Tender For Provision Of Electrical Works In Nurse Hostel At Sanjay Gandhi Memorial Hospital Mangolpuri Delhi 110083, mangolpuri-Delhi

Public Works Department-PWD has published Tender For Provision Of Electrical Works In Nurse Hostel At Sanjay Gandhi Memorial Hospital Mangolpuri Delhi 110083. Submission Date for this Tender is 28-07-2023. Electrical Maintenance Tenders in mangolpuri Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

38748720
Tender For Provision Of Electrical Works In Nurse Hostel At Sanjay Gandhi Memorial Hospital Mangolpuri Delhi 110083
Open Tender
Indian
Delhi
mangolpuri
28-07-2023

Tender Details

Tender For Provision Of Electrical Works In Nurse Hostel At Sanjay Gandhi Memorial Hospital Mangolpuri Delhi 110083- 1 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Steel Conduit, With Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable Etc. As Required. 2 Group A 3 Supplying And Fixing Of Following Sizes Of Steel Conduit Along With Accessories In Surface / Recess Including Painting In Case Of Surface Conduit, Or Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required. 4 25 Mm 5 32 Mm 6 Supplying And Drawing Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required. 7 3 X 1.5 Sq. Mm 8 6 X 1.5 Sq. Mm 9 3 X 4 Sq. Mm 10 6 X 4 Sq. Mm 11 3 X 6 Sq. Mm 12 6 X 6 Sq. Mm 13 Wiring For Circuit / Submain Wiring Alongwith Earth Wire With The Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Steel Conduit As Required. 14 2 X 16 Sq. Mm + 1 X 6 Sq. Mm Earth Wire 15 4 X 10 Sq. Mm + 2 X 6 Sq. Mm Earth Wire 16 Fabrication, Supplying And Installation Of Outdoor Type Cubical Feeder Pillar Of Suitable Size Upto 350 Mm Deep Made Out Of M.S. Sheet 1.6Mm. Thick ( 16 Swg ) Duly Compartmentalised Havingal. Busbar Of Minimum 300Amp Capacity Double Door With Locking Arrangement For Protection From Rain, Dust, Duly Fixed On M.S. Angle Iron Frame Work Of Size 50 Mm X 50 Mm X 6 Mm ( Ns ) 50 Cm Long Legs Grouted In Cement Concrete Mounted Inside The Cubical Panel I / C Connection, Inter Connection With Aluminum Thimbles, Earth Studs Duly Painted With One Coat Of Red Oxide & Two Coats Of Superior Quality Enamel Paint Complete Etc. As Reqd I / C Supplying And Fixing Following Accessories As Per Item I / C Control Wiring. 17 Providing And Fixing Following Rating And Breaking Capacity And Pole Mccb With Thermomagnetic Release And Terminal Spreaders In Existing Cubicle Panel Board Including Drilling Holes In Cubicle Panel, Making Connections, Etc. As Required. 18 250 A, 36Ka, Fpmccb 19 100 A, 30Ka, Fpmccb 20 Supplying And Fixing Following Rating, Four Pole, 415 V, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.I ) 100 A 21 Supplying And Fixing Following Rating, Double Pole, 240 V, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.I ) 63A 22 Supplying And Fixing Following Way, Single Pole And Neutral, Sheet Steel, Mcb Distribution Board, 240 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator ) A ) 12 Way , Double Door 23 Supplying And Fixing Following Way, Horizontal Type Three Pole And Neutral, Sheet Steel, Mcb Distribution Board, 415 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator ) ( A ) 8 Way ( 4 + 24 ) , Double Door 24 Supplying And Fixing 5 A To 32 A Rating, 240 / 415 V, 10 Ka, “C” Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.A ) Single Pole 25 Supplying And Fixing Suitable Size Gi Box With Modular Plate And Cover In Front On Surface Or In Recess, Including Providing And Fixing 3 Pin 5 / 6 A Modular Socket Outlet And 5 / 6 A Modular Switch, Connections Etc. As Required. 26 Supplying And Fixing Suitable Size Gi Box With Modular Plate And Cover In Front On Surface Or In Recess, Including Providing And Fixing 6 Pin 5 / 6 & 15 / 16 A Modular Socket Outlet And 15 / 16 A Modular Switch, Connections Etc. As Required. 27 Supplying And Fixing Call Bell / Buzzer Suitable For Single Phase, 230 V, Complete As Required. 28 Supply, Installation, Testing And Commissioning Of 1200 Mm Sweep, Bee 5 Star Rated, Ceiling Fan With Brush Less Direct Current ( Bldc ) Motor, Class Of Insulation: B, 3 Nos. Blades, 30 Cm Long Down Rod, 2 Nos. Canopies, Shackle Kit, Safety Rope, Copper Winding, Power Factor Not Less Than 0.9, Service Value ( Cmm / W ) Minimum 6.85, Air Delivery Minimum 215 Cmm, 350 Rpm ( Tolerance As Per Is : 374- 2019 ) , Thd Less Than 10%, Remote Or Electronic Regulator Unit For Speed Control And All Remaining Accessories Including Safety Pin, Nut Bolts, Washers, Temperature Rise=75 Degree C ( Max. ) , Insulation Resistance More Than 2 Mega Ohm, Suitable For 230 V, 50 Hz, Single Phase Ac Supply, Earthing Etc. Complete As Required. 29 Supplying, Installation, Testing And Commissioning Of Surface / Wall Mounted 18-20 Watt Led Tube With 4 Feet Batten Fitting, Led Tube Should Have Polycarbonate Housing For Efficient Heat Dissipation, In Cool Day Light ( 5700 K To 6500 K ) As Required I / C Connection With 1.5 Sq.Mm. Frls Pvc Insulated Copper Conductor, Single Core Cable Etc. As Reqd. 30 Supplying, Installation, Testing And Commissioning Of Wall Mounted Decorative Bracket Light Having Complete Fixture, 40 Watt Warm White Lamp And Opal White Glass Diffuser For Glare Free Light Etc. As Reqd. 31 Supplying, Installation, Testing And Commissioning Of 12W Round Full Glow Led Surface Downlight Having Polycarbonate Body And 2.5Kv Surge Protection Etc. As Reqd. 32 Supply, Installation, Testing& Commissioning Of 150 Mm Sweep Fresh Air Fan Having Minimum Speed Of 1350 Rpm, 260Cubic Meter Per Hour Air Flow, Maximum Power Consumption Of 30 Watt, In The Existing Opening Including Making Good The Damages, Connection Testing And Commissioning Etc. Complete As Required. 33 Supplying And Fixing Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc. As Required. 34 1 Or 2 Module ( 75Mmx75mm ) 35 6 Module ( 200Mmx75mm ) 36 Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required. 37 3 Pin 5 / 6 A Socket Outlet 38 5 / 6 A Switch 39 Telephone Socket Outlet 40 Tv Antenna Socket Outlet 41 Supplying & Fixing Suitable Size Gi Box Wih Modular Plate And Cover In Front On Surface Or In Recess Including Providing And Fixing 25 A Modular Socket Outlet And 25 A Modular Sp Mcb, C Curve Including Connections, Painting Etc. As Required. 42 Supplying, Laying And Fixing Of One Number Pvc Insulated And Pvc Sheathed / Xlpe Power Cable Of 1.1 Kv Grade Of Followingsize Aluminium Conductor Armoured Cable On Wall Surface As Required. 43 3.5 X 95 Sq. Mm 44 Supplying And Laying Of Following Size Dwc Hdpe Pipe Isi Marked Along With All Accessories Like Socket, Bend, Couplers Etc. Conforming To Is 14930, Part Ii Complete With Fitting And Cutting, Jointing Etc.Direct In Ground ( 75 Cm Below Ground Level ) Including Excavation And Refilling The Trench But Excluding Sand Cushioning And Protective Covering Etc., Complete As Required. 45 90 Mm Dia ( Od-90 Mm & Id-76 Mm Nominal ) 46 Earthing With G.I. Earth Pipe 4.5 Metre Long, 40 Mm Dia Including Accessories, And Providing Masonry Enclosure With Cover Plate Having Locking Arrangement And Watering Pipe Etc. With Charcoal / Coke And Salt As Required. 47 Supplying , Installation, Testing And Commissioning Of 3 Dimensional Led Backelite Out Door Type Ip66 Display Board In Bilingual ( Hindi / English ) As Per Approved Color And Design, Stainless Steel I.E. Back Side 4Mm Thick Sun Board And In Front Laser Cut Acrylic Sheet Of 3Mm Thick Of Approved Quality And Color As Per Latter Pattern 1 To 2 Collar ( As Per Board Size ) To Fixed Inside The Ss LatterS And Joint To Be Filled Up With Water Proof Silicon Where Ever Required To Make The Whole Structure Waterproof & Dustproof. Provided Inside The Latter Power Led Module Each 48 Consisting Of 3 Nos. Led ( As Per Board Size ) Minimum 75 Lumen Per Watt, 100Ma Power Current, 12Volt In Two Rows Along The Periphery Of Each Alpha Per, Shall Be Fixed In Such A Way To Give Uniform Bright Light To The Character LatterS And Other Accessories To Be Fixed On Aluminium Composite Panel ( Acp ) Of 4Mm Thick Exterior Grade Aluminium Not Less That 0.5Mm Of Approved Brand Fixed On Ms Welded Structure Made Out Of 2Mm Thick 65Mm X 65Mm Ms Square Pipe Section With Stiffness Welded Vertically And Horizontally In Regular Interval With Pipe From And The Pipe Frame Shall Be Covered From Back Front Facia Shell Covered By Gi Sheet Along With Latter Shell Be Fixed And Riveted All Sides I.E. Wiring And Entire Board Specially Designed Power Cable For Power Led Shall Be Of Outdoor Grade, Appx, Size Led Make Samsung, Hi-Light, Osram Actual Size Of Various Board To Approved By Engineer In Charge Before Supply The Material And Installation At Site Fixing. 49 Supplying, Installation, Testing & Commissioning Of Led Flood Light Fixture With Ip 66 & Ik 07 Protection Pressure Aluminium Die Cast Housing Capable Of Delivering A Following Lumens Output With A Minimum System Efficacy More Than 110 Lumens / Watt And A Cri Greater Than 70 . The Luminaire Shall Have A Life Class Of 50000 Hours @L70 For A Design Ambient Of 35 Deg C . The Inbuilt Electronic Driver Shall Operate At Power Factor > .95 Of Cct 5700K Minimum Internal Surge Protection Of 4 Kv With Toughned Glass / Polycarbonated Cover Lm 79 / 80 Certification To Be Provided By The Manufacturer For Led Luminaire / Led Chip Complete Etc. 50 22000 Lumens 51 Sitc Of Full Stainless Steel Body Water Dispenser With Storage Capacity Of 120 Litre, 60 Lph Cooling Capacity , R-134A Type Refrigerant I / C Complete Electrical And Plumbing Works Required To Make The System Functional Along With Dismantling Of Existing System And Less Credit For The Same.

Key Value

Document Fees
Refer document
EMD
INR 40454.0 /-
Tender Value
INR 20.22 Lakhs /-

BOQ Items

Name of Work: Provision of Electrical works in Nurse Hostel at Sanjay Gandhi Memorial Hospital, Mangolpuri Delhi-110083.
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
2Group A
3Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
425 mm
532 mm
6Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
73 x 1.5 sq. Mm
86 x 1.5 sq. Mm
93 x 4 sq. Mm
106 x 4 sq. Mm
113 x 6 sq. Mm
126 x 6 sq. Mm
13Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
142 X 16 sq. mm + 1 X 6 sq. mm earth wire
154 X 10 sq. mm + 2 X 6 sq. mm earth wire
16Fabrication, Supplying and installation of outdoor type cubical feeder pillar of suitable size upto 350 mm deep made out of M.S. Sheet 1.6mm. Thick (16 SWG) duly compartmentalised havingAl. busbar of minimum 300amp capacity double door with locking arrangement for protection from rain, dust, duly fixed on M.S. angle iron frame work of size 50 mm X 50 mm X 6 mm (NS) 50 cm long legs grouted in cement concrete mounted inside the cubical panel i/c connection, inter connection with aluminum thimbles,earth studs duly painted with one coat of red oxide & two coats of superior quality enamel paint complete etc. as reqd i/c supplying and fixing following accessories as per item i/c control wiring.
17Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
18250 A,36KA,FPMCCB
19100 A,30KA,FPMCCB
20Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. i) 100 A
21Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. i) 63A
22Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 12 way , Double door
23Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (a) 8 way (4 + 24), Double door
24Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole
25Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
26Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
27Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required.
28Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
29Supplying, Installation, Testing and Commissioning of surface/wall Mounted 18-20 Watt LED tube with 4 feet batten fitting, LED tube should have polycarbonate housing for efficient heat dissipation, in cool day light (5700 K to 6500 K) as required i/c connection with 1.5 Sq.mm. FRLS PVC insulated copper conductor, single core cable etc. as reqd.
30Supplying, Installation, Testing and Commissioning of wall mounted decorative Bracket light having complete fixture, 40 watt warm white lamp and Opal white glass diffuser for glare free light etc. as reqd.
31Supplying, Installation, Testing and Commissioning of 12w Round Full Glow LED Surface downlight having polycarbonate body and 2.5kv surge protection etc. as reqd.
32Supply, installation, testing& commissioning of 150 mm sweep fresh air fan having minimum speed of 1350 RPM, 260cubic meter per hour air flow, maximum power consumption of 30 watt, in the existing opening including making good the damages, connection testing and commissioning etc. complete as required.
33Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
341 or 2 Module (75mmX75mm)
356 Module (200mmX75mm)
36Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
373 pin 5/6 A socket outlet
385/6 A switch
39Telephone socket outlet
40TV antenna socket outlet
41Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
42Supplying,Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of followingsize Aluminium conductor armoured cable on wall surface as required.
433.5 X 95 sq. mm
44Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
4590 mm dia (OD-90 mm & ID-76 mm nominal)
46Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
47Supplying , installation, testing and commissioning of 3 Dimensional LED backelite out door type IP66 display board in bilingual (Hindi / English) as per approved color and design, stainless steel i.e. back side 4mm thick sun board and in front laser cut acrylic sheet of 3mm thick of approved quality and color as per latter pattern 1" to 2" collar (as per board size) to fixed inside the SS latter"s and joint to be filled up with water proof silicon where ever required to make the whole structure waterproof & dustproof. Provided inside the latter power LED module each
48consisting of 3 nos. LED (as per board size) minimum 75 lumen per watt, 100ma power current, 12volt in two rows along the periphery of each alpha per, shall be fixed in such a way to give uniform bright light to the character latter"s and other accessories to be fixed on aluminium composite panel (ACP) of 4mm thick exterior grade aluminium not less that 0.5mm of approved brand fixed on MS welded structure made out of 2mm thick 65mm X 65mm MS square pipe section with stiffness welded vertically and horizontally in regular interval with pipe from and the pipe frame shall be covered from back front facia shell covered by GI sheet along with latter shell be fixed and riveted all sides i.e. wiring and entire board specially designed power cable for power LED shall be of outdoor grade, appx, size LED make Samsung, Hi-Light, osram actual size of various board to approved by engineer in charge before supply the material and installation at site fixing.
49Supplying, installation, testing & commissioning of LED Flood light fixture with IP 66 & IK 07 protection pressure aluminium die cast housing capable of delivering a following lumens output with a minimum system efficacy more than 110 lumens /watt and a CRI greater than 70 . The luminaire shall have a life class of 50000 hours @L70 for a design ambient of 35 deg C . The inbuilt electronic driver shall operate at power factor > .95 of CCT 5700K minimum internal surge protection of 4 KV with toughned glass /polycarbonated cover LM 79/80 certification to be provided by the manufacturer for LED luminaire /LED chip complete etc.
5022000 Lumens
51SITC of Full Stainless Steel Body water dispenser with Storage Capacity of 120 Litre, 60 LPH cooling capacity , R-134A type refrigerant i/c complete Electrical and Plumbing works required to make the system functional along with dismantling of existing system and less credit for the same.