| 1 | Supply,Installation,Testing And Commissioning Of 22.0 Tr Air Cooled Inverter Ductable Type Air Conditining Units As Per Specification Attached Make: Daikin, Bluestar, Carrier,Mitshubishi,O General |
| 2 | SUPPLY,INSTALLATION,TESTING AND COMMISSIONING OF 22.0 TR AIR COOLEDINVERTER DUCTABLE TYPE AIR CONDITINING UNITS as per specification attached Make: DAIKIN,BLUESTAR, CARRIER,MITSHUBISHI,O GENERAL [ Warranty Period: 30 Months after the date of delivery ] |
| 3 | Supply, laying, connection and testing of Interconnecting refrigerant pipe for 22.0 Tr AC unit workwith closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as perspecifications, all piping inside the room shall be properly supported with MS hanger as per item Part-A(e) ofspecifications and Make: Totaline/Mex flow/Rajco or equivalent |
| 4 | Providing & fixing control cum transmission wiring of copper in suitable conduits between indoorand out door unit. Make: L&T/Finolex/RR Kable/KEI/POLYCAB/Havells. |
| 5 | Providing and fixing of M.S stand for outdoor units, made of ms angle 40x40x5 MM size withworking platform all around duly painted with synthetic paint as per site requirement as per IS 808 or latest/ orequivalent make |
| 6 | Supply, installation, testing and commissioning of fire retardant nonporous double layer flexiblecanvass connection between each duct type indoor unit and ducting. Make: Make of material to be got approvedby Dy CEE/PS. |
| 7 | Supply and Fixing of 4000 CFM Cabinet Type Exhaust With Elementor Pad ,STP 80 mmCentrifugal Backward Inclined DDIW Blower With Suitable High Static Pressure to CREATE the Required IntakeVelocities and over Come the Pressure lose at the inlet of filters and Duct, DDIW Centrifugal Blower ( MotorOutside the Effluent Air Stream With Different Motor Chamber for Motor) backward Inclined, non over loadingtype.(smaller motor) mounted directly on motor shaft.(slip losses and lesser maintenance ) Dynamicallybalanced to provide a vibration free operation . fan to be direct driven to motor. Make: Zeco/Edgetech/AirTree/Aircon/Daikin ( Water supply shall be provided By RCF) |
| 8 | Supply and fixing Grilles/Diffuse consisting of Duct Damper for Hoods/Grill with Damper/DiffuserWith Damper/Diffuser without Damper as per site requirement and list of makes Make: systemair/carryaire/Dynamic /airflow. |
| 9 | Supply and Fixing of Fresh Air AHU of 3500 cfm Cabinet Type Air Washer Forward WithHoneycomb Pad , Stp 40 to 50 mm Inclined DDIW Blower With Suitable High Static Pressure to CREATE theRequired Intake Velocities and over Come the Pressure lose at the inlet of filters and Duct ,].DDIW CentrifugalBlower ( Motor Outside the Effluent Air Stream With Different Motor Chamber for Motor)Forward Inclined, nonover loading type.(smaller motor) mounted directly on motor shaft.(slip losses and lesser maintenance )Dynamically balanced to provide a vibration free operation . fan to be direct driven to motor as per requirement.Make: Zeco/Edgetech/Air Tree/Aircon/Daikin |
| 10 | Supply, installation, testing and commissioning of Control panel with Star delta starter/DOL panelwith 01 No. - 0-40 A TP MCB with Conforming to BIS DOL/Star Delta starter, overload relay, ammeter (0-63A),single phase preventer. on off push button, on/off/trip indicators with protection fuse, manual reset overloadrelays, armoured cabling with proper tray supports from starter panel to fan motor Starter panel should beprovided with auto manual toggle switch & facility to operate on remote signal. Necessary earthing, smoke & firedetector providing signal to starter panel, related control cabling shall be part of starter panel as approved byconsultants & clients. Controls & interlocking accessories as Complete with Connection / interconnectionrequired for above switchgears complete in all respect to run/Start the Motor Fan in case of Fire. PreferredMAKE of switchgear and protection devices are L&T, Siemens, Schneider, Legrand, Havells or equivalentsubject to prior approval by Competent authority of RCF. Drawings to be submitted for approval before supplyand installation for satisfactory performance. |
| 11 | Supply and Fixing SS 304 Hood With Oil Filters and Hanging With Rod , faster , Volume ControlDamper Provide By Each Connection and Gasket Etc Qty as per Kitchen Requirement & as per list of makes.filters make: AIRTECH /PUROLATOR/PUROMATIC or equivalent make to be got approved from competentauthority |