Public Works Department-PWD has published Tender For Maintenance Of Electrical Installations, Fans, Street Light/ Compound Light/ Security Light, Air-Conditioning, Pump Set, Dg Set At Fire Station Connaught Place, Fire Station Rakaab Ganj ,Chanakya Puri, New Delhi. Submission Date for this Tender is 01-07-2023. Electrical Maintenance Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | SH-I (RMO Work) Routine maintenance and attending day to day complaints of electrical installations and compound/security lights along with allied fixtures & feeder pillars etc. including repairing the wiring and lighting fixture complete with carrying out the daily drill comprising of cleaning of the electrical installation, lodging of electrical complaint in the complaint register, testing the insulation resistance, earth resistance etc. and providing assistance to the Engineer-in-charge during breakdown maintenance complete with replacement of worn-out parts issued by the department to the contractor & keeping the entire installation on functional mode including operation & maintenance of various capacity drinking water supply pump sets, DG set comprising of AMF panel & allied accessories and carrying out the daily drill comprising of cleaning of pump house and maintaining log book for above installation by deploying staffs as per details of staff, terms & conditions and Inventory attached etc. as required. |
2 | SH-II (Miscellaneous Electrical Works) Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. (a) Group B |
3 | (b) Group C |
4 | Rewiring for light point/fan point/exhaust fan point/call bell point with 1.5 Sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 Sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/recessed steel conduit including dismantling as required. (a) Group B |
5 | (b) Group C |
6 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. (a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
7 | (b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
8 | (c) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
9 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (a) 3 x 1.5 sq. Mm |
10 | (b) 3 x 4 sq. Mm |
11 | (c) 3 x 6 sq. Mm |
12 | Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. (a) 25 mm |
13 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 25 mm |
14 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. |
15 | Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, “C” curve including connections, painting etc. as required. |
16 | Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. (a) 12 Module (200 mmX150 mm) |
17 | (b) 8 Module (125 mmX125 mm) |
18 | (c) 6 Module (200 mmX75 mm) |
19 | Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. (a) 1 or 2 Module |
20 | (b) 3 Module |
21 | (c) 6 Module |
22 | (d) 8 Module |
23 | (e) 12 Module |
24 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. (a) 5/6 A switch |
25 | (b) 3 pin 5/6 A socket outlet |
26 | (c) 15/16 A switch |
27 | (d) 6 pin 15/16 A socket outlet |
28 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
29 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (a) 12 way, Double door |
30 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (a) Single Pole |
31 | (b) Single pole and neutral |
32 | Supplying, installation, testing & commissioning of energy efficient recessed mounted type 34W to 36W full window glare free opal diffuser LED panel luminaries of size 2 x 2 feet (nominal size) including connections with 3 x 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc as required. The total system wattage not more than of 36W, LED lumen should be = 3960 system efficacy of = 110 lumen /watt colour temperature 4000K to 5700K, power factor>0.95, CRI (Ra)>80, THD <10%, with APFC driver having driver efficiency >85%, operating voltage 150-270 volts with minimum 2.5KV surge protection. The luminaries shall be submitted with LM-80 report with a life of 50000 Hours @ L-70 and LED photo biological safety report conforming to IEC 62471 & LED source manufacturer and LM-79 report from NABL accredited Lab. The LED chip should be of Cree, Nichia, Philips Lumiled, Osram, Edison. |
33 | Supplying, laying and fixing of following PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade etc as reqd. in the following manner: (a) 3 x 10 sq.mm on wall surface |
34 | (b) 4 x 16 sq.mm on wall surface |
35 | Supplying of following material etc. complete as required. 1.5 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable a)1.5 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable |
36 | b)4.0 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable |
37 | c)6.0 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable |
38 | d)25 mm dia. ISI marked, steel conduit |
39 | e)25 mm dia. ISI marked, PVC conduit |
40 | f)Modular GI box for 3 module |
41 | g)Modular GI box for 6 module |
42 | h)Modular GI box for 12 module |
43 | i)3 pin 5/6 A modular socket outlet, ISI marked |
44 | j)6 pin 15/16 A modular socket outlet, ISI marked |
45 | k)S.P. 5/6 A, one way modular switch, ISI marked |
46 | l)S.P. 15/16 A, one way modular switch, ISI marked |
47 | m)Modular base & cover plate for 3 module |
48 | n)Modular base & cover plate for 6 module |
49 | o)Modular base & cover plate for 12 module |
50 | p)6 A to 32 A ratings, SP MCB, “C” curve, 10 kA breaking capacity |
51 | q)6 A to 32 A ratings, SPN MCB, “C” curve, 10 kA breaking capacity |
52 | Credit of assorted electrical material such as copper wire/cable, steel/pvc conduit, switch-socket, GI Box, DB, MCB, MCCB, aluminium cables etc. |
53 | Add @31.27% on DSR-2016 (E) Items (i.e. on Rs. 633251/-) |
54 | Less @ 9.50% on DSR-2016 (E) Items (i.e. on Rs. 633251/-) |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy