Tender For Ca No. Cwe Sgnr Token-10 Of 2023-24 Provn Of Smart Meter And Server With Backup Including Allied Work For Jcos/Or Md Accn At Lalgarh Jattan Military, Ganganagar-Rajasthan

Military Engineer Services-MES has published Tender For Ca No. Cwe Sgnr Token-10 Of 2023-24 Provn Of Smart Meter And Server With Backup Including Allied Work For Jcos/Or Md Accn At Lalgarh Jattan Military. Submission Date for this Tender is 19-07-2023. Energy Meter Tenders in Ganganagar Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

38286820
Corrigendum : Tender For Ca No. Cwe Sgnr Token-10 Of 2023-24 Provn Of Smart Meter And Server With Backup Including Allied Work For Jcos/Or Md Accn At Lalgarh Jattan Military
Open Tender
Indian
Rajasthan
Ganganagar
19-07-2023

Tender Details

Ca No. Cwe Sgnr Token-10 Of 2023-24 Provn Of Smart Meter And Server With Backup Including Allied Work For Jcos / Or Md Accn At Lalgarh Jattan Military

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 12-Jul-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 19-07-2023

Key Value

Document Fees
INR 1000 /-
EMD
INR 124570.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: PROVN OF SMART METER AND SERVER WITH BACKUP INCLUDING ALLIED WORK FOR JCOs/OR MD ACCN AT LALGARH JATTAN MILITARY
Sl. No. Item Description
1Supply and Installation ofSmart Single Phase Meter with the following specifications: (i)AC Single Phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt 865-867 MHz Radio Frequency communication facility with self healing Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. (ii) Meter Should support the following data : 15 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, 15 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand. (iii) Meter should have connect / disconnect functionality operable from prepaid billing software. (iv) The meter should support open communication protocol DLMSwith the software MAKE: Secure, L&T, HPL Note: (a) The contractor would be responsible from removing the existing meter, noting down the reading and depositing it with the MES. (b) It would be possible to run the meter in both prepaid and postpaid mode (c) The meters would carry 5 year warranty. (d) The meter OEM would share meter Password, authentication details, API, protocols, HLS, LLS password etc. for integration with third party system. Alternatively, the meter OEM would share the web services for the head end integration.
2Supply and Installation of IP-67/IP-65 protection, Data Concentrator Units (DCU) compatible for remote Automatic Metering Infrastructure (AMI) solution and capable of communicating with the smart energy Meter in the corresponding frequency band and with the data server through GPRS/internet. It would have internal memory to store data of at least 200 modules. It would have inbuilt battery back-up. It would have IP-67 protection. It would support auto discovery of the meters and self healing mechanism for the breaks in the RF network complete all as specified and directed by engineer-in-charge. Make: Secure, L&T, HPL Note: Protection Rating of DCU will be decided by GE.
3Supply and installaton of single phase smart meter as repeater complete all as specified and directed by engineer-in-charge. Make: Secure, L&T, HPL
4Supply and installation of polycarbonate boxes for the single phase smart meters as required including wiring complete all as specified and directed by engineer-in-charge.
5Supply and Configuration of the Web based Software with following modules: (i) Meter Data Management Module The meter data management module would be responsible for collecting the data from the concentrator and make the data available to the billing system.The meter data management system would capture and provide the following data: (a) 15/30 min instantaneous data from all the meters for seven parameters (phase wise as applicable)– Cumulative Energy, Cumulative Apparent Energy (as applicable), Power, Current, Voltage, Power Factor and Frequency (b) Monthly billing survey data for cum energy and max demand (ii) Postpaid /Prepaid Billing Module The billing module would collect the data from the meter data management module, calculate the energy consumption, calculate billing determinant and make energy data / billing data available to admin and end users. The billing module would include functionalities for tariff setup, bill format setup, bill adjustment, occupation billing and vacation billing. It would allow postpaid and prepaid functionality as required.
6(iii) Occupation and Vacation Module The system would support occupation / vacation and billing reports. the software would be collecting data from DCU. The software would provide access to staff as well as the occupant for the data. (iv) Web site: There would be a dedicated website for the AGE and BSO team to view all the data and information. The designated users in MES would have the admin access to the application. The MES staff would also have the access of the key information on an android mobiles app (for admin use). (v) Customer Portal The system would include a customer portal for the resident /occupant to log in and view their own energy / billing data. There would be android and iOS mobile apps for the user to monitor its own data and balance on regular basis. (vi) Energy Accounting Module The system would include features of energy accounting. The system would be able to account for total energy block wise, facility wise and would also allow calculations of unaccounted energy in case total energy meter is also available. (vii) Communication Module The system would provide communication of energy data and bills via print, email and sms methods. (viii) Meter Master Data The system would support meter master data repository. The system would support meter replacement process. (ix) Excel Export The system would support export of metering and billing data in excel format.
7(x)Customer Care Module - The software would include a customer care module where the user would be log in any complaints. The service provider would monitor the complaints and carry out the necessary activities for the complaints resolution. (xi) Meter Installation Module - The software would include an app based meter installation module where the meter installation or changes can be captured on the app itself and the readings may be demonstrated to the user if required on the app itself. (xii) Activities Communication - The software support communication of the various activities such as occupation, vacation, meter change. personal detail change etc. with the user as well as the department on email. Make: Innologix, Oracle, HPL, Secure Note: (a) The software would be either on hosted on MEITY (Ministry of Information Technology) approved GCC (Government Community Cloud) or on MES provided server. (b) The software would contain two year defect liability including all operating expenses such as GPRS charges, hosting charges etc. (c) The software can be scaled up to integrated with any IS16444 based meter provided the meter inetgration details and/ or headend integration details are made available.
8Comprehensive maintenance including operating costs after two years of defect liability period. They would include the following items: (a) Monthly sim charges for the DCU. The contractor would ensure supply of appropriate SIMs to ensure necessary single availability. The contractor would change the sim or sim provider as required. In case of network issues, the contractor would liaison with the telecom service providers for necessary resolution. (b) Recurring SMS charges. The SMS would be issued for the payments alerts, low balance alerts and disconnection / connection alerts. (c) Software AMC. This would include necessary upgradations in the software such as support to the chrome browser changes, android version changes , iOS version changes. These changes happen on frequent basis and the software would support all the changes.
9(d) Changes in the Government tariff structure. The government tariff structure changes may require software upgrade. The same would be included in the AMC scope of work. (e) Remote server admin support - Ensuring adequate database back up, upgradations in the operating system, anti virus updates, database upgrade etc. (f) Reports Development - The additional reports as needed for the success of the project would be developed (g) Software installation on any alternate / backup server if required (h) The communication network monitoring and support (i) Configuration of the repaired / replaced hardware in the system (j) Trouble shooting and necessary actions to run the system as required. (k) Software bug fixing as and when required
10Excavation in trenches, not exc. 1.50 mtr wide and not exc 1.50 mtr in depth and getting out in soft / loose soil for foundations complete all as specified and directed by Engineer - in -Charge.
11M & L for PCC (1:4:8) type D-2 ( using 40mmgraded crushed stone aggregate) as in foundation filling and mass concrete complete all as specified and directed by Engineer - in -Charge.
12M&L for formwork to chajjas, lintel beam, troughts and similar items including edges rough finish surface of concrete flat complete all as specified and directed by Engineer - in -Charge.
13M&L for formwork to soffits of suspended slabs such as roof slabs,floor slabs thickness n. exc. 200 mm(horizontal or sloping) in rough finish complete all as specified and directed by Engineer - in -Charge.
14M&L for fromwork to edges of concrete flats, treads breaks in floors, window cills, concrete railings, openings in concrete walls, floor and roofs n.exc 20cm wide and sides of RCC/PCC bands in walls, orizontal or sloping and similar work exc 10 cm but n.exc 20 cm wide, roughed finished surfaces of concrete complete all as specified and directed by Engineer - in -Charge.
15M & L for mild steel TMT bars 10 mm dia and over, cut to length, bent to shape required, including cranking, bending, hooking ends and binding with mild steel wire (annealed) not less than 0.90mm dia complete all as specified and directed by Engineer-in-charge.
16All as per item No 12 here-in-before but 5mm dia and over upto and including 10mm dia as in stirrups, spaces & binderscomplete all as specified and directed by Engineer-in-charge.
17M&L for RCC M-25 (Design mix)using 20 mm graded stone aggregate as inbeams, Chajjas, cantilevers, bressummers, lintel beam & ovr 1.5m span complete all as specified and directed by Engineer-in-Charge. Note: Reinforcement shall be measured and paid separately.
18M&L for RCC M-25 (Design mix) using 20 mm graded stone aggregate as in slab suppored on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the likecomplete all as specified and directed by Engineer-in-Charge. Note: Reinforcement shall be measured and paid separately.
19M&L for brick work withfly ash bricks bricks straight or curved on plan exceeding 6 mtr mean radius and built in cement mortar (1:6) complete all as specified and directed by Engineer-in-Charge.
20M&L for 40mm thick damp proof course in cement concrete 1:2:4, type B-0, 12.5 mm graded stone aggregate with WPC to horizontal or vertical surfaces including necessary formwork complete all as specfied and directed by Engr-in-Charge. Note :-Approved water proofing compound shall be measured and paid separately as supply only.
21Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25cm complete all as specified and directed by Engineer-in-Charge.
22Spreading and levelling in layers n.exc 25cm thick and well ramming including watering as required under floors complete all as specfied and directed by Engr-in-Charge. Note. Earth required for filling shall be used obtained from earth work.
23Removal of surplus soil obtained from excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge. .
24M&L for hard core of gauge n.exc 63mm, deposited, spread and levelled in layers n.exc 15cm thick watered and rammed to a true surface brocken stone or boulders (15cm compacted thickness) complete all as specified and directed by Engineer-in-charge.
25M&L for 75 mm thick PCC (1:3:6) type C-1 using 20 mm graded crushed stone aggregate as in plinth protection finished even and smooth without using extra cement with & including 10 mm wide, 30 mm deep joints at the rate of 3.00 mtr centre to centre and at every turning & filling the joints with bitumen & sand mixture complete all as specified and directed by Engineer-in-charge.
26M & L for 75mm thick PCC (1:4:8) type D-2 ( using 40mm graded crushed stone aggregate) as in sub base below floors complete all as specified and directed by Engineer - in -Charge.
27M & L for 25mm thick PCC (1:2:4), type B-0,using 12.5mm graded crushed stone aggregate as in floor complete all as specified and directed by Engineer - in -Charge.
28M&L for Machine cut kota stone slab flooring, 20-25mm thickover and including 20 mm thick screed bed in cement mortar (1:6)base laidand jointed with grey cement slurry mixed with pigment to match the shade of slab including rubbing and mirror polishing complete all as specified and directed by Engineer-in-charge.
29M & L for 20-25 mm thick machine cut kota stone slabs as in vertical surfces such as risers of steps laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing, mirror polishing and moulding edgesincluding over and 10mm thick rendering in CM (1:4) complete all as specified and directed by Engineer - in -Charge.
30M&L for 10mm thick rendering in CM (1:6) to brick/ concrete surfaces finishedeven & smooth without using extra cement complete all as specified and directed by Engineer-in-Charge.
31M&L for rendering 15 mm thick in cement mortar (1:4) onfair face of brick walls, finished even & smooth without using extra cement,complete all as specified and directed by Engineer - in -Charge. Note: WPC shall be measured and paid separately as supply only.
32M&L for rendering 5 mm thick in cement mortar (1:3) on concrete surfaces as in ceiling, finished even & smooth without using extra cementcomplete all as specified and directed by Engineer - in -Charge.
33Supply only liquid water proofing compound complete all as specified and as directed by the Engineer-in-Charge.
34M&L for preparation and applying three coats of white wash on newly plastered surface of ceiling complete all as specified and directed by Engineer - in -Charge.
35M&L for preparation andapplying two coats of oil bound distember over a coat of primer on newly plastered surface of wall paint over3mm thick thick wall care putty complete all as specified and directed by Engineer - in -Charge.
36M&L forpreparation ofnew plasteredandtreating with two coats of applyingweather proof exterior emulsion paint (Apex Ultima or equivalent) over a coat of primer over 3 mm thick wall care puttycomplete all as specified and directed by Engineer - in -Charge.
37Material and labour for water proofing treatment over 10mm thick screed bed in CM 1:3mixing of WPC in mortar inRCC slab by applying one coat of bituminous primer @ 0.25 Kg/Sqm and providing 3mm thick APP modified water proofing membrane weighting not less than 3.5 Kg/Sqm, reinforced with non woven polyster reinforcement mat weighing not less than 160 gm/Sqm, polyster core having softening point not less than 150 degree C, longitudinal tensile strength not less than 650 N/5CM, Tearing strength of 180N/5CM including two coat of solar reflective aluminium paint @ 0.15Kg/Sqm including cleaning the newly plastered surfaces of concrete/existing plastered vertical surfaces with wire brushes free from dust etc complete all as specified and directed by Engineer - in -Charge.
38M & L for cement concrete tiles 25cm x 25cm x 22mm thick, macine pressed; over cement screed base laid over cement screed base laid over and including15 mm thick screed bed incement mortar 1:6, set and jointed with grey cement slurry mixed with pigment and no pigmentin floors/roof, and cut and polished complete all as specified and directed by Engineer - in -Charge.
39S & F for Aluminium anodised (Powder coated) Three track sliding window frame with shutters (two glazed and one gauged shutter)including all necessary joining cleats, hold fast, rubber gasket, snap beading and locking arrangements fixed with screws to wall etc. complete andglazing with 5 mm thick tinted glass to aluminium frame work using rubber gasket and including stainless steel wire cloth of 0.36mm dia & average width of aperture 1.40mm with staple or suitable fillets wire mesh fitted with screws and washers etc with the following section of frame and shutter (A) Sections for frame. (i) Top and verticals 92 x 29.50 x 1.30 mm thick (ii) Bottom 92 x 29.50 x 1.20 mm thick. (B)Sections for shutter (i) "A" section 39 x 20 x 1.50 mm thick (ii)Interlock" section 39 x 20 x 1.50 mm thick (iii) "H" section 41 x 20 x 1.10 mm thick Make: Jindal or equivalent sections of Hindalco.
40S & F powder coatedaluminium door shutters, aluminium section weighing 0.55 kg/ m including necessary joining cleats, glazing clips, ruber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminum snap beading screws etc complete all as specified and directed by Engineer - in -Charge.
41M & L for door closer hydraulically regulated of aluminium cast type , designation No. 3, universal type, suitable for door shutters of 851 to 1000 mm in width and of weight between 61 to 80 kg and fixed other parts made of mild steel heavy duty and fixed complete all as specified and directed by Engineer - in -Charge.
42S & F 4 lever brass body mortice lock, vertical type, size 100 mm complete all as specified and directed by Engineer - in -Charge.
43M&L for 4.0 mm thick figured glass, ordinary quality and glazing with aluminium snap beading of any size in each panescomplete all as specified and directed by Engineer - in -Charge.
44Surface excavation n.exc. (not exceeding) 30 cm deep and averaging 15cm deep and getting out in soft/loose soil complete all as specified and directed by Engineer - in -Charge.
45M&L for 75 mm thick PCC (1:3:6) type C2 using 40mm graded stone aggregate as in sub base below floors complete all as specified and directed by Engineer - in -Charge.
46M&L for precast cement concrete (1:2:4) type B1 using 20mm graded stone aggregate as in kerb stones size 300mm x 300mm x 100mm with plain fair faces, including chamfers, weathering, throating etc setting in CM (1:4) complete all as specified and directed by Engineer - in -Charge.
47M&L for 60mm thick M-35 grade machine Machined pressed precast concrete interlocking paver block glossy with grey cementand pigment, any shape and size confirming to IS 15658-2006 over and including 25mm thick sand cushion complete all as specified and directed by Engineer - in -Charge.
48Supply, Installation and setup of Application server and backup server Dell PowerEdge Tower Server T550. The sever would be suitable for 5000 meters. The below specifications are indicative. The servers may be hosted at the locations provided by the department. • 3.5" Chassis with up to 8 Hard Drives (SAS/SATA), 1 CPU • CPUIntel® Xeon® Silver 4314 2.4G, 16C/32T, 10.4GT/s, 24M Cache, Turbo, HT (135W) DDR4-2666 • Memory -16GB RDIMM, 3200MT/s, Dual Rank • Hard Drive - 800GB SSD SAS ISE mixed use 12Gbps 512 2.5in HP AG Drive,3.5in HYB CARR, 3 DWPD • Standard Heat Sink for Less = 150W • Dual, Hot Plug, Non-Redundant Power Supply (2+0), 600W, Mixed Mode Make: Dell, HP, IBM Note: (1) The server cost would include two year charges for high speed 1 GBPS broadband connectionfor one locations. (2) the server cost would include suitable data switch,firewall,monitor.
49Supply and Installation of UPS for the server with the specification10 KVA, 230V suitable for INDIA Harsh Environment or Equivalent complete with joints to match complete all as specified and directed by Engineer-in-charge Make: APS, Emerson, Luminous
50Provision of high speed 1 GBPS broad bandfor the server after two years of defect liability period complete with joints to match complete all as specified and directed by Engineer-in-charge
51S & F Inverter along with tubular batteries having following specifications complete all as specified and directed by Engr-in-Charge:- (a) Capacity of 2KVA of inverter 1680 W, sine wave output. (b) Battery of 12 Volts, 150Ah tubular plates technology-2 Nos (c) High durability with sealed plastic housing (d) Comprehensive protection against short-circuit, reverse polarity, battery over charge, deep discharge etc. (e) Battery warranty of minimum 36 months (f) Intuitive display to easily understand staus of mains availability, battery status, etc. Make :Luminous , Model No : Cruze 2KVA, Battery-ILTT 18048N 150AH or techno-commercially or equivalent