Water Resources and Irrigation Government Departments Closing in 0 days TDR #38848364

Improvement Of Various Water Supply Scheme By Source Strengthening, Replacement Of Old Pumping Machinery, Restoration/ Construction Of Old Pump House And Allied Structure In Gagret Constituency In Distt Una (Hp) Daulatpur Sub Division Pumping Machinery (S

Issued by Government Departments · gagret, Himachal Pradesh
Tender Value
89.90 Lakhs
Estimated cost
Bid Submission
07 Aug 2023
0 days left
EMD
1.22 Lakhs
Bank guarantee accepted
Document Fee
800
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
gagret → Himachal Pradesh
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Improvement Of Various Water Supply Scheme By Source Strengthening, Replacement Of Old Pumping Machinery, Restoration / Construction Of Old Pump House And Allied Structure In Gagret Constituency In Distt Una ( Hp ) Daulatpur Sub Division Pumping Machinery ( Sh;- S / E Of Pumping Machinery With Allied Accessories For T / Well At Amlehar Bhanjal, T / Well At Nakroh, T / Well At Gondpur Banehra, T / Well At Bhaderkali, T / Well At Dangoh, T / Well At Joh, T / Well At Abhaypur, T / Well At Babehar, T / Well Ganu Mandwara, T / Well At Raipur Marwari Etc

BOQ

Name of Work :Improvement of Various Water Supply Scheme by Source Strengthening, Replacement of old Pumping Machinery, Restoration/ Construction of old Pump House and allied structure in Gagret Constituency in Distt Una (HP) Daulatpur Sub Division Pumping Machinery (sH;- S/E of Pumping Machinery with allied accessories for T/well at Amlehar Bhanjal, T/well at Nakroh, T/well at Gondpur Banehra, T/well at Bhaderkali, T/well at Dangoh, T/well at Joh, T/well at Abhaypur, T/well at Babehar, T/well Ganu Mandwara, T/well at Raipur Marwari etc.
Sl. No. Item Description
1Submersible Pump Sets for WSS Amlehar Bhanjal Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
2Discharge, (Q)5.36LPS
3Total Head ( H ) 89.43 Mts.
4SWL in Tubewell 39.00 mtr. bgl.
5R.L. point of discharge 103 .00 mtr
6R.L. of Pump House =100.00Ntrs
7Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
8Drawdown in Tubewell35.00 mtrs.
9StaticHead = 86mtrs.
10Static suction lift3mtrs.
11Rising main Column pipe
12Length 10 mtrs Length 93 mtr
13Dia 125 mm (M) Dia 125 mm (M)
14Class GMS
15iv) Pumping hours8 hours
16v) Alititude of installations above M.S.L 100mtr
17vi) Characteristic of water
18(vii) Temperature :20.00Deg. C
19(viii) Ambient temperature42.00Deg. C
20(ix) Turbidity < than 50.00NTU
21(x) Alkalinity Mg/Ca Co3
22(xi) Size of the solidsmm
23xii) others
24xiii) Depth of T/well mtr
25ix) Dia of T/well assembly 300/200 mm
26Length of assembly pipe
27Dia of housing pipe
28Length of housing pipe
29OPERATING CONDITIONS
30i) Type of current A.C Three phases.
31ii) Frequency 50 Cycles/ Sec.
32iii) Rated Voltage 415+/-10% Volts
33iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
34v) Speed of Revolution __________________ RPM 2900
35MOTOR
36i) Ref to BIS codeBIS 9283-1979 with upto date amendments
37ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
38iii) Mechnical out put in HP
39iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
40PUMP
41i) Ref to BIS codeBIS 5659-1978 with upto date amendments
42ii) Driver Type Electric drivern
43iii) Operating Range -25%to +10% of Total head at duty point
44iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
45Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :63 amp.
46Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
47MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range63 amp. iv) Capacity
48ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
49The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range
50A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
51AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 30 Amp.
52Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
53Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 4 KVAR
54Providing suitable Air Break TypeStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
55Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
56Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
57Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 125 mm dia.
58Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :
59Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-6
60Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M) Existing safe
61Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
62Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2(10/6 mm 2)ii) Make iii)Type iv) Capacity v)Core 3
63(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 (10/6 mm 2)ii) Make iii) Type iv) Capacity v) Core 3
64Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt, as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP copper 12 SWG upto 15 HP.
65Centrifugal Pump Set for Amlaher Bhanjal Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
66Discahrge (Q) := 5.36 LPS
67Total Head (H) =203.61 mts.
68(a) SWL in sump well (h) : 100 Mtrs
69(b) Shaft level :100mtrs.
70(c ) Level at discahrge point : 215.48 mtrs.
71(d) Suction lift :, +tive
72(e) Residual head :3 Mtrs
73(f) Static head :115.48 Mtrs
74(i) Rising Main :
75(a) Length 2640 Mtrs
76(b) Dia. :80 mm
77(iv) Pumping Hours : 8 Hours
78(v) Altitude of installation above MSL :100 mtrs
79(vi) Characteristics of water :
80(a) Temperature :20.00Deg. C
81(b) Ambient temperature42.00Deg. C
82(c ) Turbidity < than 50.00NTU
83(d) Alkalinity Mg/Ca Co3
84(e) Size of the solidsmm
85(f) Other
86Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
87Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
88M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 63 Amp
89(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B.63 Amp (i) Make Havells (ii) Type(iii) Range ; suitable rating
90100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V Make AE/L&T.
91Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
92Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
93Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
94ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :-(i) MakeL&T/ Havells(ii) Model (iii) Capacity ; 63 Amp
95Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
96100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 60 Amp
97Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 7 KVAR
98Providing suitable AutoStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
99Single Phase Preventor. (i) Type.Oil Emmersible (ii) Make. Star dalta
100Providing Cast ironflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe80 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
101Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
102Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
103Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
104Providing 65 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
105Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
106Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
107i) Suction Pipe 80 mm dia.
108ii)Delivery Pipe 65 mm dia.
109iii) Common Header 80 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 80 mm dia to be joined.
110Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size 2x4.00mm (16 mm2ii) Make iii)Type iv) Capacity v)Core 3
111(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 (10/6 mm 2)ii) Make iii) Type iv) Capacity v) Core 3
112Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt, as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 6SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
113Submersible Pump Sets for WSS Nakroh Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
114Discharge, (Q)6.10 LPS
115Total Head ( H ) 64.02 Mts.
116SWL in Tubewell40.65 mtr. bgl.
117R.L. point of discharge 101.33 mtr
118R.L. of Pump House = 100
119Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
120Drawdown in Tubewell 6.00 mtrs.
121StaticHead = 60.68 mtrs.
122Static suction lift3mtrs.
123Rising main Column pipe
124Length 10 mtrs Length67.68 mtr
125Dia 125 mm (M) Dia 125 mm (M)
126Class GMS
127iv) Pumping hours8 hours
128v) Alititude of installations above M.S.L 100 mtr
129vi) Characteristic of water
130(vii) Temperature :20.00Deg. C
131(viii) Ambient temperature42.00Deg. C
132(ix) Turbidity < than 50.00NTU
133(x) Alkalinity Mg/Ca Co3
134(xi) Size of the solidsmm
135xii) others
136xiii) Depth of T/well mtr
137ix) Dia of T/well assembly 300/200 mm
138Length of assembly pipe
139Dia of housing pipe
140Length of housing pipe
141OPERATING CONDITIONS
142i) Type of current A.C Three phases.
143ii) Frequency 50 Cycles/ Sec.
144iii) Rated Voltage 415+/-10% Volts
145iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
146v) Speed of Revolution __________________ RPM 2900
147MOTOR
148i) Ref to BIS codeBIS 9283-1979 with upto date amendments
149ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
150iii) Mechnical out put in HP
151iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
152PUMP
153i) Ref to BIS codeBIS 5659-1978 with upto date amendments
154ii) Driver Type Electric drivern
155iii) Operating Range -25%to +10% of Total head at duty point
156iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
157Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :32 amp.
158Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
159MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range32 amp. iv) Capacity
160ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
161The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range
162A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
163AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 30 Amp.
164Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
165Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 3 KVAR
166Providing suitable Air Break TypeStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
167Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
168Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
169Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 125 mm dia.
170Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :
171Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-4
172Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M)Existing safe
173Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
174Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2 ii) Make iii)Type iv) Capacity v)Core 3
175(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
176Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 12 SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP Coipper up to 15 HP 12 SWG.
177Centrifugal Pump Set for WSS Nakroh Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
178Discahrge (Q) := 6.10 LPS
179Total Head (H) =201.77 mts.
180(a) SWL in sump well (h) :98.33 Mtrs
181(b) Shaft level :98.33mtrs.
182(c ) Level at discahrge point : 249.40 mtrs.
183(d) Suction lift :, +tive
184(e) Residual head :3 Mtrs
185(f) Static head :151.07 Mtrs
186(i) Rising Main :
187(a) Length3390 Mtrs
188(b) Dia. :100 mm
189(iv) Pumping Hours : 8 Hours
190(v) Altitude of installation above MSL :98.33 mtrs
191(vi) Characteristics of water :
192(a) Temperature :20.00Deg. C
193(b) Ambient temperature42.00Deg. C
194(c ) Turbidity < than 50.00NTU
195(d) Alkalinity Mg/Ca Co3
196(e) Size of the solidsmm
197(f) Other
198Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
199Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
200M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 63 Amp
201(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B. 63 Amp(i) Make (ii) Type (iii) Range ; suitable rating
202100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
203Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
204Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
205Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
206ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
207Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
208100 mm diametres AC supplyAmmeter of L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 60 Amp
209Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 7 KVAR
210Providing suitable AutoStar delta starter of Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oiel immersed star delta (ii) Make.
211Single Phase Preventor. (i) Type.Oil Emmersible (ii) Make. Star dalta
212Providing Cast ironflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar//Kartarmake for Suction Pipe80 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
213Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
214Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
215Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
216Providing 65 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
217Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
218Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
219i) Suction Pipe 80 mm dia.
220ii)Delivery Pipe 65 mm dia.
221iii) Common Header 100 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 100 mm dia to be joined.
222Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x10.00 mm2(10/6 mm 2)ii) Make iii)Type iv) Capacity v)Core 3
223(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x16.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
224Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x3 mm Above50 HP Copper for 30 HP=8 swg.
225Submersible Pump Sets for WSS Gondpur Banehra Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
226Discharge, (Q) 6.46 LPS
227Total Head ( H ) 67.33 Mts.
228SWL in Tubewell45.72 mtr. bgl.
229R.L. point of discharge 98.00 mtr
230R.L. of Pump House =
231Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
232Drawdown in Tubewell 6.10 mtrs.
233StaticHead = 63.82mtrs.
234Static suction lift3mtrs.
235Rising main Column pipe
236Length 10 mtrs Length70.82 mtr
237Dia 125 mm (M) Dia 125 mm (M)
238Class GMS
239iv) Pumping hours8 hours
240v) Alititude of installations above M.S.L 95 mtr
241vi) Characteristic of water
242(vii) Temperature :20.00Deg. C
243(viii) Ambient temperature42.00Deg. C
244(ix) Turbidity < than 50.00NTU
245(x) Alkalinity Mg/Ca Co3
246(xi) Size of the solidsmm
247xii) others
248xiii) Depth of T/well mtr
249ix) Dia of T/well assembly 300/200 mm
250Length of assembly pipe
251Dia of housing pipe
252Length of housing pipe
253OPERATING CONDITIONS
254i) Type of current A.C Three phases.
255ii) Frequency 50 Cycles/ Sec.
256iii) Rated Voltage 415+/-10% Volts
257iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
258v) Speed of Revolution __________________ RPM 2900
259MOTOR
260i) Ref to BIS codeBIS 9283-1979 with upto date amendments
261ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
262iii) Mechnical out put in HP
263iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
264PUMP
265i) Ref to BIS codeBIS 5659-1978 with upto date amendments
266ii) Driver Type Electric drivern
267iii) Operating Range -25%to +10% of Total head at duty point
268iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
269Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :63 amp.
270Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
271MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range63 amp. iv) Capacity
272ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
273The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range
274A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
275AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 60 Amp.
276Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
277Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 4 KVAR
278Providing suitable Air Break TypeStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
279Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
280Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
281Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:5312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 125 mm dia.
282Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make : Range 0-52 Kg/cm2
283Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-6
284Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M) Existing safe
285Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
286Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2(10/6 mm 2)ii) Make iii)Type iv) Capacity v)Core 3
287(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 (10/6 mm 2)ii) Make iii) Type iv) Capacity v) Core 3
288Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
289Centrifugal Pump Set for WSS Gondpur Banehra Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
290Discahrge (Q) := 6.46 LPS
291Total Head (H) =100.72 mts.
292(a) SWL in sump well (h) :95.00 Mtrs
293(b) Shaft level : mtrs.
294(c ) Level at discahrge point : 164.40 mtrs.
295(d) Suction lift :, +tive
296(e) Residual head :3 Mtrs
297(f) Static head :69.40 Mtrs
298(i) Rising Main :
299(a) Length1810 Mtrs
300(b) Dia. :100 mm
301(iv) Pumping Hours : 8 Hours
302(v) Altitude of installation above MSL : 95 mtrs
303(vi) Characteristics of water :
304(a) Temperature :20.00Deg. C
305(b) Ambient temperature42.00Deg. C
306(c ) Turbidity < than 50.00NTU
307(d) Alkalinity Mg/Ca Co3
308(e) Size of the solidsmm
309(f) Other
310Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
311Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
312M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 63 Amp
313(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B. 63 Amp (i) Make(ii) Type (iii) Range ; suitable rating
314100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
315Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
316Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
317Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
318ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
319Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
320100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 60 Amp
321Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 5 KVAR
322Providing suitable AutoStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
323Single Phase Preventor. (i) Type.Oil Emmersible (ii) Make. Star dalta
324Providing Cast ironflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe80 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
325Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
326Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
327Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
328Providing 65 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
329Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
330Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
331i) Suction Pipe 80 mm dia.
332ii)Delivery Pipe 65 mm dia.
333iii) Common Header 100 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 100 mm dia to be joined.
334Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x6.00 mm2(10/6 mm 2)ii) Make iii)Type iv) Capacity v)Core 3
335(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x10.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
336Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
337Submersible Pump Sets for WSS Bhaderkali Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
338Discharge, (Q)8.29 LPS
339Total Head ( H ) 85.95 Mts.
340SWL in Tubewell20.20 mtr. bgl.
341R.L. point of discharge102.20 mtr
342R.L. of Pump House =
343Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
344Drawdown in Tubewell 10.00 mtrs.
345StaticHead = 85.95 mtrs.
346Static suction lift3mtrs.
347Rising main Column pipe
348Length 10 mtrs Length89 mtr
349Dia 125 mm (M) Dia 125 mm (M)
350Class GMS
351iv) Pumping hours8 hours
352v) Alititude of installations above M.S.L 100mtr
353vi) Characteristic of water
354(vii) Temperature :20.00Deg. C
355(viii) Ambient temperature42.00Deg. C
356(ix) Turbidity < than 50.00NTU
357(x) Alkalinity Mg/Ca Co3
358(xi) Size of the solidsmm
359xii) others
360xiii) Depth of T/well mtr
361ix) Dia of T/well assembly 300/200 mm
362Length of assembly pipe
363Dia of housing pipe
364Length of housing pipe
365OPERATING CONDITIONS
366i) Type of current A.C Three phases.
367ii) Frequency 50 Cycles/ Sec.
368iii) Rated Voltage 415+/-10% Volts
369iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
370v) Speed of Revolution __________________ RPM 2900
371MOTOR
372i) Ref to BIS codeBIS 9283-1979 with upto date amendments
373ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
374iii) Mechnical out put in HP
375iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
376PUMP
377i) Ref to BIS codeBIS 5659-1978 with upto date amendments
378ii) Driver Type Electric drivern
379iii) Operating Range -25%to +10% of Total head at duty point
380iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
381Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :63 amp.
382Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
383MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range63 amp. iv) Capacity
384ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
385The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500V
386A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
387AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 60 Amp.
388Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
389Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 5 KVARamendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
390Providing suitable Air Break TypeStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Oil Immeried Type Star Deltaiii) Range.
391Single Phase Preventor i) Make : ii) Type : Oil ImmeriedType Star Deltaiii) Range.
392Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
393Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 125 mm dia.
394Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :
395Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-6
396Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M)Existing safe
397Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
398Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x6.00 mm2 ii) Make iii)Type iv) Capacity v)Core 3
399(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x10.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
400Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
401Centrifugal Pump Set for WSS Bhaderkali Providing horizontal spindle ,horizontal / radial split casing / end suction (back pull out arrangement). Single / double / multi stage centrifugal pump or combination of pumps in series / parallel of recommended make such as Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyoti/LUBI/GROUNDFOS /HINDUSTANas per BIS IS 1520 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for liftingwater forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor/,motors of standard make such as Kirloskar /Bhel /Crompton/NGEF /GEC/ Seimens /jyoti/ LUBI/GROUNDFOS/HINDUSTAN and suitable for operation on415 (+/-5%) volts. 50 Cycles/Sec., 3 phase AC electric supply. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor/motors as per IS 325 IS 1978 with upto date amendments read with IS 9001972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements. i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
402Discahrge (Q) := 8.29LPS
403Total Head (H) =176.05 mts.
404(a) SWL in sump well (h) : 99.20 Mtrs
405(b) Shaft level :99.20 mtrs.
406(c ) Level at discahrge point : 233.10mtrs.
407(d) Suction lift :, +tive
408(e) Residual head :3 Mtrs
409(f) Static head : 133.90 Mtrs
410(i) Rising Main :
411(a) Length1640 Mtrs
412(b) Dia. :100 mm
413(iv) Pumping Hours : 8 Hours
414(v) Altitude of installation above MSL :99.20 mtrs
415(vi) Characteristics of water :
416(a) Temperature :20.00Deg. C
417(b) Ambient temperature42.00Deg. C
418(c ) Turbidity < than 50.00NTU
419(d) Alkalinity Mg/Ca Co3
420(e) Size of the solidsmm
421(f) Other
422Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;100 Amp
423Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
424M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 100 Amp
425(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B.63Amp(i) Make(ii) Type (iii) Range ; suitable rating
426100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
427Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
428Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
429Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
430ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ; 100 Amp
431Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
432100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 100 Amp
433Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 9 KVAR
434Providing suitable AutoStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
435Single Phase Preventor. (i) Type.Oil Emmersed (ii) Make. Star dalta
436Providing Cast steelflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe100 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
437Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
438Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
439Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 100 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
440Providing 80 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
441Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
442Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
443i) Suction Pipe 100 mm dia.
444ii)Delivery Pipe 80 mm dia.
445iii) Common Header 100 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 100 mm dia to be joined.
446Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x16.00 mm2)ii) Make iii)Type iv) Capacity v)Core 3
447(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x25.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
448Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 6SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
449Submersible Pump Sets for WSS Dangoh Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 25% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
450Discharge, (Q)9.54 LPS
451Total Head ( H ) 93.41 Mts.
452SWL in Tubewell 34.44 mtr. bgl.
453R.L. point of discharge 103.00 mtr
454R.L. of Pump House =
455Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
456Drawdown in Tubewell 42.67 mtrs.
457Static Head = 89.11mtrs.
458Static suction lift3mtrs.
459Rising main Column pipe
460Length 10 mtrs Length96.11 mtr
461Dia 125 mm (M) Dia 125 mm (M)
462Class GMS
463iv) Pumping hours8 hours
464v) Alititude of installations above M.S.L 95mtr
465vi) Characteristic of water
466(vii) Temperature :20.00Deg. C
467(viii) Ambient temperature42.00Deg. C
468(ix) Turbidity < than 50.00NTU
469(x) Alkalinity Mg/Ca Co3
470(xi) Size of the solidsmm
471xii) others
472xiii) Depth of T/well mtr
473ix) Dia of T/well assembly 300/200 mm
474Length of assembly pipe
475Dia of housing pipe
476Length of housing pipe
477OPERATING CONDITIONS
478i) Type of current A.C Three phases.
479ii) Frequency 50 Cycles/ Sec.
480iii) Rated Voltage 415+/-10% Volts
481iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
482v) Speed of Revolution __________________ RPM 2900
483MOTOR
484i) Ref to BIS codeBIS 9283-1979 with upto date amendments
485ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
486iii) Mechnical out put in HP
487iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
488PUMP
489i) Ref to BIS codeBIS 5659-1978 with upto date amendments
490ii) Driver Type Electric drivern
491iii) Operating Range -25%to +10% of Total head at duty point
492iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
493Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :63 amp.
494Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
495MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range63 amp. iv) Capacity
496ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
497The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500V
498A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
499AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 63 Amp.
500Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
501Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 6 KVAR
502Providing suitable oil immmersed Star delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type :oil immmersed Star delta starteriii) Range.
503Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
504Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
505Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 125 mm dia.
506Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :
507Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-6(10/6 mm 2 Copper .
508Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M)Existing safe
509Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
510Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2 ii) Make iii)Type iv) Capacity v)Core 3
511(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
512Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 6SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
513Centrifugal Pump Set for WSS Dangoh Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
514Discahrge (Q) := 9.54 LPS
515Total Head (H) =118.17 mts.
516(a) SWL in sump well (h) : 100 Mtrs
517(b) Shaft level :100mtrs.
518(c ) Level at discahrge point : 195.60 mtrs.
519(d) Suction lift :, +tive
520(e) Residual head :3 Mtrs
521(f) Static head :95.60 Mtrs
522(i) Rising Main :
523(a) Length1875 Mtrs
524(b) Dia. :125 mm
525(iv) Pumping Hours : 8 Hours
526(v) Altitude of installation above MSL :100 mtrs
527(vi) Characteristics of water :
528(a) Temperature :20.00Deg. C
529(b) Ambient temperature42.00Deg. C
530(c ) Turbidity < than 50.00NTU
531(d) Alkalinity Mg/Ca Co3
532(e) Size of the solidsmm
533(f) Other
534Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
535Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
536M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 63 Amp
537(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B. 63 AMP(i) Make(ii) Type (iii) Range ; suitable rating
538100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
539Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
540Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
541Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
542ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ; 63 Amp
543Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
544100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 30 Amp
545Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 7 KVAR
546Providing suitable AutoStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
547Single Phase Preventor. (i) Type.Oil Emmersible (ii) Make. Star dalta
548Providing Cast ironflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe125 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
549Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 100 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
550Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 100 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
551Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 125 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
552Providing 100 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :0-52 Kg/cm2.
553Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
554Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
555i) Suction Pipe 125 mm dia.
556ii)Delivery Pipe 100 mm dia.
557iii) Common Header 125 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 125 mm dia to be joined.
558Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size 2x10.00 mm2)ii) Make iii)Type iv) Capacity v)Core 3
559(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x16.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
560Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
561Submersible Pump Sets for WSS Joh Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
562Discharge, (Q)10.47 LPS
563Total Head ( H ) 58.53 Mts.
564SWL in Tubewell 34.75 mtr. bgl.
565R.L. point of discharge 103mtr
566R.L. of Pump House =
567Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
568Drawdown in Tubewell 7.62 mtrs.
569StaticHead = 54.37mtrs.
570Static suction lift3mtrs.
571Rising main Column pipe
572Length 10 mtrs Length61.37 mtr
573Dia 125 mm (M) Dia 125 mm (M)
574Class GMS
575iv) Pumping hours8 hours
576v) Alititude of installations above M.S.L 100 mtr
577vi) Characteristic of water
578(vii) Temperature :20.00Deg. C
579(viii) Ambient temperature42.00Deg. C
580(ix) Turbidity < than 50.00NTU
581(x) Alkalinity Mg/Ca Co3
582(xi) Size of the solidsmm
583xii) others
584xiii) Depth of T/well mtr
585ix) Dia of T/well assembly 300/200 mm
586Length of assembly pipe
587Dia of housing pipe
588Length of housing pipe
589OPERATING CONDITIONS
590i) Type of current A.C Three phases.
591ii) Frequency 50 Cycles/ Sec.
592iii) Rated Voltage 415+/-10% Volts
593iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
594v) Speed of Revolution __________________ RPM 2900
595MOTOR
596i) Ref to BIS codeBIS 9283-1979 with upto date amendments
597ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
598iii) Mechnical out put in HP
599iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
600PUMP
601i) Ref to BIS codeBIS 5659-1978 with upto date amendments
602ii) Driver Type Electric drivern
603iii) Operating Range -25%to +10% of Total head at duty point
604iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
605Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :63 amp.
606Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
607MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range63 amp. iv) Capacity
608ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
609The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500 V.
610A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
611AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 60 Amp.
612Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
613Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 4 KVAR
614Providing suitable Air Break TypeStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
615Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
616Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
617Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 125 mm dia.
618Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :0-52 Kg/Cum2
619Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-6mm2 (4/2.5 mm 2 Copper ).
620Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M) Existing safe
621Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
622Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2 ii) Make iii)Type iv) Capacity v)Core 3
623(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
624Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 8 SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
625Centrifugal Pump Set for WSSJoh Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
626Discahrge (Q) := 10.47 LPS
627Total Head (H) =210.59 mts.
628(a) SWL in sump well (h) : 100 Mtrs
629(b) Shaft level :100mtrs.
630(c ) Level at discahrge point : 259.40 mtrs.
631(d) Suction lift :, +tive
632(e) Residual head :3 Mtrs
633(f) Static head :159.40 Mtrs
634(i) Rising Main :
635(a) Length3960 Mtrs
636(b) Dia. :125 mm
637(iv) Pumping Hours : 8 Hours
638(v) Altitude of installation above MSL :100 mtrs
639(vi) Characteristics of water :
640(a) Temperature :20.00Deg. C
641(b) Ambient temperature42.00Deg. C
642(c ) Turbidity < than 50.00NTU
643(d) Alkalinity Mg/Ca Co3
644(e) Size of the solidsmm
645(f) Other
646Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;200 Amp
647Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
648O.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 100 Amp
649(ii) E.L.R. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.R. (i) Make(ii) Type(iii) Range ; suitable rating
650100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
651Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
652Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
653Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
654ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ; 200 Amp
655Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
656100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 200 Amp
657Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 13 KVAR
658Providing suitable AutoStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
659Single Phase Preventor. (i) Type.Oil Emmersible (ii) Make. Star dalta
660Providing Cast steelflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe125 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
661Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 100 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
662Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 100 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
663Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 125 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
664Providing 100mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range : 0-52 Kg/cm2
665Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
666Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
667i) Suction Pipe 125 mm dia.
668ii)Delivery Pipe 100 mm dia.
669iii) Common Header 125 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 125 mm dia to be joined.
670Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x25.00 mm2)ii) Make iii)Type iv) Capacity v)Core 3
671(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x50.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
672Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 6SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
673Centrifugal Pump Set for WSSAbheypur Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
674Discahrge (Q) := 3.11LPS
675Total Head (H) =227.06mts.
676(a) SWL in sump well (h) : 100 Mtrs
677(b) Shaft level :100mtrs.
678(c ) Level at discahrge point : 279.26 mtrs.
679(d) Suction lift :, +tive
680(e) Residual head :3 Mtrs
681(f) Static head :179.26 Mtrs
682(i) Rising Main :
683(a) Length3990 Mtrs
684(b) Dia. :80 mm
685(iv) Pumping Hours : 8 Hours
686(v) Altitude of installation above MSL :100 mtrs
687(vi) Characteristics of water :
688(a) Temperature :20.00Deg. C
689(b) Ambient temperature42.00Deg. C
690(c ) Turbidity < than 50.00NTU
691(d) Alkalinity Mg/Ca Co3
692(e) Size of the solidsmm
693(f) Other
694Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
695Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
696M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 63 Amp
697(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B. 63 Amp (i) Make(ii) Type (iii) Range ; suitable rating
698100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
699Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
700Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
701Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
702ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
703Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
704100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 60 Amp
705Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 5 KVAR
706Providing suitable AutoStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
707Single Phase Preventor. (i) Type.Oil immersed (ii) Make. Star dalta
708Providing Cast ironflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe100 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
709Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
710Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
711Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
712Providing 80 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
713Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
714Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
715i) Suction Pipe 80mm dia.
716ii)Delivery Pipe 65 mm dia.
717iii) Common Header 80 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 80 mm dia to be joined.
718Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2)ii) Make iii)Type iv) Capacity v)Core 3
719(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x10.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
720Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 8SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
721Submersible Pump Sets for WSS Babehar Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
722Discharge, (Q)3.99 LPS
723Total Head ( H ) 60.16 Mts.
724SWL in Tubewell38.00 mtr. bgl.
725R.L. point of discharge 102.20 mtr
726R.L. of Pump House =
727Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
728Drawdown in Tubewell 6.50 mtrs.
729StaticHead = 56.50mtrs.
730Static suction lift3mtrs.
731Rising main Column pipe
732Length 10 mtrs Length63.50 mtr
733Dia 80 mm (M) Dia 125 mm (M)
734Class GMS
735iv) Pumping hours8 hours
736v) Alititude of installations above M.S.L 99.20 mtr
737vi) Characteristic of water
738(vii) Temperature :20.00Deg. C
739(viii) Ambient temperature42.00Deg. C
740(ix) Turbidity < than 50.00NTU
741(x) Alkalinity Mg/Ca Co3
742(xi) Size of the solidsmm
743xii) others
744xiii) Depth of T/well mtr
745ix) Dia of T/well assembly 300/200 mm
746Length of assembly pipe
747Dia of housing pipe
748Length of housing pipe
749OPERATING CONDITIONS
750i) Type of current A.C Three phases.
751ii) Frequency 50 Cycles/ Sec.
752iii) Rated Voltage 415+/-10% Volts
753iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
754v) Speed of Revolution __________________ RPM 2900
755MOTOR
756i) Ref to BIS codeBIS 9283-1979 with upto date amendments
757ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
758iii) Mechnical out put in HP
759iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
760PUMP
761i) Ref to BIS codeBIS 5659-1978 with upto date amendments
762ii) Driver Type Electric drivern
763iii) Operating Range -25%to +10% of Total head at duty point
764iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
765Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :32 amp.
766Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
767MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range32 amp. iv) Capacity
768ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
769The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range 0-500V
770A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500V.
771AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 30 Amp.
772Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
773Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 3 KVAR
774Providing suitable Direct onlineStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Direct online iii) Range.
775Single Phase Preventor i) Make : ii) Type : Direct online iii) Range.
776Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
777Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 80 mm dia.
778Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :
779Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 2.5 x 2.5 mm2 copperiii). type- IV capacity V Core-4mm2 (2.5/2.5 mm 2 Copper ).
780Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M)Existing safe
781Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
782Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x2.50 mm2 ii) Make iii)Type iv) Capacity v)Core 3
783(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
784Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 8SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
785Centrifugal Pump Set for Babehar Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
786Discahrge (Q) := 3.99LPS
787Total Head (H) =177.03 mts.
788(a) SWL in sump well (h) :99.20 Mtrs
789(b) Shaft level :99.20mtrs.
790(c ) Level at discahrge point : 211.20 mtrs.
791(d) Suction lift :, +tive
792(e) Residual head :3 Mtrs
793(f) Static head :112.00 Mtrs
794(i) Rising Main :
795(a) Length3480 Mtrs
796(b) Dia. :80 mm
797(iv) Pumping Hours : 8 Hours
798(v) Altitude of installation above MSL : 99.20mtrs
799(vi) Characteristics of water :
800(a) Temperature :20.00Deg. C
801(b) Ambient temperature42.00Deg. C
802(c ) Turbidity < than 50.00NTU
803(d) Alkalinity Mg/Ca Co3
804(e) Size of the solidsmm
805(f) Other
806Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
807Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
808M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 63 Amp
809(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B. 63 Amp(i) Make(ii) Type(iii) Range ; suitable rating
810100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
811Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
812Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
813Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
814ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
815Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
816100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 60 Amp
817Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 5 KVAR
818Providing suitable Oil immersed star delta of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
819Single Phase Preventor. (i) Type.Oil Emmersible (ii) Make. Star dalta
820Providing Cast steelflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe80 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
821Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
822Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
823Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
824Providing 65 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
825Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
826Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
827i) Suction Pipe 80mm dia.
828ii)Delivery Pipe 65 mm dia.
829iii) Common Header 80 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 80 mm dia to be joined.
830Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2)ii) Make iii)Type iv) Capacity v)Core 3
831(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x10.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
832Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 8 SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
833Submersible Pump Sets for WSS Ganu Mandwara Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 25% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
834Discharge, (Q)4.77 LPS
835Total Head ( H ) 67.64 Mts.
836SWL in Tubewell39.17 mtr. bgl.
837R.L. point of discharge 103 mtr
838R.L. of Pump House =
839Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
840Drawdown in Tubewell 28.83 mtrs.
841StaticHead = 63.83mtrs.
842Static suction lift3mtrs.
843Rising main Column pipe
844Length 10 mtrs Length70.83 mtr
845Dia 100 mm (M) Dia 125 mm (M)
846Class GMS
847iv) Pumping hours8 hours
848v) Alititude of installations above M.S.L 100mtr
849vi) Characteristic of water
850(vii) Temperature :20.00Deg. C
851(viii) Ambient temperature42.00Deg. C
852(ix) Turbidity < than 50.00NTU
853(x) Alkalinity Mg/Ca Co3
854(xi) Size of the solidsmm
855xii) others
856xiii) Depth of T/well mtr
857ix) Dia of T/well assembly 300/200 mm
858Length of assembly pipe
859Dia of housing pipe
860Length of housing pipe
861OPERATING CONDITIONS
862i) Type of current A.C Three phases.
863ii) Frequency 50 Cycles/ Sec.
864iii) Rated Voltage 415+/-10% Volts
865iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
866v) Speed of Revolution __________________ RPM 2900
867MOTOR
868i) Ref to BIS codeBIS 9283-1979 with upto date amendments
869ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
870iii) Mechnical out put in HP
871iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
872PUMP
873i) Ref to BIS codeBIS 5659-1978 with upto date amendments
874ii) Driver Type Electric drivern
875iii) Operating Range -25%to +10% of Total head at duty point
876iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
877Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :32 amp.
878Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
879MCCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range32 amp. iv) Capacity
880ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
881The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range
882A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
883AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 30 Amp.
884Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
885Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 3 KVAR
886Providing suitable Air Break TypeStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltae iii) Range.
887Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
888Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
889Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 100mm dia.
890Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :
891Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-6mm2 (4/2.5 mm 2 Copper ).
892Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M)Existing safe
893Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
894Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2 ii) Make iii)Type iv) Capacity v)Core 3
895(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
896Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 6SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
897Centrifugal Pump Set for WSSGanu Mandwara Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
898Discahrge (Q) := 4.77 LPS
899Total Head (H) =216.52 mts.
900(a) SWL in sump well (h) : 100 Mtrs
901(b) Shaft level :100mtrs.
902(c ) Level at discahrge point : 224.26 mtrs.
903(d) Suction lift :, +tive
904(e) Residual head :3 Mtrs
905(f) Static head :124.26 Mtrs
906(i) Rising Main :
907(a) Length3600 Mtrs
908(b) Dia. :80 mm
909(iv) Pumping Hours : 8 Hours
910(v) Altitude of installation above MSL :100 mtrs
911(vi) Characteristics of water :
912(a) Temperature :20.00Deg. C
913(b) Ambient temperature42.00Deg. C
914(c ) Turbidity < than 50.00NTU
915(d) Alkalinity Mg/Ca Co3
916(e) Size of the solidsmm
917(f) Other
918Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
919Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
920M.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 63 Amp
921(ii) E.L.C.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L.C.B. 63 Amp(i) Make(ii) Type (iii) Range ; suitable rating
922100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
923Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
924Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
925Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
926ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ;63 Amp
927Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
928100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 30 Amp
929Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 7 KVAR
930Providing suitable Oil immersedStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Oil immersed star delta (ii) Make.
931Single Phase Preventor. (i) Type.Oil Emmersible (ii) Make. Star dalta
932Providing Cast steelflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe80 mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
933Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
934Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 65 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
935Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 80 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
936Providing 65 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
937Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
938Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
939i) Suction Pipe 80mm dia.
940ii)Delivery Pipe 65 mm dia.
941iii) Common Header 80 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 80 mm dia to be joined.
942Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x10.00 mm2)ii) Make iii)Type iv) Capacity v)Core 3
943(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x16.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
944Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 6SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
945Submersible Pump Sets for WSS Raipur Marwari Supply and errection of submersible pumping set of reputed make such as KSB/Calama/BS /Oswal / worthigton/ LUBI/ GROUNDFOS/HINDUSTAN/ SEERAX/SABAR/Johnston/Amrut conforming to latest relevent BIS . The pump should be fitted with free fine impellers of suitable alloys as per BIS ;5659-1978 with upto date amendments, suitable for raw /clear water having greased packed bearing and shell with wound stator on motor side and with shaft protection on pump side ensuring better life for shaft conforming to BIS specifications The pump shall be directly coupled to submersible squirrel cage electric induction motor of same make conforming to BIS ;9283-1979with upto date amendments, totally dust and water proof for submersible pump, duly isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed,lubricated bearing andprovidedwith stainless steel thrust bearing plate to withstand non vertical loads with minimum wear and tear.It should also be fitted with a device to make up expa-of water with heating of motor The pumpset should include water level guard i/c cable ,errection clamps, cable clips and suitable for opertion on data given below. Specifications offered a Pumps :- Specifications i) Makeii) Modeliii)No. of stages iv) Manufacter\"s certificate to be attached Performancei) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speedv) Insulation
946Discharge, (Q) 10.70 LPS
947Total Head ( H ) 57.42 Mts.
948SWL in Tubewell30.49 mtr. bgl.
949R.L. point of discharge 503 mtr
950R.L. of Pump House = 500 mtrs
951Seasonal fluctuation + draught condition + bowl assembly.9 mtrs.
952Drawdown in Tubewell 10.67 mtrs.
953StaticHead = 53.16mtrs.
954Static suction lift3mtrs.
955Rising main Column pipe
956Length 15 mtrs Length 60.16 mtr
957Dia 125 mm (M) Dia 125 mm (M)
958Class GMS
959iv) Pumping hours8 hours
960v) Alititude of installations above M.S.L 100 mtr
961vi) Characteristic of water
962(vii) Temperature :20.00Deg. C
963(viii) Ambient temperature42.00Deg. C
964(ix) Turbidity < than 50.00NTU
965(x) Alkalinity Mg/Ca Co3
966(xi) Size of the solidsmm
967xii) others
968xiii) Depth of T/well mtr
969ix) Dia of T/well assembly 300/200 mm
970Length of assembly pipe
971Dia of housing pipe
972Length of housing pipe
973OPERATING CONDITIONS
974i) Type of current A.C Three phases.
975ii) Frequency 50 Cycles/ Sec.
976iii) Rated Voltage 415+/-10% Volts
977iv) System of earthing Double Loop earthing as per BIS 3843-1987 latest
978v) Speed of Revolution __________________ RPM 2900
979MOTOR
980i) Ref to BIS codeBIS 9283-1979 with upto date amendments
981ii) Type of enclousre of motr As per BIS :4691-1985 (latest)
982iii) Mechnical out put in HP
983iv) Class of insulation: Class BThe motor should be able to withstand intial current of2.50 times the rated current for two minutes without suffering damages of permanet deformations
984PUMP
985i) Ref to BIS codeBIS 5659-1978 with upto date amendments
986ii) Driver Type Electric drivern
987iii) Operating Range -25%to +10% of Total head at duty point
988iv) Deliver size of Pump ;---------- (to be quoted by tenderer)
989Providing ICTP Main Switch with HRC fuses ofL&T/ Havells make and having capacity 30% extra of the operational rating as per IS : 13947- P I & II with upto date amendments.i) Make :ii) Type : iii) Capacity :63 amp.
990Providing MS Sheet steel fabricated floor mounted closed ( Almirah type) switchboard including angle iron post of suitable height and size ISA 40x40x6 mm duly painted with sheet of 16 gauge comprising and capable of mounting the following accessories with all internal connections.Panel/ Switch Board i) Drawing.ii) Layout Plan
991MCB of kilburn / L&T/ Havells make of suitable capacity on incoming feeder withor withoutinitial oil filling asthe case may be with neutral linked under voltage releases as per IS ; 2516-1985 with upto date amendments.i) Make : ii) Type : iii) Range63 amp. iv) Capacity
992ELCB of recommended makeL&T /Havellsas per IS ; 2516-1985 with up to date ammendments and of suitable range which should have control box , operating handle & trip / reset bush button on / off of indicators, reindicating off springcondition of the circuit breaker for over current protection. The circuit should be equiped with magnet thermal releasewith metallic tape CTS. It shouldalso be fitted with earth faultfor tripping of breakeron occurence of Earth fault. ELCB i) Make : ii) Type : iii) Range 63Amp. iv)Capacity
993The voltage monitor Relay 3 phase with all protection and usual indicator and electric siren against single phasing, low voltage, high voltage, reverse phasing, overloading and phase voltage difference as per IS; 3842 ( Latest Edition )i) Make : ii) Type : iii) Range
994A.C. supply, voltmeter of recommended makeA.E./ L&T /Havells of suitable range withselector switches as per IS ;1248-1983 with latest amendments. Voltmeter i) Make : ii) Type : iii) Range 0-500.
995AC supply ammeter ofA.E / L&T/ Havellsmake of suitable range with selector switches and CIS operated as per IS :1248 ( P-I&II ) -1983 with upto date amendments.Ammeter i) Make : ii) Type : iii) Capacity 60 Amp.
996Bus bar chamber having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating offull length for neutral phase as per IS ; 8084-1976 and IS : 11353-1985 read with BIS ; 5578 -1985 with upto date amendments including.Three phase indicator lamps complete with toggle switches for individual motors as per IS 3452(P- I&II ) with upto date amendments. 3 Phase indicators3 phase indicators i) Make : ii) Type : iii) Rating
997Capacitor ofBHEL /L&T make as per IS ; 2834-1968 with upto date amendments, to raise the power factor at site to 0.95 for directconnections to induction motor individually of required KVA rating according to H.P. offered including cables as per relevent ISI code ( of Seimens / Glocter/ IEC make) from bus bar chamber to capacitor as per IS : 4064-1978 with upto date amendments .Rate of capacitor will be approved by HPSEB.i) Make : ii) Type : iii) Range. 4 KVAR
998Providing suitable Air Break TypeStar delta starter ofL&T/Havell\"s /MEI/BHEL/Kilburn make as per IS: 13947-IIwith up to date amendments for Squirrel Cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Single Phase Preventor i) Make : ii) Type : Air Breaker typeiii) Range.
999Single Phase Preventor i) Make : ii) Type : Air Break Type Star Deltaiii) Range.
1000Providingand fixing double flanged Cast iron Sluice valve ofLeader /Kirloskar /LP/RG Brandmakefor the delivery lineof pump and capable of withstandingthe normal seat pressure and as perIS :- 780-1992with latest ammendmentsi) Make : ii) Type : iii) Make :- Cast Iron Class PN-1.00 for Column Pipe 125 mm dia
1001Providing and fixing double flanged swing type cast IronReflux valve of Leader/ Kirloskar/Kartar / LP/RG Brandmake having Bye pass arrangement on the delivery line of the Pump and capable of \"withstanding normal Seat Pressure as per IS:15312 Part-1 with latest ammendmentsi) Make : ii) Material : Cast Ironiii)ClassPN-1.00For for R/main 125 mm dia.
1002Providingand fixing pressuregauge ofPrega / Precisionmake completewith all accessories such as stop cock, copper tubing as per IS ; 3624-1987 with upto date amendements.i) Make :0-52 Kg/cm2
1003Supply of PVC Jointless , Flat water proof cables as per BIS 694-1998 Latest with upto date amendments , Suaitable for the pump set offered from OCB to Motor Including all otherelectrical equipments / accessories such as thimble , flexible pipe solder , nuts and bolts , cable glands etc . laid in pipes or trenches under floor .The tpye size and make shall be subject to approved of HPSEB authorities .i) Make :Finolex/ Havells ii) Size 4 x 2.5 mm2 copperiii). type- IV capacity V Core-6mm2 (4/2.5 mm 2 Copper ).
1004Lowering of GMS Column pipefor assembly 125 mm dia including MSflanges\" of Table17 as per IS : 6392-1971 with upto date amendments, rubber/asbestos gasket of min. 3mm thickness as per IS 2712-1979 and required numbers of nuts and bolts as per IS ;1364-1983 . The Column pipe shall be as per relevent IS Code and to withstand 1.50 times total head stipulated underitem No. 70 . The Column pipe should be extended upto 5 mtr. beyond the outer wall of the pump house in the direction ofRising main . The Column pipe should be properly jointed with the Rising main including all necessary accessories like increaser / reducer, flanges, bends etc, including supporting clamps (2Nos.) at the top ofT/well assembly, and as per the direction of Engineer - in - Charge. (The pipe shall be supplied by the Department free of cost from Divisional Store Badoh(Gagret). Column Pipe 125 mm dia GMS pipe (M)Existing safe
1005Installation of allitemsappearing as above as per the systematic drawing attached with the documents or as per the direction of Engineer - in- charge.
1006Providing and laying copper PVC insulated armoured power cable (one cable carrying all the three phases) of suitablle size and capacity to motors and all other electrical equipments as per IS ;1554(P-I ) 1988 or latest with upto date amendments of Seimen /Gloster / IEC / ICC / EICO / National / Grandlay /Finolex/ Havells makeincludingallother accessories such as thimble, flexible pipes, solder nuts and bolts, cable glands etc. laid in pipes of trenches under floor. Armoured Power Cable A)Supply Side From meter of HPSEB toBus Bar and Switch)Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2 ii) Make iii)Type iv) Capacity v)Core 3
1007(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
1008Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 6SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP
1009Centrifugal Pump Set for WSS RaipurMarwari Providing horizontal spindle ,horizontal / radial split casing / end suction (back full out arrangement). Single / double / multi stage of Mather and Platt /KSB/Beacon weir/Kirloskar / BE/Jyotias per BIS IS 1520- 1980 with upto date ammendments read with IS-9137.1978 or latest edition suitable for lifting clear water forundermentioned characteristic with Bronze impellers / priming funnels, casing ring and shaft sleeves of Bronze shaft of stainless steel with cast iron casing, coupled directly through a flexible coupling on a common cast iron/cast steel base plate (base plate to be framed from the manufacturers of the pumping unit only) to slipring/Squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/NGEF /ABB/GEC( Marathon)/BHEL/Jyotiand suitable for operation on 11 KV HT 400 (+/-15%) volts. 50 Cycles/Sec., 3 phase AC electric supply of 2900 RPM. The power of electric motor/motors shouldbe at least + 10% in excess of the maximum power required by the pump/pumps in the Operation range of (+10%) and (-15%) of the duty point head. The motor should beas per IS 325 IS 1978 with upto date amendments read with IS 900 - 1972 it should include cost of Bearing. Nuts, Bolts and painting etc. and should meet the following requirements.Specification i) Make ii) Model iii) No of Stagesiv) manufacters certficate to be attached Performance (i) Dischargeii) Head iii) Efficiency of Pump a) Duty Headb) (+) 10% Duty Head.c) (-) 15% Duty Headd)Performance curve to be attachedb) Motors; Specification i) Make ii) Model iii) B.H.P iv) Speed (v) Insulation
1010Discahrge (Q) := 10.70 LPS
1011Total Head (H) =257.83 mts.
1012(a) SWL in sump well (h) : 500 Mtrs
1013(b) Shaft level :500mtrs.
1014(c ) Level at discahrge point : 648.96 mtrs.
1015(d) Suction lift :, +tive
1016(e) Residual head :3 Mtrs
1017(f) Static head :148.96 Mtrs
1018(i) Rising Main :
1019(a) Length8440 Mtrs
1020(b) Dia. :125 mm
1021(iv) Pumping Hours : 8 Hours
1022(v) Altitude of installation above MSL :100 mtrs
1023(vi) Characteristics of water :
1024(a) Temperature :20.00Deg. C
1025(b) Ambient temperature42.00Deg. C
1026(c ) Turbidity < than 50.00NTU
1027(d) Alkalinity Mg/Ca Co3
1028(e) Size of the solidsmm
1029(f) Other
1030Providing ICTP Main Switch with HRC fuses of L&T/Crompton/Standard/Havells makeand having 30% extra of the operational rating as per IS: 1 3947-PI&II0 with up to date amendments. ICTP Switches :- (i) Make (ii) Model(iii) Capacity ;200 Amp
1031Providingof MS.sheetfabricated floor mounting closed (Almirah type) switch board angle Iron Post of Suitable height and size iSa 40x40x6 mm Duty pointed with sheet of 16 gauge comprising and capable of mounting the following accessoriespanel /Switch Board i) Drawingii) layout plan
1032O.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be withneutral linkedunder voltage releases as per IS: 2516-1985 with up to date amendments with.M.C.B. (i) Make. (ii) Type (iii) Range:Suitable Capacity. 200 Amp
1033(ii) E.L.B. of recommendedMAKE Havell/MDS/INDETEC make as per IS: 2516-1977 with upto date amendmentwhich should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape CTS. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.E.L..B.200 Amp (i) Make(ii) Type(iii) Range ; suitable rating
1034100mm square type A.C. supply voltmeter A.C. supply voltmeter of AE/L&Tmake of suitable range with selector switches as per IS: 1248-1983 with up to date amendments. Voltmeter. (i) Type.(ii) Make (iii) Range 0-500 V
1035Providing Power Factor meter as per Standed make as per revalentIS codewith up to date amendments. Power factor meter.(i) Make. (ii) Range 0-500 V
1036Providing Fecquencymeter Standed make as per revalentIS codewith up to date amendments. Fecquencymeter (i) Type.
1037Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments . THREE PHASE INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentBus Bar chamber. (i) Type (ii) Make. (iii) Rating : Suitable rating 3 Phase Indicators
1038ICTPSwitch with HRC fuses of L&T/Crompton/Standard/Havells make and Suaitable Capacityas per IS 4066-1973 with up to date amendments. INDICATOR lAMPS COMPLETE WITH TOGGLE SWITCHS FOR INDIVUAL MOTORS AS PER is 3452(PI&II)with uo to date ammendmentICTP Switches :- (i) Make (ii) Model(iii) Capacity ;200 Amp
1039Three phase INDICATOR:- (i) Type(ii)Make(iii) Capacity ;
1040100 mm diametres AC supplyAmmeter of IMP /L&T Havells make of suitable range with selector switches and CTS operated as per IS:1248 (P-II) 1983 with up to date amendments. Ammeter.(i) Type (ii) Make. (iii) Range. 200/5 Amp
1041Capacitor of Mecheil /Bhel /GEC/L&Tmake as per IS:2834-1986 with up to date amendments toraise the power factor at site to 0.95 for direct connections to induction motor individuallyof required KVAR ratingaccordingto HP offered including cables as per relevant ISI code ( of Siemens/Glocter/IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate rangeas per IS: 4064-1978 withupto date amendmentsCapacitor: (i) Type (ii) Make(iii) Range : 16 KVAR
1042Providing suitable AutoStar delta starter of IMP /Bhel /Havell\"s/L&T make as per IS: 13947 with up to date amendments for Squirrel Cage motor mounted on panel board withSheet Steel enclosures , under voltage release with single phase preventor as per IS 1248 (P-V)-1983 with up to date amendments. Starter: (i) Type.Auto Transformer (ii) Make.
1043Single Phase Preventor. (i) Type.Auto Transformer(ii) Make.
1044Providing Cast steelflanged /Screwsluice valve ofwith stainer as per IS 188-1999 with up to date amendments Leader/Kirloskar/Kart ar/ Bhel /Glad /Kartarmake for Suction Pipe125mm diaSluice valve. (i) Make. (ii) Class ASA 150(iii) Seat PressureKg/cm2 (iv) Material.
1045Providing doubleflanged Cast Steel sluice valve of of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 100 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –1414Api -600with up to date amendmentsFor Delivery Pipe of Pump(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
1046Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 100 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments. Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
1047Providing double flanged (Swing type)Cast steel reflux valve of Leader/Kirloskar/Kartar/ Bhel /Glad /Kartar make and 125 mm dia. on the delivery line of pump and capable of with standing normal seat pressure as per IS –5312-1992with up to date amendments Reflux valve valve.(i) Make. (ii) Class ASA 150(iii) Seat PressureMPA(iv) Material.
1048Providing 100 mm dia. circular dial pressure gauge of Prega /Precision /Fiebig /Bourden make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-52 Kg/cm2 (Pressure gauge) (i) Make. (ii) Range :
1049Installation of all items appearing at as aboveas per the systematic drawing attached with the tender documents or as perthe direction of Engineer-in Charge.The contarctor should ensure proper jointing of delivery pipe line ofpump with the Rising main including all necessary accessories likeincreaser /reducer specials etc. as per site conditions and complete in all respects with in all leads and lifts as per direction of Engineer-in-charge
1050Fixing of double flanged GMS pipingwork(layout to be approved by Engineer-in-Charge) for suction and delivery pipes suitable to pumps offeredand common header as per the risingmain respectively complete with all specials such as bends,Tees,Reducers Inceasers with companion flanges matching with the relevant specifications of the accessories as indicated in the Drawing i/c rubber/ asbestos gasket of 3 mm thickness as per IS : 2712-1979 and required number of Nuts and Bolts as per 1364-1983.-the pipes shall be as per relevent IS code and to withstand 1.5 times total head. (The pipe shall be issued free of cost at divisional store. However MS flanges will be provided by the firm)
1051i) Suction Pipe 125 mm dia.
1052ii)Delivery Pipe 100 mm dia.
1053iii) Common Header 125 mm dia. and will extend upto 5 metres from the outer wall of the pump house in the direction of Rising main of 125 mm dia to be joined.
1054Providing and laying 3 core copper PVC Insulated armoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other elelctrical equipments as per IS: 1554(P-I)1988 or latest with upto date amendments of Seimen/Gloster/IEC/ICC/EICO/ National /Grandlay make including all other accessories such as thimble, flelxible pipes, solder, nuts & bolts, cable glands etc. laid in pipes or trenches under floor. Armoured Power Cable(A) Motor side(From Switch to Starter & Starter to motor) i) Size2x4.00 mm2)ii) Make iii)Type iv) Capacity v)Core 3
1055(B) Supply Side(From meter of HPSEB to Bus Bar & Switch) i) Size 2x4.00 mm2 ii) Make iii) Type iv) Capacity v) Core 3
1056Providingand fixing double loop earthingwith Cooper and Suitablethick electrodecomplete with material such as thimble, nuts and bolts, charcoal, salt,25 mm x5 mm as per IS ; 3043-1987 with upto date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect as per the dirction of the Engineer - in - Charge. i) i) G.I Wire 8 SWG upto 15 HP ii) G.I Flat 25x3 mm 15 to 50 HP iii) G.I Flat 32x6 mm Above50 HP

AI Tender Summary

OUR REF NO 38848364
AUTHORITY Government Departments
TENDER VALUE 89.90 Lakhs
LAST DATE 07-08-2023
Authority
Authority Name Irrigation And Public Health Department
Work Description Improvement Of Various Water Supply Scheme By Source Strengthening, Replacement Of Old Pumping Machinery, Restoration / Construction Of Old Pump House And Allied Structure In Gagret Constituency In Distt Una ( Hp ) Daulatpur Sub Division Pumping Machinery ( Sh;- S / E Of Pumping Machinery With Allied Accessories For T / Well At Amlehar Bhanjal, T / Well At Nakroh, T / Well At Gondpur Banehra, T / Well At Bhaderkali, T / Well At Dangoh, T / Well At Joh, T / Well At Abhaypur, T / Well At Babehar, T / Well Ganu Mandwara, T / Well At Raipur Marwari Etc
Basic Detail
Tender No GGT-UNA01-752 No 3304-44 dt 26.07.2023
Bidding Type Tender
Location
City gagret
State Himachal Pradesh
Key Dates
Publish Date 26 Jul 2023
Submission Date 07 Aug 2023
Open Date 07 Aug 2023
Finance
Tender Value 89.90 Lakhs
Tender Fee 800
EMD 1.22 Lakhs
Exemption Not Available
Document List
9e4d614f-a659-4e3b-b4c5-892eb7435c21.html
BOQ_114670.xls
Form6and8-Imp-Daulatpur.pdf
Tendernotice_1.pdf
Term-and-Condations-Imp-D.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jul 26, 2023
11:30 IST

Tender Published

Tender notice published.

Completed
Aug 07, 2023
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Aug 07, 2023

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
html

9e4d614f-a659-4e3b-b4c5-892eb7435c21.html

xls

BOQ_114670.xls

pdf

Form6and8-Imp-Daulatpur.pdf

pdf

Tendernotice_1.pdf

pdf

Term-and-Condations-Imp-D.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders