S3 specification complete all as specified and as directed.
69M&L for preparation of old painted surfaces by removing dust, rust, oil and applying synthetic enamel paint of approved make and colour on Pipe of size 80mm bore andincluding sluice valves in W/S installations with colour code as complete all as specified & directed.
70M&L for preparation of old painted surfaces by removing dust, rust, oil and applying synthetic enamel paint of approved make and colour on Pipe of size 100mm bore andincluding sluice valves in W/S installations with colour code as complete all as specified & directed.
71M&L for preparation of old painted surfaces by removing dust, rust, oil and applying synthetic enamel paint of approved make and colour on Pipe of size 125mm bore andincluding sluice valves in W/S installations with colour code as complete all as specified & directed.
72M&L for preparation of old painted surfaces by removing dust, rust, oil and applying synthetic enamel paint of approved make and colour on Pipe of size 150mm bore andincluding sluice valves in W/S installations with colour code as complete all as specified & directed.