Tender For Repair And Maint Of Dg Set, Pump Motor, Water Supply Lines And Connected Works For Aor Of Hq 13 Sect Under Age (I) Cif (R), Udhampur-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Repair And Maint Of Dg Set, Pump Motor, Water Supply Lines And Connected Works For Aor Of Hq 13 Sect Under Age (I) Cif (R). Submission Date for this Tender is 22-07-2023. Diesel Generators Tenders in Udhampur Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

38306540
Corrigendum : Tender For Repair And Maint Of Dg Set, Pump Motor, Water Supply Lines And Connected Works For Aor Of Hq 13 Sect Under Age (I) Cif (R)
Open Tender
Indian
Jammu And Kashmir
Udhampur
22-07-2023

Tender Details

Repair And Maint Of Dg Set, Pump Motor, Water Supply Lines And Connected Works For Aor Of Hq 13 Sect Under Age ( I ) Cif ( R )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 15-Jul-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 22-07-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 16500.0 /-
Tender Value
INR 8.25 Lakhs /-

BOQ Items

Name of Work: REPAIR AND MAINT OF DG SET, PUMP MOTOR, WATER SUPPLY LINES AND CONNECTED WORKS FOR AOR OF HQ 13 SECT UNDER AGE (I) CIF (R)
Sl. No. Item Description
1Supply, Laying, jointing & testingin trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 16 sqmm 4 core with all fixing & connecting accessories including taking down old unserviceable cable. NOTE :- Excavation and earth work shall be measured and paid separatly
2All as per Item No 1 here-in-before but35 sqmm 3.5 core.
3All as per Item No 1 here-in-before but50 sqmm 3.5 core.
4All as per Item No 1 here-in-before but95 sqmm 3.5 core.
5All as per Item No 1 here-in-before but120 sqmm 3.5 core.
6Material and labour in replacement of alluminium cable thimbles of size 120 Sqmm UG Cable including complete connection and crimping.
7All as per Item No.6 above but 95 Sqmm.
8All as per Item No.6 above but 50 Sqmm.
9All as per Item No.6 above but 35 Sqmm.
10All as per Item No.6 above but 25 Sqmm.
11Supply and fix in replacement Off load change over switch 200 amps 415 volts 4 pole 50 Hz in sheet metal enclosure with out side handel operated complete all as directed by Engr In Charge.
12Supply and fix in replacement On load change over switch 100 amps 415 volts 4 pole 50 Hz open execution type with rotary type handel operated complete all as directed by Engr In Charge.
13Supply and fix in replacement MCCB 4 pole adjustable type 250 amps ruptering capacity 36 KA for 415 volts complete as directed by Engr In Charge.
14Supply and fix in replacement MCCB 4 pole adjustable type 200 amps ruptering capacity 36 KA for 415 volts complete as directed by Engr In Charge.
15Supply and fix in replacement MCCB 4 pole adjustable type 160 amps ruptering capacity 36 KA for 415 volts complete as directed by Engr In Charge.
16Supply and fix in replacement MCCB 4 pole adjustable type 100 amps ruptering capacity 36 KA for 415 volts complete as directed by Engr In Charge.
17Dismantling and taking out self starter assembly suitable for 62.5 KVA DG Set and replacement of wornout spare parts like field coil, armature assembly, solenoid assembly, corbon brush, corbon brush assembly, clutch plate assembly and bushes including servising and refixing to engine complete all as specified.
18Supply and fix in replacement stop solenoid 12V 10 amps single coil 75mm dia cat part No - 02.477.01.0.00
19Supply and fix replacement generator control unit KG541 level-0 cat part No - D8.048.07.0.00
20Dismantling and taking out battery charging alternater assembly suitable for 62.5 KVA DG Set and replacement of wornout spare parts like field coil, rotor assembly, carbon brush, rectifier assembly and bushes etc including servisingand refixing complete all as specified.
21Supply and fix replacement exhaust fan (450mm) with connector cat part No -D8.079.26.0.00
22Dismantling and taking out fuel injector pump assembly suitable for 62.5 KVA DG Set and complete overhauling of FIP including replacement of unserviceable parts like rebuild overhauling kit, rebuild seal kit, fuel injector "O" rings, OEM gaskets, spring gasket injector, valve bearing etc complete all as specified.
23Taking down radiator from the engine of 62.50 KVA DG set and refixing after cleaning washing and soldering to leaking water tubes including 2 ltrs of coolant complete
24Taking out Turbocharger of 62.50 KVA DG and replacement of Compressor Housing,Compressor Wheels,Turbine housing,Turbine Wheel,Wastegate Acuator with clamps,setting, caleberation and testing complete
25Repair, servicing and comprehensive maintenance ofDG Sets of any make of the following capacities incl replacement of defective /burn out parts by new parts such as filters,gaskets,V belts,Engine oil , rubber hoses,cleaning of alternator by vacuum cleaner and greasing of bearing with cother connected work for the cap62.5 kVA Make : Kirloskar/cummins/Mahindra Powerol complete all as specified and directed by Engr-in-charge. Note: Labour charge for :--- (ii) Periodical routine maintenance to be carried out as per the periodicity as under :- (a) The cost of fixing of all components/parts and trasportation of DG sets spare parts from site to workshop and vice versa shall be deemed to be included in the unit rates. (b) Cost of oiling, greasing , tightening of nut, bolts & minor extra are included in the unit rate quoted by the contractor. NOTE: Supply only of Spare parts required for repair/maint will be measured & paid separately under relavent items.
26All as per Srl Item No 25 but of cap30 kVA of any Make & type
27All as per Srl Item No 25 but of cap10-15 kVA of any Make& Type
28Supply only air filter element Suitable for Kirloskar 4R1040T model / Mahindra Powerol 62.5 kVA capacity
29Supply only air filter element Suitable for Kirloskar/ Mahindra Powerol 30 kVA capacity
30Supply only air filter element Suitable for Kirloskar/ Mahindra Powerol 10-15 kVA capacity
31Supply only Fuelfilter element Suitable for Kirloskar 4R1040T model / Mahindra Powerol 62.5 kVA capacity
32Supply only Fuelfilter element Suitable for Kirloskar/ Mahindra Powerol 30 kVA capacity
33Supply only Fuelfilter element Suitable for Kirloskar/ Mahindra Powerol 10-15 kVA capacity
34Supply only Lub oilfilter element Suitable for Kirloskar 4R1040T model / Mahindra Powerol 62.5 kVA capacity
35Supply only Lub oilfilter element Suitable for Kirloskar / Mahindra Powerol 30 kVA capacity
36Supply only Lub oilfilter element Suitable for Kirloskar/ Mahindra Powerol 10-15 kVA capacity
37Supply and fix in replacement banded cogged belt (2JAX51-LP-1326) cat part No - 06.032.03.0.00
38Supply and fix in replacement V belt (A-47) 1227 length cat part No - 04.140.01.0.00
39Supply and fix in replacement fuel pipe (7.5, 14x14B, 700 PB) cat part No - 34.151.04.0.00
40Supply and fix in replacement silencer assembly cat part No - 48.318.10.0.00
41Supply and fix in replacement rubber hose for air intake cat part No - 48.464.02.0.00
42Supply and fix in replacement Kirloskar green AVR for alternator 62.5 KVA DG set (Model: TAVR-10/TAVR-20/TAVR-14) cat part No - 2H.811.32.0.00
43Supply & pouring in sump/topping up of Engine oil of grade 15W-40/20W-50 in engine or replacement of EngineMake - Servo/Castrol/IOCL/HPCL
44Material and labour in replacement coolant for radiator of any make any type DG set at various loactions all as directed by Engr-in-charge
45Disconnecting incoming / outgoing cable connection from alternator of 63/62.5 kVA DG set and taking out from DG set room checking carefully and transporting to auth workshop for repair and rewinding of alternator dismentling into parts and cutting the burnt/damage copper winding wire from alternator / stator cleaning slots and rewinding the stator/alternator with super enamelled copper winding wire of existing gauge & size and insulation paper etc complete varnishing of rewinded alternator replacement of carbon brush set bearing set etc complete and transporting the alternator to DG set room coupling with DG set and testing complete include water load test all as specified and directed by Engr-in-charge. NOTE: All neccessary T&P for dismantling,transporting and installation cost is deemed in this work
46Diconnecting the input and output electric supply from automatic voltage stabiliser of capacity (100 KVA to 200 KVA) and taking out from Palma and shifting to civil workshop Rajouri (about 35 KMs away from Palma) for carrying out repair works. Note:- The rate quoted by the contractor shall incude the rate for T&P, transportation and necessary men power required during loading and unloading.
47Opening the top cover of votage stabiliser taking out the complete servo stabiliser oil and keep it for reuse and taking out dimmer assembly and transformer assembly for checking the defects.
48Supply and fix in replacement Dimmerstate unit of capacity 100 KVA to 200 KVA servo voltage stabilizer 28 amps of Make Volina complete all as specified and directed.
49Supply and fix in replacement main transformer of capacity 100 KVA to 200 KVA servo voltage stabilizer of make Volina complete all as specified and directed.
50Supply and fixing in replacement Electronic circuit board (Printed circuit board) for controlling of synchronous motor of torque 10 KG and auto/manual under voltage high voltage operation.
51Supply and fix in replacement PCB holder.
52Supply and fixing in replacement trigger transformer.
53Supply and fixing in replacement panel lamps alongwith connecting leads for over voltage under voltage etc.
54Supply and fix in replacement carbon brush.
55Supply and fix in replacement digital volt meter 72 x 72mm.
56supply and fixing in replacement servo motor 10 KG torque.
57Supply and fixing in replacement RC network for 10 KG servo motor
58Supply and fix in replacement auto manual switch.
59Material and labour for filling in with new transformer oil for top up to voltage stabilizer having low viscosity of approved make as per IS 355 of 1992 and di-electric strength 40 KV(after filtration) complete all as specified and directed by Engineer-in-Charge. Make : Savita/Castrol
60Taking out submersible pump and motor of capacity 5 HP from the tube well lowered at the depth of 90 to 110 mtr from the ground level including taking out GI flanged column pipes 40mm bore of 03 metre length each (column pipe are provided with flanged joints at every 03 metre length) and one Nos submersible cable 3 core of any size incl disconnecting electrically and delivery out let pipe and lowering after complete repair and maint of the same complete as in order to start the submersible pump complete all as directed by Engr-in-charge
61Rewinding submersible motor 5 HP of03 Phase, 415 voltswith PVC insulated solid copper conductor (wire) superior quality of approved make, size & number of wire as per existing complete including replacement of worn out cable connectionsincluding testing and commissioningof motor after rewinding complete all as specified.Make of Motor : KSB
62Supply only the following spare parts for submersible motor as per existing make and size :- Make of motor KSB
63(a) GM Bearing Bush
64(b) Rotor sleeve
65(c) Water seal
66(d) Thrust bearing
67(e) Housing upper
68(f) Housing lower
69(g) Cable seal
70(h) Thrust plate
71(j) Coupling S/S
72(k) Key for coupling
73(l) LNK bolt S/S
74(m) Revolving disc
75(n)Seal bush
76(p) Sand guard
77Opening and reassembling of submersible pump of capacity 5 HP and replacement of the worn out spare parts as mentioned under respective item no 64 here in after. Make of pump: KSB
78Supply only the following spare parts forsubmersible pump as per existing make and size :- Make of pump KSB
79(a) Stage bowl
80(b) Impellers
81(c) Pump shaft S/S (single stage)
82(d) Hook bolt (Upper & lower)
83(e) GM neck ring
84(f)Key for pump shaft (Each stage)
85(g) Distance sleeve
86(h) D.O.L Bush
87(j) Sand guard
88(k) Impeller key
89(l) Inter ring
90(m) Guide bush
91(n) Suction chamber
92(p) D.O.L. Sleeve
93Dismantling of existing defective induction motor of thesize 5 HP capacity any makefrom the foundation, disconnecting the electric connection, coupling pulley, and taking out to work shop cutting down and removing existing burnt out copper windings, cleaning of slots and rewinding with super enamelled solidcopper conductor ( winding wire) complete including varnishing, drying, ovening, overhauling, greasing and fixing in the same position, making necessary electric connection and testing of induction motor complete all as specified and as directed by Engineer-in-Charge.
94Excavation in trenches in any type of soil not exc. 1.5 metre wide and not exc. 1.5 metre in depth and getting out for taking up / layingunder ground electric cable or for pole etc complete all as specified and as directed.
95Returning, filling in, including spreading levelling watering and well ramming in layers not exceeding 25 cms in depth in soft/loose soils complete all as specified and as directed.
96Removing surplus soils to a distance not exceeding 50 mtr and depositing where directed at a level not exc. 1.5 mtr above the starting point all complete as specified and as directed.
97Sand cushioning with fine sand to under ground cables in trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable as specified in clause 19.75 of SSR Part-I, complete all as specified and directed by Engr-in-Charge.
98Brick clay (old size brick )with width equal to length of brick as mechanical protection to cables with well burnt sub class ‘B’ (old size) bricks laid dry flat all as directed.
99Supply & Fix in replacement Single phase submersible pump set controller /starter for upto 5 HP submersible pump set with suitable cap starting & running capacitors complete Make: L&T Model MU-G6 DOLTechnocommetially ABB/kirloskar
100M&L for dismentalling all unserviceable part by opening complete Engineand replacing of new following Parts as per OEM, servicing & testing of DG set by taking out of FIP to workshop for repair and caliberation replacing following parts of 62.5 KVA DG Setincluding reassembling and testing DGcomplete all as specified and directed. Make of DG set : Kirloskar and Model No. HA694. NOTE: Supply only of Spare parts required for repair/maint will be measured & paid separately under relavent items.
101Supply only the following spare parts for 62.5 KVA DG Set
102(i)Supply only C/R Bearing Cat part No. M.552.4.00.003 as per sample Make : Kirloskar
103(ii)Supply only Piston Cat Part No. T4.202.08.0. PRMake : Kirloskar as per sample
104(iii) Supply only Piston Liner Cat part No. T1.058.20.0.PR as per sample Make : Kirloskar
105(iv)Supply only Piston Ring T4.202.10.0. PRMake : Kirloskar as per sample
106(v)Supply only Head Gasket cat Part No. T4.030.09.0.00 as per sample Make : Kirloskar
107(vi) Supply only Head Repair as per sample Make : Kirloskar
108(vii)Supply only Head Valve Cat Part No. T1.057.03.9.00 and T1.057.05.0.00 as per sample Make : Kirloskar
109(viii)Supply only Head Seal cat part No. T4.033 as per sample Make : Kirloskar
110(ix)Supply only Set of Joint Cat Part No. T4.087.24 as per sample Make : Kirloskar
111(x)Supply only Turbo Charger cat Part No. T4.187.02.0.PR as per sample Make : Kirloskar
112(xi)FIP Repair with replacement of following parts :-
113(xii)Supply only Injector cat part No. 4H.1429.18.0.PR as per sample Make : Kirloskar
114(xiii)Supply only Set of Ring for FIP cat part No. 4H.373.02.0.00 as per sample Make : Kirloskar
115(xiii)Supply only Pump shaft for FIP as per sample Make : Kirloskar
116(xiv) Calibrarion of Fuel injection pump complete including the following parts all as specified and directed :-
117(a) S & F Benjo bolts for 62.5 kVA DG Set complete all as specified and directed
118(b) S & F disel Hose pipe for 62.5 kVA DG Set complete all as specified and directed
119Supply and fix in replacement exhaust fan, steel body heavy duty 1450 RPM AC single Phase. 230V of size 300mm sweep with, blades, frame and louvers suitable for DG set.
120Supply and fix in replacement of battery for DG set 12 V 150 AH and 1 Pair connection lead copper 1.0 Mtr length 25 sqmm copper wire multi stranded with brass terminals
121Deduction to be made from BOQ for schedule of credit (Sch "A" Part - II) Amount of ? 22,497.00during AOC Note:- Tenderers shall not quote for this Schedule
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy