| 1 | Octagonal G.I. pole |
| 2 | a ) Site survey, Supply, erection, testing & commissioning of M.S. Galvanized Octagonal Decorative Poles with base platefabricated from special steel plates as per BSEN 10025/IS 5986 with excellent ultimate tensile strength, yield stress and elongation and corrosion resistance properties and suitable weld ability. Plates to be out and folded to form a octagonal cross section and welded longitudinally as per IS 9595/IS 10178. The pole shall withstand windpressure of 180 Km/Hr as per IS:875 and of 9meters length in single section, continuously tapered profile for stability and aesthetics with face to face dimension being 190mm at bottom and 85mm at top and 3.0mm wall thickness with foundation base plate made of Hot rolled M.S plateas per IS:2026 and 300mm x 300mmx16mm thick duly welded to the base of the pole with foundation Bolts of 800mm length and M24 category with Nuts for grouting in concrete as per drawing. |
| 3 | *500mm to 1500mm long or suitable size as per design of the Company (Galvanizedas above) Double Cross arms made out of G.I. tubular pipes Class B of suitable size and welded fit the top of the above pole and MS Plate for rigidity between cap and pipe with provision of passing the electrical cable from the pole to the end of cross arm for connection of the street lighting LED luminaries. |
| 4 | Excavation & concreting: |
| 5 | b)Excavation of pole pit in all kind of soil includingrock of all verity of size 1200mm with filling of sand to a height of 100 mmand then laying foundation of Reinforced cement concrete (1:2:4) base foundation 1000mm x 1000mm x 200mm Height& 900MM X 900MM X 600MM Height RCC from base to TOP high with granite metal of nominal size20mm to 25mm including side shuttering and grouting of foundation bolts and supply and erection of pole as specified above including watering and ramming it as required including provision for passage of cables and finishing the surface with 1:4 ratiocement plaster as per Drawing. However , minimumrequirement of external forces for which the pole has to be designed as mentioned in the BOQ. Depending on the site condition the bidder has to consider the slight modification, if any to meet the design criteria subject to above the minimum foundation size as mentioned for which no separate payment will be made. |
| 6 | Supplying, installation and Commissioning of energy saving LED confirming to (90w) street light luminaries equivalent to Model No: CRP-404-90-57-SL-GL-NSG of Crompton make to be fixed on the ends of cross arms mounted on the GI octagonal poles complete with connection from terminal box at the pole base to the luminaries with the help of 1.5 Sq.mm 650/1100 Volt grade 3core flexible copper cable, PVC insulated and sheathed conforming to IS:694, complete with supply of all materialssuch as luminaries withcontrol gear, lamp, connecting wires and all accessories and sundries as required for the work and as per direction of EIC. |
| 7 | Supply, delivery, laying, testing complete as required & as per the direction of Engineer-in-charge of 4c x 16sqmm Al. Ar PVC cable with its protection 40mm dia HDPE (H) pipes (Supplyand laying cost paid separately) with excavation of 750mm deep cable trench in all kinds of soil & rock (other than granite) and back filling with excavated soil from panel to pole to pole. The cable shall have ISI marking and name of the manufacturer on the body of the cable. (span length 30mtr) |
| 8 | Supply of materials and making of end termination of with brass double compression cable glands and bi-metallic crimping type cable lugs for PVC insulated & PVC sheathed aluminium conductor armoured power cable of 1100 volt grade of the following sizes complete as required and as per direction of EIC. |
| 9 | 4 x 16sqmm Al. Ar. Cable. |
| 10 | Supply & Laying of 40mm dia HDPE Pipe for cable protection as per technical specification as required completed. |
| 11 | Supply and fixing of 1nos 10kA \"C\" curve 6A to 16A SP MCB including suitable size Bimetalic / Steel rail for mounting the 2nos SP MCBs, supply and fixation of 12\" x 5\" Hylamp sheet to protect the wiring as cover. One no 3phase 5wire connector is to be provided for loop-in loop-out of 3phase power including earth connectivity. |
| 12 | Supply, delivery, laying, testing complete as required & as per the direction of Engineer-in-charge of 3 ½ x 35mm2 Al.Ar. PVC cable with its protection 50mm dia HDPE (H) pipes with excavation of 750mm deep cable trench in all kinds of soil & rock (other than granite) and back filling with excavated soil from S/Spanel to street light panel. The cable shall have ISI marking & name of the manufacturer on the body of the cable. |
| 13 | Supply of materials and making of end termination of with brass double compression cable glands and bi-metallic crimping type cable lugs for PVC insulated & PVC sheathed aluminium conductor armoured power cable of 1100 volt grade of the following sizes complete as required and as per direction of EIC. |
| 14 | 3.5CX 35sqmm Al. Ar. Cable. |
| 15 | Supply, installation, testing & commissioning of earth pit complete with 3mtrx50 mm dia G.I. perforated earth electrode complete with inspection chamber & cover as per technical specification and instruction of EIC.(2nos for street light panel and 2nos for street lighting lamp as 1no for each 10 poles) |
| 16 | Supply of all materials, laying & termination of 2nos of No.8 G.I. wire for earth connections to the street light panelas required as per technical specification and instruction of EIC. |
| 17 | Supply, installation, testing and commissioning of GI coil earthing including excavation of earth pit in all kinds of soil/ rock filling with charcoal & salt, connections to earthing studs / bolt of the pole complete including supply of all materials. |
| 18 | Supply, installation, testing & commissioning of outdoor type street light control panel boards madeout of 2mm CRCA steel sheet duly painted by epoxy light grey enamel paint including cost of cable end termination and comprising the followings: |
| 19 | Incomer : 1no of 40A4PMCB with LEGRAND. |
| 20 | Busbar: 4nos cu. Busbar duly PVC sleeved. (Size-25 x 3mm) |
| 21 | Instruments: 3nos.LED type phase indicating lamps with control fuses & toggle switch. |
| 22 | 1set 0-500V Digital voltmeter,Ammeter,CT 3 nos,70 Amp contractor and Digital timer switch. |
| 23 | There is provision for fixing of energy meter. |
| 24 | OUT GOING |
| 25 | 25 Amp 4P MCB |
| 26 | Construction of 2 nos 25KVA, 11/0.4KV Pole Mounted Substation |
| 27 | Supply, delivery and installation of 10mtr Long 150 x 150mm R.S Joist Pole including excavation of Pole pit in all kinds of complete as required for Substation DP complete with all respect. |
| 28 | As S/S 2 nos DP |
| 29 | Supply and fixing of Pressure channel with 100 x 50 x 6mm 2.8mtr long 4nos in each DP (9.2kg/mtr) as requried as per technical specification & direction of E.I.C. |
| 30 | Supply and fixing of Transformer mounting channel with 100 x 50 x 6mm, 2.8mtr long 2nos for each DP (9.2kg/mtr) as requried as per technical specification & direction of E.I.C. |
| 31 | Supply and fixing of AB switch and HG fuse mounting channel with 75 x 40 x 6mm 1mtr long 4nos in each DP (6.8kg/mtr) as requried as per technical specification & direction of E.I.C. |
| 32 | Supply and fixing of Cantilever channel GI for supporting AB swith arm with 75 x 40 x 6mm 1mtr long 2nos in each DP (6.8kg/mtr) as requried as per technical specification & direction of E.I.C. |
| 33 | Supply and fixing of Transformer belting with 50 x 50 x 6mm 2.8mtr long 2nos in each DP (4.5kg/mtr) with side angle (Total 7mtrs) as requried as per technical specification & direction of E.I.C. |
| 34 | Supply and fixing of Angle for mouting L.T. Distribution box with 50 x 50 x 6mm 2.5mtr long 2nos in each DP (4.5kg/mtr) as requried as per technical specification & direction of E.I.C. |
| 35 | Supply and fixing of 11KV Polymer type disc. Insulator as per the direction of EIC. |
| 36 | Supply & fixing of 11KV Polymer type hard ware fittings as per the direction of EIC. |
| 37 | Supply, installation, testing and commissioning of 400A horizontal gang operated type AB switch with operating pipes handle & I hook etc.complete as reqd. & as per site engineers instruction & technical specification. |
| 38 | Supply, installation, testing and commissioning of 400A Horn Gap fuse complete as reqd. & as per site engineers instruction & technical specification. |
| 39 | Supply, installation, testing and commissioning of 11 KV 10kA class lightening Arrestors complete as reqd. & as per site engineers instruction & technical specification. |
| 40 | Supply, installation, testing & commissioning of HT stay set complete for 11KV O.H. line as per technical specification and site Engineerinstruction with following materials. |
| 41 | HT stay set complete. |
| 42 | G.I. Stay wire (7/10) |
| 43 | H.T. stay insulator |
| 44 | HT stay clamp |
| 45 | Supply, installation, testing and commissioning of earthing complete as per technical specification & site engineers instruction as follows. |
| 46 | Earthing device(G.I pipe) (40mm dia medium gauge 3mtr long) |
| 47 | Material for Massionary work for Earth pit, Charcoal, salt etc. including construction of earthing chamber (Size-2\" x 2\") and RCC slab cover. |
| 48 | Supply of allmaterials & fixing/laying of following G.I. flat/ Wire for earth connection to all electrical equipments & iron parts as reqd & asper site engineers instruction & technical specification |
| 49 | 25 x 5mm G.I. Flat for earthing. |
| 50 | 40 x 6mm G.I. Flat for neutral. |
| 51 | Supply of all materials for nut bolting of different M.S structure for 11KV O.H. line / Substation as per technical specification and direction of E.I.C |
| 52 | Assorted size GI nuts & bolts and washer. |
| 53 | Concreting of staypit C.C. - 1:3:6 using 40mm BHG metal size - 5\" x 2\" x 2\" = 20CFT = 0.570 Cum.Padding 900x600x900mm = 0.0810.651Cum @ 3071.25 = 1999.38 each. |
| 54 | Concreting of pole pit ratio1:1.5:3( 500 mmx500 mmx1800mm)=0.45 cu. Mr. |
| 55 | Couping of support section ratio 1:1.5:3 with dimention (500x500x450) mm =0.1125 Cu. Mtr |
| 56 | Supply & stringing of 55sqmm AAA insulated conductor over head line including jumpering, fixing of PG clamps etc. complete as per site condition and direction of EIC. |
| 57 | Supply & Installation, testing and commissioning of 25KVA 11/0.4KV outdoor type Aluminium wound 3star rated transformer with LT end termination box with water tight gaskets and extended copper bus for terminationand cable glands complete as reqd & as per site engineers instruction & technical specification. |
| 58 | Supply, installation, testing & commissioning of outdoor type street light control panel boards madeout of 2mm CRCA steel sheet duly painted by epoxy light grey enamel paint including cost of cable end termination and comprising the followings: |
| 59 | Incomer : 1no of 63A 25 KA 4PMCCB with LEGRAND. |
| 60 | Busbar: 4nos cu. Busbar duly PVC sleeved. (Size-25 x 3mm) |
| 61 | Instruments: 3nos.LED type phase indicating lamps with control fuses & toggle switch. |
| 62 | 1set 0-500V Digital voltmeter. |
| 63 | There is provision for fixing of energy meter. |
| 64 | Supply & painting with Aluminium paint to the poles & cross arms. |
| 65 | Brick wall boundaring (size 10\" x 12\") sand filling and metal spreading, fixing of Iron grill gate with two nos RCC base pillar etc. as per TPCODL specification. |
| 66 | Sundries for survey, PVC tape, ampire tape, danger board, small size nut & bolt preparation of drawing etc. |
| 67 | 11KV Line (1 span) in each S/S |
| 68 | Supply, delivery and installation of 10 mtr Long 150x150mm R.S Joist Pole including excavation of Pole pit in all kinds of complete as required for Line Pole complete with all respect. |
| 69 | As 11KV Line Pole |
| 70 | Supply and fixing of 11KV V cross arm as required and as per the direction of EIC. |
| 71 | Supply and fixing of back clamp for 11KV V cross arm as required and as per the direction of EIC. |
| 72 | Supply and fixing of 11KV Pole Top Bracket as required and as per the direction of EIC. |
| 73 | Supply and fixing of 11KV straight crossarm using 100x50x6mm Channel as required and as per the direction of EIC. |
| 74 | Supply & fixing of 11KV G.I Pin with Polymer type Insulator as per the direction of EIC. |
| 75 | Concreting of pole pit ratio1:1.5:3( 500 mmx500 mmx1800mm)=0.45 cu. Mr. |
| 76 | Couping of support section ratio 1:1.5:3 with dimention (500x500x450) mm =0.1125 Cu. Mtr |
| 77 | Supply & painting with red-oxide paint to the poles and cross arms. |
| 78 | Supply & painting with Aluminium paint to the poles & cross arms |
| 79 | Supply & installation of coil earthing as per technical specification& site engineer instruction. |
| 80 | Supply and fixing of Danger Board |
| 81 | Supply and fixing of G.I Barbed wire |
| 82 | Sundries for survey, PVC tape, ampire tape, danger board, small size nut & bolt preparation of drawing etc. |