| 1 | SH-I:- (EI, Fittings, LT panels, DB’s & AC work)Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. a) Group C |
| 2 | Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.a) Group C |
| 3 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit/channel as required. a) 3 x 1.5 sq. mm |
| 4 | b) 3 x 4 sq. mm |
| 5 | c) 6 x 4 sq. mm |
| 6 | d) 9 x 4 sq. mm |
| 7 | e) 3 x 6 sq. mm |
| 8 | f) 6 x 6 sq. mm |
| 9 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. a) 20 mm |
| 10 | b) 25 mm |
| 11 | c) 32 mm |
| 12 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlet and 2 Nos. 5/ 6 A modular switch, connections etc. as required. |
| 13 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
| 14 | Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. |
| 15 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.a) 6 Module |
| 16 | b) 3 Module |
| 17 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 15/16 A switch |
| 18 | b) 6 pin 15/16 A socket outlet |
| 19 | c) 5/6 A switch |
| 20 | d) 3 pin 5/6 A socket outlet |
| 21 | Dismantelling of existing hylem sheet of different sizes from bus bar boxes/GI boxes i/c supplying & fixing6 mm thick phenolic laminated sheet of different size as per bus bar box size complete with making holes for fastners & cutting of sheet as per modular sitches-sockets/sheet i/c providing & fixing suitable fastners for fixation of sheet as per Direction of Engineer in chargei/c repairing the damage if any etc. as required at site. |
| 22 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) a) 12 way (4 + 36), Double door |
| 23 | b) 8 way (4 + 24), Double door |
| 24 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)a) 4 way (4 + 12), Double door |
| 25 | b) 6 way (4 + 18), Double door |
| 26 | Supplying and fixing Cable End Box (Loose wire box)(IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required.a) For 4 / 6 way, Double door TPN MCBDB |
| 27 | b)For 8 /12 way, Double door TPN MCBDB |
| 28 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.a) Single pole |
| 29 | Supplying, Laying and fixing of one number PVC insulated and PVC sheathed / XLPE Alarmoured power cable of 1.1 KV grade of following size on wall surface/recess as required. a) size 3 X 10 sq. mm |
| 30 | b) size 4 X 25 sq. mm |
| 31 | c) size 3½ X 95 sq. mm |
| 32 | d) size 3½ X 120 sq. mm |
| 33 | e) size 3½ X 150 sq. mm |
| 34 | f) size 3½ X 185 sq. mm |
| 35 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade of followingsize direct in existing GI /HDPE pipe / PVC channel / trench / cable tray complete with making connection etc as required. a) size 4 X 25 sq. mm |
| 36 | b) size 3½ X 120 sq. mm |
| 37 | c) size 3½ X 150 sq. mm |
| 38 | d) size 3½ X 185 sq. mm |
| 39 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.a) 90 mm dia (OD-90 mm & ID-76 mm nominal) |
| 40 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. a) 4 X 25 sq. mm (28mm) |
| 41 | b) 3½ X 95 sq. mm (45 mm) |
| 42 | c) 3½ X 120 sq. mm (45 mm) |
| 43 | d) 3½ X 150 sq. mm (50 mm) |
| 44 | e) 3½ X 185 sq. mm (57mm) |
| 45 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required. |
| 46 | Earthing with G.I earth pipe 4.5 mtr long x 40mm dia i/c accessories and providing masonary enclosure with cover plate, having locking arrangement with salt & charcoal etc. as reqd. |
| 47 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. |
| 48 | Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 49 | Providing and fixing of PVC Trunking of following sizes complete with flexible cover, joint, endcap, cover, partition clip wherever reqd. on surface of wall/existing mounting etc. as required. a) 105 mm x 50 mm |
| 50 | b) 32 mm x 20 mm |
| 51 | SITC of wall fan 400 mm sweep oscillating type having plastic blade complete with all accessories such as front jaali i/c connection etc. as reqd. |
| 52 | Supplying, Installation, testing and commissioning of recess/surface mounted type Luminaries, glare free opal diffuser LED Panel of Nominal size 595 x 595 mm suitable for Armstrong / POP / GB ceiling with made out of CRC / MS Powder coated housing. Having the following specifications:i) Total System Lumens - 34 to 36 Watt,ii) Color Temprature - 5700 K to 6500 K,iii) Power Factor - > 0.95iv) CRI - > 80,v) System Lumen Efficency - >100 LM/W,including connections, testing etc complete as required. |
| 53 | S/I/T/Cof 1200 mm sweep BEE star rating energy efficient ISI marked ceiling fan capacitor type with double ball bearing suitable for operation of single phase AC supply with power Consumption of Max.50W capable to deliver220 CFM (min.),speed of 350 rpm (min.)i/c wiring the down rod of standard length (upto 30 cm) with 1.5 Sqmm FR PVC insulated copper conductor single core cable etc as reqd. |
| 54 | SITC of 1.5 TR inverter window type Air conditioner unit fitted with rotary compressor duly filled with R-32 or better refeigerant gas (eco-friendly) having BEE 3 Star Rating, with minimum 4900 watt nominal cooling capacity with cordless remote suitable for operation on 230 volts, single phase AC supply in the exisiting window including dismantling of existing air conditioner & fixing AC with suitable sizewooden frame as per size of the AC, smooth fine & paint with two or more coats of super enamel paint matching of room interior & remaining space will covered with 2/4 mm thick wooden ply and sealing the fap etc. complete as required. at site. |
| 55 | Supplying & Fixing of 4 KVA capacity automatic voltage stablizer with time delay relay and high/low voltage trip facility having voltage range 150 V to 290 V +10% with copper flexible cable connection etc. as required at site. |
| 56 | Supplying and fixing of 25 mm dia. size medium class PVC conduit/pipe along with accessories in surface/recess including cutting the wall and making good the same in case of recessed pipe for AC drain as required at site. |
| 57 | Supplying and Fixing of refrigerant copper pipes of following sizes along with 1/2\" Nylon Insulation tube complete with 3 core 2.5 sq.mm copper cable, clipping on wall surface i/c testing and commissioning etc. as reqd. a) 1/4\" & 1/2\" |
| 58 | b) 3/8\" & 5/8\" |
| 59 | Fabrication, supplying, installation, testing & Commissioning of Indoor type cubical type double door feeder pillar panel of upto 300/450 mm depth made out of 2mm thick(14 SWG) CRCA MS Sheet having detachable gland Plates, floor mounted, compartmentalized , front operation, dust & vermin proof duly powder coated with proper locking arrangement complete with 300/500 Amp. TPN high conductivity aluminum alloy bus barwith DMC/SMC supports, continuous earth bar, interconnections, connections and providing & fixing of angle iron stand made out of 50mm X 50mm X 6mm thick M.S. Angle iron to suit the size of feeder pillar with 4 nos. 50 cms. legs grouted in cement concrete duly painted with one coat of red oxide & two coats of superior quality enamel paint etc. as reqd at site. (To be fabricated from CPRI approved fabricator.) |
| 60 | Providing and fixing following rating and breaking capacity and pole MCCB/TPN/SPN MCB with thermomagnetic release and terminal spreaders & associated switchgears in the above cubical panel board/TPDB including drilling holes in cubicle panel, fitting strips for MCB ,making connections, etc. as required.a) 400 A, 50kA, FPMCCB with thermal release & terminal spreaders |
| 61 | b) 250 A, 36 kA, FPMCCB with thermal release & terminalspreaders |
| 62 | c) 200 A, 36kA, FPMCCB with thermal release & terminalspreaders |
| 63 | d) 125 A, 16 kA, TPMCCB with thermal release |
| 64 | e) 100 A, 16 kA, TPMCCB with thermal release |
| 65 | f) 63 A, 10 KA , TPN MCB (C-Curve) |
| 66 | g) 63 A, 10 KA , SPN MCB (C-Curve) |
| 67 | h) Digital type voltmeter with seperate selector switch of class 0.5 |
| 68 | i) Digital type Ammeter with seperate selector switch and CT\"s of class accuracy 0.5 |
| 69 | j) Phase indication lamp 0-240 V A.C. |
| 70 | Providing and fixing of 2 mm thick duly powder coatedand phosphated sheet steel enclosure for installation of upto 400A MCCB i/c connection, testing etc as required. |
| 71 | Credit for following old/dismantle material received from above work i/c dismantling & removal from site.a)Assorted Panel With Switchgears |
| 72 | b) Assorted M.S. Boxes/Scrap |
| 73 | c) Assorted P/T Switch/Sockets |
| 74 | d) Assorted Ceiling fan |
| 75 | e) Assorted Wall fan |
| 76 | f) Assorted Tube fitting /Down lighter fittings |
| 77 | g) Assorted PVC Insulated Copper Conductor Wire (1.5/4.0/6.0 Sq. mm) |
| 78 | h) Assorted 2X2 Light Fitting Panel |
| 79 | i) Assorted Conduit/Wiremesh/Angle Iron/M.S. Scrap |
| 80 | j) Assorted Window/Split Type Air Conditioner Unit |
| 81 | k) Assorted PVC Insulated Armoured Power Cable |