Tender For Provision Of Exhaust Fans And Dg Set Of 160 Kva Under Ge Saugor, saugor-Madhya Pradesh

Military Engineer Services-MES has published Tender For Provision Of Exhaust Fans And Dg Set Of 160 Kva Under Ge Saugor. Submission Date for this Tender is 16-08-2023. Electrification Work Tenders in saugor Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

38855210
Tender For Provision Of Exhaust Fans And Dg Set Of 160 Kva Under Ge Saugor
Open Tender
Indian
Madhya Pradesh
saugor
16-08-2023

Tender Details

Tender For Provision Of Exhaust Fans And Dg Set Of 160 Kva Under Ge Saugor ; 1 M&L For One Light Pointpoint Controlled By One Switch With 1.5 Sqmm Pvc Insulated Frlsh, Class 2 Unsheathed, Copper Conductor Stranded 1100 Volt Grade Cable In & Incl Pvc Casing Caping / Conduit Of Size Not Less Than 20Mm Isi Marked Ivory White With All Accessories Such As Tee, Bend, Joint Cover Including Anodized Ms Sunken Boxes Made Out Of Ms Sheet Of Thickness Not Less Than 1.6 Mm With Earth Dolly And Pvc Laminated Hylem / Anchor Isi Marked Top Cover 3.0 Mm Thick For Mounting Of Switches / Sockets / Regulator Etc And Pvc Insulated & Unsheathed 1100 Volt Grade Copper Conductor, Stranded 1.5 Sqmm. Cable As Continuous Earth Lead Complete All As Specified And Colour Coding Of Cables Such As Phase -Red, Neutral – Black, And Earth – Green Complete All As Specified And Directed 2 S&F Switch Piano Type Flush, Single Pole, One Way, 5 Amp 230 Volt Complete All As Specified And Directed. 3 S&F Ceiling Rose, Surface Backlit, 63.5X48 Mm Three Terminal Complete All As Specified And Directed. 4 S&F Exhaust Fan, Metal Body Ac Single Phase. 230V Of Size 300Mm Sweep With 900 Rpm Blades, And Frame And Louvers Including Making Hole In Stone / Brick Masonry And Making Good To Match The Existing Surface Complete All As Specified And Directed. 5 S&F Exhaust Fan Made Of Sturdy Engineering Plastic Complete With Louvers Shutter, Voltage 230V, 50 Hz, Rpm 1200, Copper Winding Of Sweep 250Mm Including Making Hole In Stone / Brick Masonry And Making Good To Match The Existing Surface Complete All As Specified And Directed. 6 Supply And Installation Of Accoustic Enclosed Diesel Engine Driven Generating Set In Incl Minimum Of 248 Bhp / 1500 Rpmwater Cooled Multi Cylinder And Coupled With 160 Kva / 126 Kw 415 Volt 0.8P.F ( Lag ) 50 Hz Ac Alternator, Mounted On A Common Base Framewith Safeties ( Llop &Hwt ) Along With All Std Accessories I.E. Fuel Tank, Floor Mounted Standard Electric Control Panel, Battery ( Charged ) Inclusive Of One Set Of Anti Vibrration Pads ( Avm ) With Leads Exhaustsilencer As Per Std Scope Of Supply , Amf Control Panel Type 415 Volts 3 Phae 4 Wire Complete Relay Panel For Noise Free Compartement ( Acoustic Enclosure ) Housing All As Directed By Engineer-In-Charge Including Following Accessories For 160 Kva Dg Set:- 7 Diesel Engine - The Engine Shall Be Vertical Multi Cylinder Four Stroke 1500 Rpm Water Cooled With Water Pump Assembly Battery Charging Alternator Of Suitableinstrument Panel, In Built Governor Starting Battery Heavy Duty With Leads ( As Recommended By The Manufacturer ) Suitable Size And Length Of Exhaust Pipe Withnecessary Claddingmaterials, Exhaust Coupling Inside Acoustic Enclosure / Canopy, Silencer And Exhaust Pipe Above Canopy All As Specified By Oem And All Other Standard Fittnig Fixtures All As Per Oem Specification Complete As Per Iso 8528, Bs 5514 / Iso 3046 & Suitable Bhp For The Generator, ( Bhp Not Less Than 299 Bhp ) All As Directed By Engineer-In-Charge. 8 Ac Alternator : The Ac Alternator ( Generator ) Shall Be Designed For An Out Put Of 160 Kva / 126 Kw, 50 Hz At Full Load For Continuous Rating & 10 % Forover Loadfor One Hour At 0.8 ( Lag ) Pf Confirming To Bs - 5000 Part 99 / Is 4722 Including Self Excited And Self Regulating Screen Protected , Standard Panelwith All Accessories Cable Terminal Box Suitable Size Of Glands Earth Terminal Etc. Complete All As Per Oem Specifications All As Directed By Engineer-In-Charge. 9 Fuel ( Services ) Tank:- The Fuel Tank Shall Be Builtin Type Of Capacity To Run Minimun As 12 Hours On Full Loadand Shall Include Fuel Level Indicator Fuel Piping Internally With Necessary Pipingas Recommended By The Manufacturer From Tank To Engine And For Over Flow Etc., Complete All As Specified And Directed By Engr-In-Charge. 10 The Tools As Per The ManufacturerS List Shall Be Provided By The Contractor Alongwith The Set At No Extra Cost. 11 Unit Rate Quoted Shall Deemed Include The Control Cableof Suitable Rating / Capacity From Dg Set To Amf Panel, Diesel Lub Oil, Coolant For Radiatoretcfor Smoothfunctioning Of Dg Setduringph I& Ph I I Complete Testing And Initial Fulltank Filling Ofdiesel Oil Afterph I& Ph I Itesting, Topping Ofdiesel, Lub Oil, Coolant For Radiator Etc Required For Commissioning And Testing Of Dg Set . 12 Inverter 50 W Capacity Suitable For Led Bulbs With All Accessorieswith Necessary Connections And Wiring From Dg Set Battery.Inside Theacoustic Enclosure . 13 Supply, Laying, Jointing Testing And Commissioining Cross Linked Polythylene ( Xlpe ) Insulated Cable For Working Voltages Of 1100 V Pvc Sheathed, Armoured, 3 Core With Reduced Neutral Conductor 3.5 Core Nominal Cross Sectional Area Of Main Conductor150sqmm Strandedaluminium Conductor Isi Markedas Per Is 7098 ( Parrt-I ) 1988 Including Cavle Glands, , Lugs Etc To Suit The Cable Size And To Be Lain Intrenches, Fixed Along Pole, Under Floors, Through Gi Pipe Lain Under Floors / Roads, Through Concealed Gi Pipe Along Wall Etc Complette All As Specified And As Directed 14 M&L For Earthing32mmx6mm Complete With Galvanised Steel Earth Plate Electrode 600Mm X 600Mm X 6 Mm Thick, Burried Directly In Ground ( Earth Pitnot Less Than 2.25 M Below Ground Level ) With The Top Edge Of Earth Plate At Depth Not Less Than 1.5 M Below Ground Level, Connected To Galvanised Eath Lead Wire 4.0 Mm Dia By Means Of Bolts, Nuts, Check Nuts And Washers Of Galvanised Iron Or Steel All As Shown In Electrical Plate No. 5 Connected To Earthing Test Point All As Specified Or Indicated Including Testing On Completion.Complete All As Specified And As Directed 15 M&L For On Load Change Over Switch 160 Amps , 415V, 4 Pole, 160 Amps With Ss Enclosure Item Code No.Ihcnfe0160 Complete All As Specified And Directed 16 M&L For Synthetic Rubber Insulated Mats 3.0 Mm Thick For Electrical Purpose As Per Is 15652-2006 ( Superseding Is 5424 ) Suitable For Electrical Shock Safety Of Sizes 2Mx1m Complete All As Specified And Directed

Key Value

Document Fees
INR 500 /-
EMD
INR 69000.0 /-
Tender Value
INR 34.50 Lakhs /-

BOQ Items

Name of Work: PROVN OF EXHAUST FANS & 160 KVA DG SET UNDER GE SAUGOR
Sl. No. Item Description
1M&L for one light pointpoint controlled by one switch with 1.5 Sqmm PVC insulated FRLSH, Class 2 unsheathed, copper conductor stranded 1100 volt grade cable in & incl PVC Casing caping/ conduit of size not less than 20mm ISI marked ivory white with all accessories such as tee, bend, joint cover including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and PVC laminated hylem/Anchor ISI marked top cover 3.0 mm thick for mounting of switches/sockets/ regulator etc and PVC insulated & unsheathed 1100 volt grade copper conductor, stranded 1.5 sqmm. cable as continuous earth lead complete all as specified and colour coding of cables such as Phase -Red, Neutral – Black, and Earth – Green complete all as specified and directed
2S&F switch piano type flush, single pole, one way, 5 Amp 230 Volt complete all as specified and directed.
3S&F ceiling rose, surface backlit, 63.5x48 mm three terminal complete all as specified and directed.
4S&F exhaust fan, metal body AC single Phase. 230V of size 300MM sweep with 900 RPM blades, and frame and louvers including making hole in stone/brick masonry and making good to match the existing surface complete all as specified and directed.
5S&F exhaust fan made of sturdy engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250MM including making hole in stone/brick masonry and making good to match the existing surface complete all as specified and directed.
6Supply and installation of Accoustic Enclosed diesel engine driven generating set in incl minimum OF 248 BHP / 1500 RPMwater cooled multi cylinder and coupled with 160 KVA /126 KW 415 Volt 0.8P.F ( Lag )50 Hz AC alternator, mounted on a common base framewith Safeties(LLOP &HWT) along with all std accessories i.e. fuel tank,floor mounted standard electric control panel, Battery(Charged) inclusive of one set of Anti Vibrration Pads(AVM) with leads exhaustsilencer as per std scope of supply , AMF Control panel type 415 Volts 3 phae 4 wire complete relay panel for noise free compartement (acoustic enclosure ) housing all as directed by Engineer-In-Charge including following accessories for 160 KVA DG Set:-
7Diesel Engine - The engine shall be vertical multi cylinder four stroke 1500 RPM water cooled with water pump assembly battery charging alternator of suitableinstrument panel, in built governor starting battery heavy duty with leads (as recommended by the manufacturer) suitable size and length of exhaust pipe withnecessary claddingmaterials,exhaust coupling inside acoustic enclosure / canopy,silencer and exhaust pipe above canopy all as specified by OEM and all other standard fittnig fixtures all as per OEM specification complete as per ISO 8528, BS 5514 / ISO 3046 & suitable BHP for the generator,(BHP not less than 299 BHP) all as directed by Engineer-In-Charge.
8AC Alternator : The AC alternator (Generator) shall be designed for an out put of 160 KVA / 126 KW,50 HZ at full load for continuous rating & 10 % forover loadfor one hour at 0.8 ( lag ) PF confirming to BS - 5000 part 99/IS 4722 including self excited and self regulating screen protected ,standard panelwith all accessories cable terminal box suitable size of glands earth terminal etc. complete all as per OEM specifications all as directed by Engineer-In-Charge.
9Fuel (Services) Tank:- The fuel tank shall be builtin type of capacity to run minimun as 12 hours on full loadand shall include fuel level indicator fuel piping internally with necessary pipingas recommended by the manufacturer from tank to engine and for over flow etc., complete all as specified and directed by Engr-in-Charge.
10The tools as per the manufacturer"s list shall be provided by the contractor alongwith the set at no extra cost.
11Unit rate quoted shall deemed include the Control cableof suitable rating / capacity from DG set to AMF panel, Diesel lub oil, Coolant for Radiatoretcfor smoothfunctioning of DG SetduringPH I& PH I I complete testing and initial fulltank filling ofDiesel Oil afterPH I& PH I Itesting,topping ofDiesel, Lub oil,Coolant for Radiator etc required for commissioning and testing of DG set .
12Inverter 50 W capacity Suitable for LED bulbs with all accessorieswith necessary connections and wiring from DG Set Battery.inside theacoustic enclosure .
13Supply, laying, jointing testing and commissioining cross linked polythylene (XLPE) insulated cable for working voltages of 1100 V PVC sheathed, armoured, 3 core with reduced neutral conductor 3.5 core nominal cross sectional area of main conductor150sqmm strandedaluminium conductor ISI markedas per IS 7098(Parrt-I) 1988 including cavle glands, , lugs etc to suit the cable size and to be lain intrenches, fixed along pole, under floors, through GI pipe lain under floors/roads, through concealed GI pipe along wall etc complette all as specified and as directed
14M&L for earthing32mmx6mm complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick, burried directly in ground (earth pitnot less than 2.25 m below ground level) with the top edge of earth plate at depth not less than 1.5 m below ground level, connected to galvanised eath lead wire 4.0 mm dia by means of bolts, nuts,check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion.complete all as specified and as directed
15M&L for On load change over switch 160 Amps , 415V, 4 Pole, 160 Amps with SS enclosure item Code No.IHCNFE0160 complete all as specified and directed
16M&L for Synthetic rubber insulated mats 3.0 mm thick for electrical purpose as per IS 15652-2006 (Superseding IS 5424) suitable for electrical shock safety of sizes 2mx1m complete all as specified and directed