![https://www.tenderdetail.com Tender Details](/Content/img/TenderDetail.png)
![Tender Detail](/Content/img/TenderDetail.png)
Road And Building Department-RBD has published Tender For Construction Of Eye Modular Operation Theater Complex (1No) Such As Pre And Post Operation, Sterilization Room, Doctors Room And Other Related Areas) Inside At Dist.Head Quarter Hospital Rayagada. Submission Date for this Tender is 24-07-2023. Building Work Tenders in rayagada Odisha. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Air Handing Units AHU : Double skin air handing units ceilling suspended type, with 2 mm thickthermal break aluminum profile, 43+ 2 thickPuf panel having a densitynotless thankg/m3 panelshallhave 0.6 mm precoatedG.I sheet asouterskinand 0.6mm thickplane GI inner skin. The Unitshall besuitablefor clean roomapplicationswith covinginside. Thw AHU shall consists of return air mixingchamber G4 filter section with filter, DX type cooling Coil, fan section with Direct Drive PlugFanwith TEFCSquirrel cage induction motor. Fine filter section with EU 7 filter after the fan section. AHU shall be complete with |
2 | Doubleskinair handingunitswith 2mm thick thermalbreak aluminiumprofile, 43+-2 thickPufpanelhavingadensitynot lessthan38Kg /m 3 Panelshallhave0.6mmprecoated G.I sheetas outerskinand 0.6mmthickplane GIinner skin. The Unit shallbe suitablefor cleanroomapplicationswith coving inside. The AHUshall consistsofreturnairmixingchamber, EU 4 filterand EU7 filter , Chilledwatercoolingcoil fansection with DIDW centrifugalbackward curved fanwith TEFC squrirralcageinductionmotor , HEPA filtersection with EU13 HEPAfilter. AHUshall be complewithfresh air returnairand supply airdampers Fan section & filtersection shallhave service. |
3 | AHU Control Panel: Self standing/ wall mounted electrical panelconstructed out of 16 G CRCA sheetdulypowdercoated with suitablecapacity of main incomingMCCB,busbarmeteringpanelconsistingof voltmeter, ammeter andoutgoingfeedersconsisting of MCCB /MPCB , Contractorsrelays single phase prevetorforahus motors LDB & PDBs |
4 | Ducting : GI ducting24 swg with all jointssealed with siliconsealanntinsulated with XLPE rubberinsulation withaluminumfoil faced and joints withtapeincluding suports |
5 | Condensing Unit : 5.5 TR Nominal capacity Air cooledcondensingunit with singlecompressor . This will beconnected withcopperpipeswith DX coolingCoil inside AHU includingRefrigerant copper piping with fittings, |
6 | Dampers: GI Volumncontrol damper |
7 | Hatch BoxStaticpassboxmadeof SS 304 constructionwith UV lightand door interlocks Internal size600x600 |
8 | DifferentialPressure Gauge: Magnhelic gauge with GI box with SS cover plate and Sensors with necessary tubing |
9 | Electricals : LDB /pdbWITH CMBswiringfor light, power socktsetc and cabling for AHU , CDUearthing , 5/15 amp |
10 | OT pendent Light |
11 | LED lightPanel: OT peripheriallightsystem with 30WLED withelectronicballast |
12 | LEDlightPanelforotherrooms30W ledWITHELECTRONICBALLASTSUITABLETO MOUNT ON GRIDCEILLING SYSTEM |
13 | LaminarAirflowterminalfor supplyair aluminum constructionwith DOPfor fixingof H13 HEPAFilter filterforsupplycleanair above OT bed. Unit shall haveprovisionfor OT lightingarrangementat centre panel (2"x2) |
14 | OT Return air Riser :80 mm thickdoubleskin(ppgi) ONBOTH SIDESWITH 40+- 2 KG /M3densityPUF filled on bothsidesand centralportionRA riser duct, 0.6 mm sheetsonbothsides duct 900x100 mmmadeof GI internalforreturn of air Returnair riserat corners of OTcomplete with |
15 | Supplyand returnair diffuserwithcollar damper |
16 | OT Cleanroomceilling system : Walkabledoubleskinfalseceillingof 50mm thickwith skin (PPGI) on bothsides with40+-2 kg/mg densityPUFfilingwith 0.6 mm thicksheetson |
17 | Cleanroomwall panel :50 mm thick doubleskin(PPGI)onboth sideswith40+-2 Kg /M3density PUFfiling 0.6mm |
18 | Coving: Wall wall and wall to ceillingCoving |
19 | OT SWINGDOOR : Supplyof CleanroomSolidSteelDoorsmade up of 0.8 mm thickGI Sheet , Doorleaf 44mm thick , anddoorframeof 1.2 mm tjhickGI sheetwith PUFas infillmaterialwithPolyesterPowderCoatedfinishwithacessoriess such as doorclosure D -Handle , SS Hinges Door Lock, Push plates AutomaticDropseal view panel. |
20 | OT SWINGDOOR : Supplyof CleanroomSolidSteelDoorsmade up of 0.8 mm thickGI Sheet , Doorleaf 44mm thick , anddoorframeof 1.2 mm tjhickGI sheetwith PUFas infillmaterialwithPolyesterPowderCoatedfinishwithacessoriess such as doorclosure D -Handle , SS Hinges Door Lock, Push plates AutomaticDropseal view panel. |
21 | OT Hermeticallysealed automaticsliding DoorDoor core 60mm thickwith 4mm thickHPCLSkinat bothsidesofthe doorto providebetter strengthand rigiditywith PUFinfill of 40 Kg/m3 density , PUFthickness52 mmHigh grade aluminium extrusion profileto carrydoor weight Canopy powder caoted GI Sheetwith closing caps |
22 | Grid CeillingoutsideOT Room-2"x2"FOR Non cleanAreas |
23 | PU Paint forBrickWall for labinside partitionwalls |
24 | AluminiumDoor Normallylockablemade with clear4mmpolycarbonate glazingtop bottom tracksJambsFlashing& |
25 | AluminiumDoor Normallylockablemade with clear4mmpolycarbonate glazingtop bottom tracksJambsFlashing& installation hardware DoubleDoor of size 1800mmx |
26 | Vinyl flooring 2 mm thickall joints fusion welded for |
27 | Floorcoving 50 Rfor OT Room |
28 | X-Ray view board mounted on wallwithilluminated board for single view of x ray plate approxsize 14" x17" |