Military Engineer Services-MES has published Tender For Repairs Replacement Maint Of External Electrification To Underground Cables Switch Gears Lt Panels Earthing Control Panels Service Connections And Etc At Residential Area Dsc Cpdc And Elsec Area Under Ge I Rnd Rci Hyderabad. Submission Date for this Tender is 20-07-2023. Electrification Work Tenders in hyderabad Telangana. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 06-Jul-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 13-07-2023 |
2 | 13-Jul-2023 | Date of extension | Date | 20-07-2023 |
Sl. No. | Item Description |
1 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour |
2 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
3 | MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
4 | MCCB 4pole, 400Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Outgoing) |
5 | MCCB 4pole, 250Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Outgoing) |
6 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -04 No (Outgoing) |
7 | Digital Ammeter 0 to 1000Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
8 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
9 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
10 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour |
11 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
12 | MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
13 | MCCB 4pole, 400Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Outgoing) |
14 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -04 No (Outgoing) |
15 | Digital Ammeter 0 to 1000Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
16 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
17 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
18 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour |
19 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
20 | MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
21 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -07 No (Outgoing) |
22 | Digital Ammeter 0 to 1000Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
23 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
24 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
25 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour |
26 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
27 | MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
28 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -08 No (Outgoing) |
29 | Digital Ammeter 0 to 1000 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
30 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
31 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
32 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour |
33 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
34 | MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
35 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -05 No (Outgoing) |
36 | Digital Ammeter 0 to 1000 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
37 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
38 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
39 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1000Amps rating for phase and neutral 4 strips with colour |
40 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
41 | MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Incoming) |
42 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -11 No (Outgoing) |
43 | Digital Ammeter 0 to 1000 Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
44 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
45 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
46 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 800Amps rating for phase and neutral 4 strips with colour |
47 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
48 | MCCB 4pole, 400Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (Outgoing) |
49 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -04 No (Outgoing) |
50 | Digital Ammeter 0 to 400Amps with selector switch- 01 No and 3 No of CT coil ratio 800:5 - 01 Set |
51 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
52 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
53 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 400Amps rating for phase and neutral 4 strips with colour |
54 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
55 | MCCB 4pole, 200Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No (incomming) |
56 | MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -03 No (Outgoing) |
57 | Timer 10KV - 01 No |
58 | Power Contactor ML-6 - 01No |
59 | Digital Ammeter 0 to 200Amps with selector switch - 01 Set |
60 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
61 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
62 | Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board outdoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 3mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 3000 Amps rating for phase and neutral 4 strips with colour |
63 | coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs, copper control wiring of required size for instruments and duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, necessary earthwork excavation and provision of PCC platform 100mm thick with PCC 1:2:4 type B-2 using 40mm graded stone aggregate one meter around the panel board, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate complete all as specified and directed including the followingaccessories :- |
64 | ACB 4pole, 2500 Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -01 No(incomming) |
65 | MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II -04 No (Outgoing) |
66 | Provision of bus bas of capacity 3000Amps with suitable duct for electrical connection between transformer and incommer of ACB up to 10 meter complete all as directed by eng-in-charge. |
67 | Digital Ammeter 0 to 3000 Amps with selector switch - 01 Set |
68 | Digital Voltmeter0-500Volts with selector switch, 7 position and 2A HRC fuses/MCBs - 1Set |
69 | Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set |
70 | M&L for replacement of Synthetic insulating mat of size 2m x 1m x 2.5 mm complete all as specified & directed by Engineer-in-charge. |
71 | M&L MS Chequeredplate of thickness 5 mm as per site requirement sizes to cover cable duct openings including repairing works to edges of Duct to place MS Chequered plate equally on the duct in the installations complete including taking out the broken PCC duct covers duct covers all as specified & directed by Engineer-in-charge. |
72 | Excavation in trenches not exceeding 1.5 Mtr wide and not exceeding 1.5 mtr depth for laying cable at andgetting out insoft/loosesoil all as specified and directed. |
73 | Returning, filling in soil including spreading, levelling, watering and well ramming in layers, not exceeding 25 cm thick all as specified and directed |
74 | Removing surplus soil to a distance not exceeding 50 Mtr and deposited at a level not exceeding 1.5 mtr above from the starting point all as specified |
75 | Supply and spreadsand in trenches for cable cushioning including watering and consolidationall as specifiedNote : For the purpose of payment punned thickness only will be measured. |
76 | Supplying and laying reinforced precast concrete cable cover, Class LV, Type I,flat,size 250 mm x 150mm x 40mm complete all as specified and directed. |
77 | Supplying, laying, jointing, testing and commissioning 1100 volts grade, 400 Sqmm 3.5 core LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 galvanized steel strip or wire armoured, heavy duty, electric cables, with multistranded aluminium conductor laid in trenches/ passing through pipe/duct/road crossing or fixed on poles, walls with suitable size clamps made out ofmild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., including taking down unserviceable cable complete all as specified and directed. Note : Earthwork Excavation, sand cushioning GI pipe and cable protection will be measured and paid separately. |
78 | All as per item No. 17 above 3.5 core 300 Sqmm |
79 | All as per item No. 17 above 3.5 core 240 Sqmm |
80 | All as per item No. 17 above 3.5 core 185 Sqmm |
81 | All as per item No. 17 above 3.5 core 150 Sqmm |
82 | All as per item No. 17 above3.5 core 120 Sqmm |
83 | All as per item No. 17 above 3.5 core 95 Sqmm |
84 | All as per item No. 17 above3.5 core 70 Sqmm |
85 | All as per item No. 17 above3.5 core 50 Sqmm |
86 | All as per item No. 17 above3.5 core 35 Sqmm |
87 | All as per item No. 17 above3.5 core 25 Sqmm |
88 | All as per item No. 17 above4 core 16 Sqmm |
89 | M&L for cutting of existing bituminous/PCC road or flooring/plinth protection laying of GI pipe in intersection for passing of LT XLPE cable including excavation in any type of soil returning filling in and making good top 30 cm of the trench by providing PCC 1:2:4 typ-e B1 using 20mm graded stone aggregate to flush with existing road surface complete all as directed. |
90 | Disconnecting electric supply and removing burnout/unserviceable cable jointing kit, supply and jointing new straight through heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 to 50 Sqmm for 1.1 KV (Earthed ) grade including tesitng complete all as specified and directed. |
91 | All as per item No 30above but cable of size 70 Sqmm to 120 Sqmm |
92 | All as per item No 30above but cable of size 150 Sqmm to 185 Sqmm |
93 | All as per item No 30above but cable of size 240 Sqmm to 300 Sqmm |
94 | All as per item No 30above but cable of size400 Sqmm |
95 | S&F in repair, sheet metal enclosuer with 63 amps 3 pole and neutral socket and plug top with MCCB complete all as specified and directed by eng-in-charge. |
96 | S&F in repair, sheet metal enclosuer with 32 amps 3 pole and neutral socket and plug top with MCCB complete all as specified and directed by eng-in-charge. |
97 | S&F in repairs, 3pole 63Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
98 | S&F in repairs, 3pole 125Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
99 | S&F in repairs, 4pole 160Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
100 | S&F in repairs, 3pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
101 | S&F in repairs, 4pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
102 | S&F in repairs, 3pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
103 | S&F in repairs, 4pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
104 | S&F in repairs, 4pole 400Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
105 | S&F in repairs, 4pole 630Amp MCCB, 50KA rupturing capacity at 415volt with adjustable thermal and magnetic settings,conform to IEC -60947-II/ IS-13947-II complete all as specified. |
106 | S&Fin repairs40mm dia GI pipe light grade fixed to walls/poles or laid in trenches, road crossing etc., for protection of underground cable/earth strip including sealing ends with hessian cloth impregnated with bituminous compound in ground and with teak wood bushes for ends fixed on walls/poles complete all as specified and directed. |
107 | S&Fin repairs50mm dia GI pipe light grade fixed to walls/poles or laid in trenches, road crossing etc., for protection of underground cable/earth strip including sealing ends with hessian cloth impregnated with bituminous compound in ground and with teak wood bushes for ends fixed on walls/poles complete all as specified and directed. |
108 | S&Fin repairs80mm dia GI pipe light grade fixed to walls/poles or laid in trenches, road crossing etc., for protection of underground cable/earth strip including sealing ends with hessian cloth impregnated with bituminous compound in ground and with teak wood bushes for ends fixed on walls/poles complete all as specified and directed. |