}

Tender For Construction Of Biomedical Waste Management Storage Cum Equipment Room At Chc, Bentakar In The District Of Cuttack For The Year 2023-24, Cuttack-Odisha

Road And Building Department-RBD has published Tender For Construction Of Biomedical Waste Management Storage Cum Equipment Room At Chc, Bentakar In The District Of Cuttack For The Year 2023-24. Submission Date for this Tender is 03-07-2023. Waste Disposal Services Tenders in Cuttack Odisha. Bidders can get complete Tender details and download the document.




Tender Notice

38319178
Tender For Construction Of Biomedical Waste Management Storage Cum Equipment Room At Chc, Bentakar In The District Of Cuttack For The Year 2023-24
Open Tender
Indian
Odisha
Cuttack
03-07-2023

Tender Details

Construction Of Biomedical Waste Management Storage Cum Equipment Room At Chc, Bentakar In The District Of Cuttack For The Year 2023-24

Key Value

Document Fees
INR 6000 /-
EMD
INR 12300.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:Construction of Biomedical Waste ManagementStorage cum Equipment room atCHC Bentakar in the district of Cuttack for the year 2023-24.
Sl. No. Item Description
1Civil Works: Earth work in excavation of foundation in hardsoil including rough dressing and levelling the beds within 50m. initial lead and 1.5m. initial lift with cost, conveyance, taxes as per specification and directionof Engineer in charge
2Filling foundation and plinth with good quality river sand with watering and ramming incluing cost, conveyane, cost of all materials and labour etc complete as per direction and specification of Engineer in charge
3Cement concrete (1:3:6) in foundation and plinth using 4cm(1½”) size hard crusher broken granite stone metal of approved quality and from approved quarry including lowering, laying concrete watering, curing etc, complete to required levels laid in layers to required thickness including cost, conveyances, royalties, taxes of all materials and cost of all labour with T&P required for the work etc, complete as per specification & direction of the Engineer-in-charge
4RCC work ofM-20 Grade with 20mm and down graded size crushed stone aggregates mixed by concrete mixer, laying in layers and compacting by vibrator & all leads and lifts including frame works including cost, conveyance, cost of all labour, T&P, cost of all materials etc. complete as per direction and specification of Engineer-in-charge.(a)Column base and footing
5Plinth Beam
6Column & Beam in Superstructure
7LINTEL
8CHAJJA
9RCC Well Ring (50mm thick slab)
10ROOF SLAB
1175mm thick Cover Slab
12Cutting, straightening coiled or bent up M.S. Rod or tor steel using SAIL/RINL/TATA/JINDAL STEEL/ SHYAM STEEL includingbending, binding, welding and joining if necessary and tying the grills and placing in position as required for R.C.C. Work and for providing fan hooks as required, hoisting, lowering, laying including cost, conveyances, taxes of M.S. Rod or tor steel and binding wires of 18 to 20 gauge and labour required for the work for bending, binding and tying the grills in all floors (payment will be made on standard weight of B.I.S. for M.S. Rods or tor steel only) etc. complete as per specification & direction of Engineer-in-charge .
13Fly Ash Bricks masonry (25cmx12cmx8cm) having crushing strength not less than 75Kg/sqcm in cement mortar (1:6) after immersing the bricks for six hours in water before use in Foundation & Plinthand for ornamental flower beds, plinth molding and similar such type of works with all necessary projections, cutting, circular molding, corbelling, watering, curing etc. including cost, conveyances, royalties ofmaterials and cost of all labour with T&P required for the work etc. complete along with testing of strength as per relevant I.S.standard andas per specification & direction of Engineer-in-charge. (Foundation)
14Fly Ash Bricks masonry (25cmx12cmx8cm) having crushing strength not less than 75Kg/sqcm in cement mortar (1:6) after immersing the bricks for six hours in water before use in Superstructureand for ornamental flower beds, plinth molding and similar such type of works with all necessary projections, cutting, circular molding, corbelling, watering, curing etc. including cost, conveyances, royalties ofmaterials and cost of all labour with T&P required for the work etc. complete along with testing of strength as per relevant I.S.standard andas per specification & direction of Engineer-in-charge. (Foundation)
15Providing 2.5cm thickGrading concrete (1:2:2) on roof slab with 6mm size black crusher broken granite chipsall floors finished smooth to Roof surfacecleaning the surface to proper plumbs & level and making necessary grooves, beads & drip course to give required ornamental finish as per drawing, watering, curing, scaffolding, screening sand etc. complete with cost, conveyances, royalties ofmaterials and cost of all labour with T&P, sundries required for the work etc. complete as per specification & direction of Engineer-in-charge.
16Providing 16mm thick cement plaster in cement mortar (1:6) in all floors finished smooth to outside surface of brick walls after racking out joints, scrapping & cleaning the surface & finishing the plaster surface smooth using wooden float only to proper plumbs & level and making necessary grooves, beads & drip course to give required ornamental finish as per drawing, watering, curing, scaffolding, screening sand etc. complete with cost, conveyances, royalties ofmaterials and cost of all labour with T&P, sundries required for the work etc. complete as per specification & direction of Engineer-in-charge.
17Providing 12mm thick cement plaster in cement mortar (1:6) in all floors finished smooth to outside surface of brick walls after racking out joints, scrapping & cleaning the surface & finishing the plaster surface smooth using wooden float only to proper plumbs & level and making necessary grooves, beads & drip course to give required ornamental finish as per drawing, watering, curing, scaffolding, screening sand etc. complete with cost, conveyances, royalties ofmaterials and cost of all labour with T&P, sundries required for the work etc. complete as per specification & direction of Engineer-in-charge.
18Providing 6mm thick cement plaster.(1:4) to RCC surface finished smooth including closed deep chiping and slury treatment including watering, curing, scaffolding, screening sand etc. complete with cost, conveyances, royalties ofmaterials and cost of all labour with T&P, sundries required for the work etc. complete as per specification & direction of Engineer-in-charge
19Providingfitting and fixing of Kadappa tiles in floors of approved makeover 25mm thick cement mortar(1:1) including cost, conveyances, royaltiesofmaterials and cost of all labour with T&P required for the work etc, complete as per specification & direction of the Engineer-in-charge
20Providing and laying of Glazed Ceramic Wall Tiles in dado/skirting confirming to IS : 15622 of approved make, quality, colour and size 600mm x 300mm upto required height from floor level fixed over an under layer of 12mm thick bed of cement mortar (1:3) (1 Cement : 3 Coarse sand)including cutting to size, laying and filling the joints with white cement slurry mixed with colouring pigment to match the shade and colour, cleaning the surfaces with oxlaic acid, machine grinding, mirror polishing including the cost of all materials, cost of all labour, conveyance, royalties, loading, unloading,sundries, watering and curing, T&P, etc. complete as per the direction of the Engineer-in-Charge.
21Supplying, fitting & fixing in all floors of M.S.grills and gates, with top rails, steel windows, critical frames for windows balustrades of stair case and parapet railing made out of M.S.square bar/flat as per approved drawing and design including making holes in walls and RCC structure, wood work etc and making good to the damages to walls with cement concrete(1:2:4) with hard crusher broken granite stone chips of 12mm to 20mm size(20mm size not to exceed 25%) of approved quality with cost of all materials labour, cost of welding all T&P, sundreis etc complete in all respect as per specification and direction of Engineer in charge(screws and other hardward required materials to be used in the work shall be of approved quality and specification and shall have to be supplied by the contractor at his own cost. a) Door
22Supplying, fitting & fixing in all floors of M.S.grills and gates, with top rails, steel windows, critical frames for windows balustrades of stair case and parapet railing made out of M.S.square bar/flat as per approved drawing and design including making holes in walls and RCC structure, wood work etc and making good to the damages to walls with cement concrete(1:2:4) with hard crusher broken granite stone chips of 12mm to 20mm size(20mm size not to exceed 25%) of approved quality with cost of all materials labour, cost of welding all T&P, sundreis etc complete in all respect as per specification and direction of Engineer in charge(screws and other hardward required materials to be used in the work shall be of approved quality and specification and shall have to be supplied by the contractor at his own cost. b) Window
23Supplying, fitting & fixing in all floors of M.S.grills and gates, with top rails, steel windows, critical frames for windows balustrades of stair case and parapet railing made out of M.S.square bar/flat as per approved drawing and design including making holes in walls and RCC structure, wood work etc and making good to the damages to walls with cement concrete(1:2:4) with hard crusher broken granite stone chips of 12mm to 20mm size(20mm size not to exceed 25%) of approved quality with cost of all materials labour, cost of welding all T&P, sundreis etc complete in all respect as per specification and direction of Engineer in charge(screws and other hardward required materials to be used in the work shall be of approved quality and specification and shall have to be supplied by the contractor at his own cost. b) Ventilator
24Labour charges for fitting fixing MS gates, MS door, Ms window with grills, grills collasible gates etc. as per approved design including cost, conveyance, taxes of all materials, labours sundries T&P required for the work as per specification and direction of Engineer in charge. Door
25Labour charges for fitting fixing MS gates, MS door, Ms window with grills, grills collasible gates etc. as per approved design including cost, conveyance, taxes of all materials, labours sundries T&P required for the work as per specification and direction of Engineer in charge. Window and Ventilator
26Priming one coat with wall primer water bound cement primer including including cost, conveyance, taxes of all materials, labours sundries T&P required for the work as per specification and direction of Engineer in charge.
27Finishing the wall surface with cement putty water based of approved make and finished smooth & even surface to receive painting including cost of scaffolding staging charges with cost, conveyances,of all materials, cost of labour, T&P required for the work etc. complete as per specification & direction of the Engineer-in-charge.
28Painting two coats with approved plastic emulsion paint over a coat of primer to inside surface of walls after cleaning the surface including watering, curing with cost, conveyance,of all materials, labour, T&P required for the work etc. complete as per specification & direction of Engineering-in-charge.
29Painting two coats with a coat of approved paintinironwork over red oxide primer including sand papering, polishing the surface, cost, conveyances ofmaterials and cost of all labour TandP etc complete as per specification and direction of Engineer in charge
30Finishing the exposed surfaces of wall with weather coat of any approved shade on new work two coats over one coat of primer to give am even shade including cost of weather coatcost, conveyances,of all materials, cost of labour, T&P required for the work etc. complete as per specification & direction of the Engineer-in-charge.
31Providing, suppying fitting and fixing with deep burial pit and sharp pit with precast RCC circular slab including cost, conveyances,of all materials, cost of labour, T&P required for the work etc. complete as per specification & direction of the Engineer-in-charge.
32E.I Works: Recessed wiring to light point/ fan point/Exhaust fan point/Call bell point with 1.5sqmm FR PVC Insulated single core multistarand copper Conductorof ISI marked with 20mm dia non metalic PVC flexible conductwith 6A 250V MODULAR type switch ISI marked and ceiling rose marked mounted on Modular GI Boxhaving front modular base plateof suitable size, with 1.5sqmm FR PVC Single core multistrand copper conductor as earth wire includingallaccessories and connection as per direction of Engineer in charge (Make of wire Finolex / Havells / Anchor / Finolex/Polycab) switch /socket/modular GI Board (Make- legrand Myrius antibacterial /SchneiderLIVIA antibacterial )light pointGroup-A
33-do- LightpointGroup-B
34-do- Fan pointGroup-B
35-do- Fan pointGroup-C
36Recessedwiring to 5AMP/6AMPmodular socket out let with 2x1.5sq mm for FRLS PVC insulated single core multistrand copper conductor of ISI marked in reccess20mm dia non metalic PVC flexible conduit size ISI marked,MS Box and earthing point with1x1.5sqmm FR PVC insulated single core multistarnd copper conductor for loop earthing etc,as required complete in all respect as per direction of Engineer in charge (Make of wire Finolex / L&T / Anchor / Havels / V-Guard / Greatwhite / HPL )(Make- legrand Myrius antibacterial /SchneiderLIVIA antibacterial )Separate point-
37On Existing board-
38S/F of metal Box of 180mm x100 X 60 mm nominal size of surface or in cress with suitable size of phenolic laminated sheet cover infront including providing and fixing of 5 pin,15/16 AmpModular socket out letand 15/16 AmpModular switch ISI marked connection painting etc as required complete in all respect as per direction of Engineer in charge (Make- legrand Myrius antibacterial /SchneiderLIVIA antibacterial )
39Recessed Extra leadSub-main wiring for light and fan point in 2x1.5mm2FR PVC insulated single core multistrand copper conductor of ISI Marked confirming to IS-694/1990 in 20mm dia nonmetalic heavy duty flexible conduct 1.6 sqmm thick along with 1x1.5 sqmm FR PVC insulated single core multistrand copper conductor as earth wire as required complete in all respect as per direction of Engineer in charge (Make of wire Finolex / L&T / Anchor / Havels / V-Guard / Greatwhite / HPL / MESCAB)2x1.5 sqmm +1x1.5 sqmm1100 Volts confirming to IS 694/1990
40Recessed wiring to Sub-main in 2x2.5 sqmm FR PVCinsulated single core multistrand copper conductor of ISI marked confirming to IS 694/1990 in 20mmdia non metalic heavy duty flexible conduct 1.6mm thick along with 1x1.5sqmm FR PVC insulated single core multistrand copper conductor as earth wire as required complete in all respect as per direction of Engineer in charge(Make of wire Finolex / L&T / Anchor / Havels / V-Guard / Greatwhite / HPL / MESCAB) (MCB DB box to swtich board) 2x2.5 sqmm +1x1.5 sqmm1100 Volts confirming to IS 694/1990
41Recessed wiring to Sub-main in 2x4 sqmm FR PVCinsulated single core multistrand copper conductor of ISI marked confirming to IS 694/1990 in 20mmdia non metalic heavy duty flexible conduct 1.6mm thick along with 1x1.5sqmm FR PVC insulated single core multistrand copper conductor as earth wire as required complete in all respect as per direction of Engineer in charge(Make of wire Finolex / L&T / Anchor / Havels / V-Guard / Greatwhite / HPL / MESCAB)(Mainswtich/Busbar to MCB DB box) 2x4 sq mm+1x1.5 sqmm 1100 Volts confirming to IS 694/1990
42Recessed wiring to Sub-main in 2x6 sqmm FR PVCinsulated single core multistrand copper conductor of ISI marked confirming to IS 694/1990 in 20mmdia non metalic heavy duty flexible conduct 1.6mm thick along with 1x2.5sqmm FR PVC insulated single core multistrand copper conductor as earth wire as required complete in all respect as per direction of Engineer in charge(Make of wire Finolex / L&T / Anchor / Havels / V-Guard / polycab / HPL / MESCAB/KEI)(Mainswtich/Busbar to MCB DB box)2x6 sq mm+1x2.5 sqmm 1100 Volts confirming to IS 694/1990
43Supply of 16mmsq. mm 4 Core 1.1KV Grade ISI Marked pvc insulated pvc sheathed XLPE Alluminium Armored power Cable (Make-Polycab /Havells/Finolex/)
44Laying of up to 150mmsq. mm 3 1/2 Core 1.1KV Grade ISI Marked pvc insulated pvc sheathed XLPE Alluminium Armored power Cable
45S/F of 4 way TPNMCB DB on existgsurface / wall mounting with all connection complete in all respect as per direction of engineer incharge (Make : Schneider (ACTI 9 ) /legrand/siemens)
46Supply and fixing of SP 6-32 A rating 240 V "C" series miniature circuit breaker suitable for lighting and other loadsin the existing MCB DB ISI marked complete with connections testing and commissioning completein all respect as per direction of Engineer in charge(Make : Schneider (ACTI 9 ) /legrand/siemens)
47Supply and fixing of FP 6-32 A rating 240 /415V "C" series miniature circuit breaker suitable for lighting and other loadsin the existing MCB DB ISI marked complete with connections testing and commissioning completein all respect as per direction of Engineer in charge(Make : Schneider (ACTI 9 ) /legrand/siemens)
48Supply and fixing of FP 63 A rating 240 /415V "C" series miniature circuit breaker suitable for lighting and other loadsin the existing MCB DB ISI marked complete with connections testing and commissioning completein all respect as per direction of Engineer in charge(Make : Schneider (ACTI 9 ) /legrand/siemens)
49Supply and fixing of 4 pole MCCB 63-100A,Ics = 100% Icu, 16 KA breaking capacity, adjustableThermal,fixedmagnetic type in existing cubicle panel board including drilling holes in cubcle panel, making connections, etc. as required completein all respect as per direction of Engineer in charge (Make : Schneider (ACTI 9 ) /legrand/siemens)
50S/F of 100 A cubical panel boardmade of 16 SWG C.R sheet with powder coated with provision of following items with fabrication erection testing & comissioning of total enclosed panel board of size not less than 18"x24"x10" with copper busbar of 100A, 415V 4strip & internal connection & provision for termination of incomming & out going cable , earthing etc, complete with supply & fixing of following switch gears.technical specification:
51Supplyof 48 inch / 1200mm A.C. Celling Fan High speed metalic colour ISI Marked with all connection complete in all respect as per direction of Engineer in charge (Make:- Havells/ Almonard /Orient/Khaitan/Crompton/V-guard)
52Fixing of above mentioned ceiling fan
53S/F of step type electronic Fan RegulatorISI Marked with all connection completein all respect as per direction of Engineer in charge(Make- legrand Myrius antibacterial /SchneiderLIVIA antibacterial )
54S/F of 12 inchHeavy duty (Metalic Colour)Exahust Fan with wall cutting, S/F of proper size of hume pipe, concreating, plastaring, painting with all connection testing and commissioning complete in all respect as per direction of Engineer in charge(Make:- Havells/ Almonard /Orient/Khaitan/Crompton/V-guard)
55Supply and fixing of 20watt,CW/WW 5700K,1800 Lumen led Aluminium Housing batten on wall ,making connections, etc. as required completein all respect as per direction of Engineer in charge (Make : Panasonic/ Great white/ Orient/ wipro/ Havells/Phillips)(2Years Warranty)
56S/F of Street light 45Watts new generation energy saving & environmental friendly long life versatile pressure die-cast alluminium IP66 roadway luminaire with high power LED as light source with acrylic cover (Make : Philips/Panasonic/Orient / Havells/great white/wipro)
57Fixing of Street light with G.I bracket and pipe
58S/F of Earthing with medium class 40mm 3Mtr. Long ISI markedGI Earth pipe including accessories such as funnel GI nut, Bolt, washer , hinged cover plate with looking arrangement, 40mm to 20GI rediusor 5nos 20mm dia holes on GI pipe required charpol salt, Excavation of earth brick work in cement mortar complete in all respect as per specification of SR 2011 and asper Direction of Engineer-in -Chage
59Supply and laying of 6 swggi wire in recess/surface
60Supply and fixing of Surface mounting Industrial sockets & Straight plugs ( 380/415 VA, 16 A 3P+N+E) IP 44 making connections, etc. as required completein all respect as per direction of Engineer in charge (Make : Schneider (ACTI 9 ) /legrand/siemens/hager)
61P.H Works: Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor pvc pipesconforming to ASTM-D-1785/89 (Sch-80) and pipe fittings of the following nominal bore with clamps including making good the wall, ceilingand floor all complete as per specification and direction of the Engineer in charge. In ground floor 25mm dia UPVC ASTM pipe
6240mm dia UPVC ASTM pipe
6350mm dia UPVC ASTM pipe
64Supplying all materials, labour, T&P and cutting holes through existing brick work including making good the damages in cement mortar (1:4) for taking GI pipes and fittings/ PVC pipes and fittings etc all complete as per PH specification and direction of the Engineer in charge. 250mmthick wall In Ground Floor
65Supplying allmaterials, labour, T&P and cutting grooves in pucca floors and walls for takingGI/ PVC pipes and making good the damages as per the direction of the Engineer in charge. In ground floor
66Supplying all materials, labour, T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all jointing materials complete as per specification and direction of the Engineer in charge. 15 mm dia CP L.B. Bib cock (Plaza/Amber/Aquatic)
6715mm dia CP angle stop cock (Plaza/Amber/Aquatic)
6815mm dia CP flange
6915mm Cp extention piece
70125mmdia C.P.grating
7125mm brass full way valve
7240mm brass full way valve
7350mm brass full way valve
7425mm brass ball cock with ball
75CP soap holder
76Supplying all materials,labour,T&P and fixing Rotational moulded polyethylene cylindrical vertical water storage tanks including cutting holes through the tank and fixing mild steel tubes and fittings and providing extra sockets and jam nuts, fixing ball valve etc, including hoisting upto a height of 5 metres above ground level and placing the tank to the required position and providing 1st class K.B brickwork in cement mortar (1:6) of 0.46m height in staging and in circular protection wall to support the tank, 12mm thick cement plaster (1:6) over brickwork, R.C.C slab of size 1.60mx1.60m and 0.10m thick, R.C.C beam of 0.25mx0.30m and 3.18m average length in cement concrete(1:2:4) using 12mm size h.g chips including centering and shuttering,watering, curing, conveyance of all materials to worksite etc all complete as per specification and direction of the Engineer in charge 1000litre capacity water storage tanks(Sintex make) (first Floor)
77Supplying all materials, labour, T&P and fixing wash basins with hole for pillar taps with cast iron or M S brackets painted white including cutting holes in walls and making good the damages with supply of wooden plugs, screws and cement etc, fixing pedestal for wash basin recessed at the back for the reception of pipes and fittings, fixing PVC waste pipe of 32mm nominal diameter for wash basin including brass check nut complete, fixing pillar taps(Plaza make) capstan head screw down high pressure lettered ‘Hot’ and ‘Cold’ with long screws, shanks and back nuts of 15mm dia nominal bore, fixing 15mm dia PVC inlet connection pipe and making connection with pillar cocks and supply mains for wash basin, fixing 32mm dia CP brass waste,etc all complete as per specification and direction of the Engineer in charge 550mmx400mm size wash hand basin (Parryware/Cera/ Nycer Make)
78Supplying all materials, labour, T&P and fixing mirror of superior glass mounted on 6mm thick A.C sheet or plywood sheet and fixed to wooden plugs with CP screws and washers complete as per specification an direction of the Engineer in charge 600mmx450mm size B.E mirror
79Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricantby non-heat application method/as per manufacturer’s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge 110mm dia U-PVC SWR pipes(Supreme/Ashirvad)
80110mm U-PVC door bend
81110mm U-PVC plain bend
82Supplying all materials, labour, T&P and providing cement concrete (1:2:4) with 12mm size hard broken granite chips including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge In ground floor
83Supplying all materials, labour, T&P and providing 12mm thick cement plaster (1:4) on brickwork including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge 12mm thick CP (1:4) on bw- In Gf(inside/outside)
84Supplying all materials, labour, T&P and providing ceramic tiles in floors, treads and landing on 25mm thick bed of cement mortar 1:1 (1 cement:1 sand) joined with neat cement slurry mixed with pigment to match the shades of the tiles etc complete as per direction of the Engineer in charge. (Ceramic floor tiles of size 30cm x 30cm to be pre-approved by the Engineer in charge) Ground floor
85Supplying all materials, labour, T&P and fixing porcelain glazed tiles in dados skirting on 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigments to match the shades of the tiles etc. complete as per direction of the Engineer in charge. (Ceramic wall tiles of size 30cmx45cm plain / printed series to be pre-approved by the Engineer in charge) In ground floor
86Supplying all materials, labour, T&P and constructing soakway pit of the following size with precast RCC rings joined loose, gravel backing in the rear of well steining, precast RCC cover slab in cement concrete (1:1.5:3) using 12mm size hg chips fitted with iron lifting handles including cutting hole in the rings for inlet pipe,earthwork in open well excavation in all kinds of soil and refilling of cavity around the pit & painting the iron works, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge RCC rings soakway pit 1.22m dia x 2.10m deep
87Supplying all materials, labour, T&P and laying in trenches (to level or slope) unplasticized PVC pipes conforming to IS: 4985/2000 of the following outside dia for class–3(0.60mpa) including jointing with supply of approved solvent cement by non-heat application method/as per manufacturer’s specification, providing and laying in trench cement concrete (1:4:8) with 40mm size hard granite metal in the Type C-1 standard bedding surrounding or encasingincluding concrete for bedding and curing etc all complete as per PH specification and direction of the Engineer in charge. 110mm dia u-pvc pipe alround concrete
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail