Military Engineer Services-MES has published Tender For Repair/Maint To Central Ac Plants Incld Maint Oflt Panels Ahu, Cooling Tower And Other Misc Works At Brd Af Stn Under Ge (Af) Tughlakabad. Submission Date for this Tender is 11-07-2023. Electrical Panel Tenders in Nagpur Maharashtra. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 26-Jun-2023 | Corrigendum1 | BOQ | 04-07-2023 |
2 | 04-Jul-2023 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 11-07-2023 |
Sl. No. | Item Description |
1 | M&L for checking the leakage in both low and high side of the system by feeding dry nitrogen to maintain adequate pressure in the system, plugging the leaks including S&F replacement of Teflon sealing of all refrigerant line valves like liquid lines valves/suction/ discharge valves of compressors, gland packages of all angle valves flaring of all connections framing welding etc complete for the following plants:- Note:1.Entire work is to be carried out by OEM i.e Bluestar for following plants. |
2 | AC plant of capacity 3 x 37.5 TR-Plant for RSBN. OEM- Bluestar |
3 | AC plant of capacity 3x15TR-Plant for Signal Section.OEM- Bluestar |
4 | AC plant of capacity 2 x 30 TR-Plant for ESCT. OEM-Bluestar |
5 | AC plant of Capacity 3x7.5 TR plant for PW-VI. OEM-Bluestar |
6 | AC plant of Capacity 1x7.5 TR plant for PW-III. OEM-Voltas |
7 | AC plant of Cap 2x5.5TR-Plant for New signal centre.OEM-Bluestar |
8 | AC plant of Capacity 3 x 26 TR plant for Spyder. OEM-Bluestar |
9 | Opening the upper sheet and side sheet of AHU’s of the following plants for access to cooling coil, including M&L for washing/cleaning of cooling coil externally with mild acid (or caustic soda hot water solution) followed by water jet including cleaning/washing of air filters and descaling of cooling coil of AHU,re-fixing and changing of necessary fitting, T&P for mounting and all connections framing welding as specified and directed.Note:1.Entire work is to be carried out by OEM i.e Bluestar for following plants. |
10 | AC plant of capacity 3x37.5 TR-Plant for RSBN. Make-Bluestar |
11 | AC plant of capacity 3x15 TR-Plant for Signal Sec. Make-Bluestar |
12 | AC plant of capacity 2x30 TR-Plant for ESCT. Make-Bluestar |
13 | AC plant of capacity 3x26 TR-Plant for spyder. Make-Bluestar |
14 | M&L for repair of AHU motor suitable for AC plants with following capacity by dismounting it from weather making unit of AHU, rewinding of 10/12.5HP motor same gauge with super enamelled copper wire including removing burnt winding cleaning of slotes sepration of rotor and startor making insulation to all joint all as specified and directed. |
15 | Supply only in replacement of following defective spare parts of AHU motor of any description/make and capacity 10/12.5 Hp and in any positioin :- |
16 | Replacement of ball bearing. |
17 | Replacement of cooling fan. |
18 | Replacement of capacitor of suitable mfd |
19 | Replacement of seal, bush |
20 | Turning and polishing of motor shaft including lathe work |
21 | M&L for fixing in replacement of gun metal gate valve butterfly type of 15 mm dia complete all as specified and directed. |
22 | 20 mm dia |
23 | 25 mm dia |
24 | M&L in replacement ofY type strainer CI bodyflanged endswith stainless stell strainer type as per existing |
25 | 65 mm dia. |
26 | 80 mm dia. |
27 | M&L for opening the outer sheets of package unit to access cooling coil, washing / cleaning of cooling coil externally with mild acid (or caustic soda hot water solution) followed by water jet including cleaning / washing of air filter and re-fixing, complete all as specified and directed . Note- Entire work is to be carried out by OEM only i.e Bluestar/Voltas/Fedders Lloyd |
28 | AC Plant of capacity 1 x 7.5 TR Plant for PW-III. OEM-Voltas |
29 | AC Plant of capacity 3 x 7.5 TR Plant for PW-VI. OEM- Bluestar |
30 | AC Plant of capacity 2 x 5.5 TR Plant for signal Sec. OEM- Bluestar |
31 | AC plant of Capacity 2x5.5TR-Plant for New signal centre.OEM-Bluestar |
32 | Cleaning of existing choked fins of existing cooling towers with chemical, removing the sludge and replace of defective fins,repair leakage base plate ,cleaning and two coat of epoxy paintsrequired complete all as specified and directed by Engr-in-Charge. |
33 | AC plant of capacity 3x37.5 TR-Plant for RSBN . Make-Bluestar |
34 | AC plant of capacity 3x15 TR-Plant for Signal Sec. Make-Bluestar |
35 | AC plant of capacity 2x30 TR-Plant for ESCT. Make-Bluestar |
36 | AC plant of capacity 3x26 TR-Plant for spyder. Make-Bluestar |
37 | AC plant of Capacity 3x7.5 TR plant for PW-VI. OEM-Bluestar |
38 | AC plant of Capacity 1x7.5 TR plant for PW-III. OEM-Voltas |
39 | M&L for evacuation of gas from the system into the empty cylinder provided by department/pumping down to the system, descaling condenser unit of the following capacity plants after bypassing the cooling tower, pumps & supply and circulation of the descalling solution (ANTI SCALENE SCALE FOEE-100) with pump brushing the tubes and where required drilling the stubbon scalling without damaging the tube, replacement of deshed end gasket and unserviceable nuts and bolts assembling back complete testing and commissioning including removing air lock, recharging the gas taken out of the system complete all as specified and directed . Notes:Descaling pumps, nylon brush, acid including storage containers, drill and drill bits to be arranged by contractor and cost of the same deemed to be included in the rate quoted for the following:- |
40 | AC plant of capacity 3x37.5 TR-Plant for RSBN. No of compressors are 9(OEM- Bluestar) |
41 | AC plant of capacity 3x15 TR-Plant for Signal Sec (OEM- Bluestar). No of compressors are 3 |
42 | AC plant of capacity 2x30 TR-Plant for ESCT (OEM-Bluestar). No of compressors are 4 |
43 | AC plant of capacity 3x26 TR-Plant for spyder (OEM- Bluestar. No of compressors are 6 |
44 | AC plant of Capacity 3x7.5 TR plant for PW-VI. OEM-Bluestar no of compressorare12 |
45 | AC plant of Capacity 1x7.5 TR plant for PW-III. OEM-Voltas No. of compressorare 9 |
46 | M & L for Vacuum the system and after maintaining vacuum for 24 hours supply and charge refrigerant gas HCFC 22 complete all as specified and directed . Make:-Mafron/Refron |
47 | M & L for Vacuum the system and after maintaining vacuum for 24 hours supply and charge refrigerant gas 407 C complete all as specified and directed . Make:-Mafron/Refron |
48 | M&L in replacement for EWT/LWT sensor suitable for tripping for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT, 3x7.5 TR PW-VI, 3x7.5 TR PW-III AC plant as required and specified by OEM i.e Bluestar. Complete all as specified and as directed. |
49 | M&L in replacement for digital temperature humidity display assembly as per existing sample for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT, 3x7.5 TR PW-VI, 3x7.5 TR PW-IIIAC plant as required and specified complete all as specified and as directed . Make :- Fluke or equivalent ISI Marked. |
50 | M&L in replacement for Thermometer gauge with thermowell complete with fittings etcas reqdcapacity 0-50 degree celcius placed on pipe line as per existing for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT, 3x7.5 TR PW-VI, 3x7.5 TR PW-III AC plant as required and specified. Complete all as specified and as directed by Engr-in-Charge. Make:- Feibig ,H Guru. |
51 | M&L in replacementpressure gauge complete with fittings ,cock valve ,syphon and pressure gauge etc Range 0-10.6 KG/cm2 (low/high) as per existing for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT3x7.5 TR PW-VI, 3x7.5 TR PW-III AC plant as required and specified complete all as specified and as directedMake:- Feibig ,H Guru. |
52 | Taking down defective /unserviceable AC compressor of capacity5.5/7.5 TR package type AC, and repair of the same compressor at company authorized outlet including replacemnet of bearing -02 Nos, rewinding ofsame gauge with super enamelled copper wire including removing burnt winding cleaning of slotes sepration of rotor and startor making insulation to all joint pressuretesting, oiling, lathe work, piston rings, shaft seal, bush& establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. NOTE- Compressor maintenance cost for next 6 months is deemed to be included in qouted rates. |
53 | Taking down existing water softener and supply and fixing water treatment system 440 LPM capacity non chemical online electrostatic type including control panel, outer casing made of SS 304 both ends flangedincluding necessary nut, bolts and rubber packing and cutting welding required at site all specified and directed by Engr-in-Charge. Make: Model no 302 of M/s Weldon Engineers or equivalent of Ion Exchange/Pristine water |
54 | Supply and fixing in replacement PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sq mm 3 core all as specified and as directed. |
55 | Supply and fixing in replacement PVC insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq mm 3.5 core all as specified and as directed. |
56 | M&L for painting of AC Plant as per existing colour including Compressor, condenser, motor, chiller pump, AHU, cooling tower, Plant LT panel including base and all pipe lines & connected valveetc complete all as specified and directed. |
57 | AC plant of capacity 3x37.5 TR-Plant for RSBN |
58 | AC plant of capacity 3x15 TR-Plant for Signal Sec |
59 | AC plant of capacity 2x30 TR-Plant for ESCT |
60 | AC plant of capacity 2x26 TR-Plant for Syder |
61 | AC plant of Capacity 3x7.5 TR plant for PW-VI. OEM-Bluestar |
62 | AC plant of Capacity 1x7.5 TR plant for PW-III. OEM-Voltas |
63 | M&L in replacement of control panel suitable for upto 7.5 TR package unit incl display unit, PCB model No -12.8412K10, contactor model No 3TF30100A-02 Nos, relay NO+NC, wiring complete all as specified and directed Make:-Blue Star package model No DPUA5475 & equivalent |
64 | M&L in replacement of Single phase preventor VSP 2 auto/manual reset of any size , 415V, |
65 | M&L in replacement MCCB (AC 415 V) with adjustable thermal & fixed magnetic setting Four pole 400 Amp 36 KA complete all as specified and directed . |
66 | M&L in replacement MCCB (AC 415 V) with adjustable thermal & fixed magnetic setting Four pole 620 Amp 36 KA complete all as specified and directed . |
67 | M&L in replacement MCCB 200 A, 4 Pole, 415 V, 36 KA Breaking capacity,withadjustable thermal & fixed magnetic release complete all as specified and directed . |
68 | M&L in replacement MCCB 100 A, 4 Pole, 415 V, 35 KA Breaking capacity,with fixed thermal magnetic release complete all as specified and directed . |
69 | M&L in replacement for MCCB 3 pole 63 amps, 25 KA, complete all as specified and directed . |
70 | M&L in replacement of Electronic overload relay (Manual reset) relayrange 9-16 amp suitable for direct mountimg complete all as specified and directed |
71 | M&L in replacement of Electronic overload relay (Manual reset) relay frame size 4 inch relay range 24-40amp suitable for contactor frame size CH 1 to CH 2 Type MPR200Nx . |
72 | S&F in replacement of flare nuts (5/8, 3/8) for connecting copper pipe for indoor & outdoor unit complete all as specified and directed . |
73 | M & L welding/brazing rod copper for fluxing to ac plant equipments complete all as specified and directed. |
74 | Supply only Butane gas cane of 225 gms for brazing complete all as specified and directed . |
75 | S&F in replacement Power contactor 3 pole Type MNX 18 AC 3 rating 18 A with auxiliary contact 1 NO + 1 NC ,Make- L&T/Legrand |
76 | M&L in replacement Power contactor 3 pole Type MNX 70 AC 3 rating 70 A with auxiliary contact 2 NO + 2 NC , cat No - ST19002. Make- L&T/Legrand |
77 | M&L in replacement Power contactor 3 pole Type 2 M 50 AC 3 rating 50A, coil capacity 240VAC. Make:- HCC-3XU04AV246N or equivalent. Make- L&T/Legrand |
78 | S&F in replacement Power contactor 3 pole Type3 ML AC 3 rating 40/45 A with auxiliary contact 2NO + 2NC, cat No - SS90721. |
79 | S&F in replacement Power contactor 3 pole Type MNX 25 A AC 3 rating 25 A with auxilary contact 2NO + 2NC, cat No - SS90921 Make- L&T/Legrand |
80 | S&F in replacement Power contactor 3 pole Type 1.5 ML AC 3 rating 25 A with auxilary contact 2 NO + 2 NC, Cat No - SS91851. Make- L&T/Legrand |
81 | M&L in replacement Power contactor 3 pole Type MNX 12 AC 3 rating 32 A with auxilary contact 2NO + 2NC. Make- L&T/Legrand |
82 | M&L for thermal insulation for ducts with 13mm thick nitrile rubber insulation, complete all as specified and directed . |
83 | Supply and installation in replacement of aluminium powder coated grills / diffusers for supply air/return air and size 400x 400mm, square type with MS volume control dampers complete all as specified and directed . |
84 | M&L in replacement of supply/return air ducting fabricated out of GI Sheet of thickness as under, complete all specified and directed . |
85 | Made out of 22 Gauge |
86 | Made out of 24 Gauge |
87 | S&F in replacement of high pressure cutout for R-22. complete all specified and directed by Engr-in-Charge Make:- Danfoss or equivalent ISI Marked. |
88 | S&F in replacement of Low pressure cutout for R-22. complete all specified and directed by Engr-in-Charge Make Danfoss or equivalent ISI Marked. |
89 | S&F in replacement of Oil pressure cutout for R-22. complete all specified and directed by Engr-in-Charge Make Danfoss or equivalent ISI Marked. |
90 | S&F in replacement of Solonoid Valve for AC plant of Cap upto 80 TR complete all specified and directed |
91 | S&F in replacement of Safety relief Valve for AC plant of Cap upto 80 TR complete all specified and directed. |
92 | M&L in replacment of PUF Insulation 36 mm thick, density 36kg/cm and 26 gauge GI cladding complete with necessry mounting arrangement like clamps nut bolt etc suitable for existing AC plant cap upto 100 TR all as specified and as directed. |
93 | M&L in replacement of PCB contoller panel with display unit complete with necessary mounting, contactor, wiring kit, thimble, contact complete suitable for existing AC Plant cap upto 100 TR, PCB model No WCUS1015A complete all as specified and as directed . |
94 | Repair of PCB contoller panel with display unit complete with necessary mounting, contactor, wiring kit, thimble, contact complete suitable for existing AC Plant cap upto 100 TR, complete all as specified and as directed . |
95 | M&L in replacement Duct filter with ss material filter media capacity shall capable 5 microns as per existing, suitable for AC plant of capacity upto 75 TR, package units as per site requirement. Complete all as specified and directed . |
96 | M&L in replacement Strip heating element of cap 3KW (3000 W)240 Volt Ac 50 Hz single phase complete all as specified and directed . Make- Dass pass or equivalent ISI Marked. |
97 | M&L in replacement compressor Strip heaters of cap 1.5KW,240 Volt Ac 50 Hz single phase complete all as specified and directed. Make- Dass pass or equivalent ISI Marked. |
98 | M&L in replacement Aluminium sprinkler 3"x63mm with necessary mounting complete suitable for existing cooling towers,complete all as specified and as directed . |
99 | M&L in replacement rigid PVC (drift size 600 MM X 600 MM X 125 MM) elemator for distribution of water over fills with necessary mounting complete suitable for existing cooling towers cap upto 100 TR,complete all as specified and as directed by Engr-in-Charge |
100 | Taking out the U/S motor and rewinding of motor capacity 7.5 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos. |
101 | Taking out the U/S motor and rewinding of motor capacity 5 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos. |
102 | Taking out the U/S motor and rewinding of motor capacity 3 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos. |
103 | Taking out the U/S motor and rewinding of motor capacity 2 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items. All as specified and directed . (a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush (c) Replacement of cooling fan - 01 Nos. |
104 | Opening of pump 7.5 HP centrifugal for repair and replacement of following u/s parts including re-fixing of all the same and testing and commissioning complete all as directed. |
105 | Opening of pump 5 HP centrifugal for repair and replacement of following u/s parts including re-fixing of all the same and testing and commissioning complete all as directed. |
106 | Opening of pump 3 HP centrifugal for repair and replacement of following u/s parts including re-fixing of all the same and testing and commissioning complete all as directed. |
107 | Supply only in replacement of following defective spare parts ofmotor of any description/make and capacity 5/7.5 Hp and in any positioin :- |
108 | Replacement of gun metal impeller. |
109 | Replacement of gun metal bush |
110 | Replacement of ball bearing. |
111 | Replacement of oil seal |
112 | Replacement of gland |
113 | Replacement of gun metal impeller for 03 HP |
114 | M&L in replacement of fasteners made of aluminium with suitable size for fixing of cooling tower fan blades including nut, bolts etc. |
115 | Cleaning of Y type strainer by opening of all nut bolts and removing filter under strainer cleaning the accumulated mud, cooling tower of any capacity, choked nozzles, valves etc. Complete all as specified and directed . |
116 | M&L for fixing cooling tower FRP Type forced draft suitable for AC plant capacity 60 TR along with high speed fan motorand mounting and connection frame along with nut bolt, washer, sprinkler.Complete all as specified and directed . |
117 | Taking down the unserviceable MCB and replace same MCB TP 63 Amp, 415V, 10 kA complete all as specified and directed . |
118 | M&L in replacement of Rotational moulded polyethylene water storage capacity 2000 L tank (cylindrical vertical with closed top) hoisted and fixed in position all as specified and as directed . |
119 | Taking down the unserviceable MCB SP and replace the same MCB SP "C" Curve 6-32 Amp 10 kA complete all as specified and directed . |
120 | M&L in replacemenbr of filter dryer strainer suitable for central AC plant of various capacities for installation in suction/chiller/liquid line. Make - Danfoss |
121 | Repairing and overhauling, commissioning and testing of AC compressor suitable for 15 TR at various location of AC plants, comprising of dismantling replacement of unserviceable components including, metaling grinding, polishing and reflux nuts, bolts, washers, assembling the compressor testing on load complete all as specified and directed. Note:-Spare parts/Component will be measured & paid seperately under item no 66 here in below" Model No SM185S4RC of Danfoss or equivalent of Blue Star/Voltas |
122 | Supply only under mentioned spare parts for AC plants for maintenance of repair to compressor |
123 | Connecting rod |
124 | Cylinder liner |
125 | Piston |
126 | Piston ring |
127 | Gajan pin |
128 | Suction plates |
129 | Suction read and discharge read |
130 | Oil pump |
131 | Loder assembly |
132 | Gasket sets complete |
133 | Tyre coupling with lock |
134 | Oil filter |
135 | Spring section |
136 | Spring ducting |
137 | Oil seal |
138 | Main Bearing |
139 | M&L in replacement of fabrication and designing for motor and pump mounting made up of channel MS angle iron, Ms channel, Ms sheet and ensuring the allignment of pump and motor thickness not less than 7 mm Framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg each to be measured under "Structural Steel") complete all as specified and directed . |
140 | M & L in replacement of Pre - insulated MS pipe dia 65 mm , Class "C" having thickness of PUF insulation 36 mm of density 36 Kg/Cum and 26 gauge GI claddingcomplete suitable for above ground with all mounting arrangements like clamps with nut bolt , brazing etc. Complete all as specified and as directed. |
141 | M & Lin replacement of Pre - insulated MS pipe dia 80 mm , Class "C" having thickness of PUF insulation 40 mm of density 36 Kg/Cum and 26 gauge GI cladding complete suitable for above ground with all mounting arrangements like clamps with nut bolt , brazing etc. Complete all as specified and as directed. |
142 | M & L in replacement of Pre - insulated MS pipe dia 50 mm , Class "C" having thickness of PUF insulation 36 mm of density 36 Kg/Cum and 26 gauge GI claddingcomplete suitable for above ground with all mounting arrangements like clamps with nut bolt ,brazing etc. Complete all as specified and as directed. |
143 | M&L in replacement of inner copper tubing of chiller of capacity 37.5 TR including necessary brazing, welding work complete all as specified and directed by Engr-in-Charge. Dismantling of existing pipeline and miscellineous work required at site, refixing of all water lines, insulation, check leakage, testing and sensors is deemed to be included in quoted rate by Contractor . Make-Bluestar or equivalent ISI Marked. |
144 | Supply and fix the following unserviceable accessories of complete central/package type AC plant of capacity upto 100 TR including connecting testing complete all as directed:- |
145 | out door unit condensing/AHU motor"s fan blade |
146 | V Belt of AHU |
147 | canvas cloth for linkage as per existing |
148 | Phase sequence corrector |
149 | Expansion valve as per existing |
150 | Anti freeze thermosat |
151 | MS Nuts, bolts and washers of various sizes as required. |
152 | Compressor oil No-90 |
153 | S & F in repairs indicator lamps suitable for 3 phase LT panel board/as per sample complete all as specified and directed by Engr-in-Charge. |
154 | M&Lin replacement of ampere meter digital type, 415V suitable for existing panel CT operated of range 0-100 as required. Make- AE/L&T/Legrand |
155 | M&Lin replacement of voltmeter digital type, 415V suitable for existing panel CT operated of range 0-500. Make- AE/L&T/Legrand |
156 | M&L in replacement of MNX/MCX front block 2NO and 2NC complete all as specified & directed. make-AE/kappa/SG |
157 | M&L in replacement of terminal block single way suitable for mounting unit complete all as specified & directed. make-AE/kappa/SG |
158 | M&Lin replacement of panel mounted ON/OFF push button with contact block. SG/L&T/Selzer |
159 | M&L in replacement of CT50/5 complete all as directed.make-AE/kappa/Legrand |
160 | M&L for fixing in replacement of butterfly valvewith CI body ,SS Disc ,nitrile rubber seal & O ring ,PN 1.6 Pressure rating comlete all as specified by Engr-in-Charge against replacement ofthe existing one, complete all as specified and as directed by Engr-in-Charge. Make Zoloto/Leader/Castle |
161 | 50 mm dia |
162 | 65 mm dia |
163 | 80 mm dia |
164 | M & L in replacement of Earthing complete with galvanised steel earth plate electrode, 600x600x6mm thick, buried directly in ground vertically to depth not less than 1.5 meters below normal ground level, connected to galvanised iron earthing strip 25x4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, CGI watering pipe 15 mm bore light grade with funnel and wire mesh, PCC chamber in cement concrete 1:3:6 type c1, 80mm thick pre-cast RCC 1:2:4, type B-1 cover reinforced earth plate surrounded by alternate layers of packed charcoal, salt oacked which shall not be less than 15cm in all side of earth plate complete all as shown in electrical plate No 3 of MES schedule Part-I.specified and directed by Engr-in-charge . |
165 | supply ,Fixing and testing MS "C " Class pipe of size 50 mm all as specified and directed by Engr-in-charge. |
166 | All as per item No 83 above but size 65mm dia pipe |
167 | Supply ,fixing in replacement including testingFRP Cooling Tower inducted draft type with motor ,plant of heat rejection capacity60 Tonnage with FRPPanel as made out with FRP type water basin ,PVC filling with integral louversand drift eliminator,filled throughhigh density polythene (HDPE) nozzles of having self rotating type sprinklers ,statically and dynamically balanced axial flowfan typefan direct driven with TEFCsquirrel cage induction motor ,suction screen ,make up quick fill arrangement ,overflow and drain connections with necessaryvalves and suitable inspection ladder ,access arrangement for cooling tower interior ,cement concrete platform including necessaryfoundation ,steel supporting structure,anti-vibration mounting complete all as specified and directed. Make:DELTA/ADVANCE/MIHIR Note:- Unsv cooling tower to be deposited into MES salvage yard. |
168 | Repair / maintenance of LT panel board overhauling by dismantling all cable terminals, taking out starters, busbars, MCCBs, replacement of:- (a) unsv copper / aluminium cable end terminals. (b) unsv nuts, bolts & washers (c) unsv aluminium bus bars 250A rating for 3 phase and neutral - 01 Set(25x5mm Al strip total qty 4 mtr for 3 phase and one neutral) (d) unsv selector switches (e) unsv ON/OFF Push buttons (f) unsv staters-7.5HP-02 Nos (g) unsv staters-12.5HP-02 Nos (h) unsv door panel fixing screws and hings (j) unsv panel wiring and complete assembling of LT panel board with serviceable items as dismantled and new items as replaced, spray painting with one coat of synthetic enamel paint to external surface of panel board, testing after completion all as specified and directed. Note: MCCBs, Ampmeter, voltmeter, selector switches, push buttons, LED indicators, CTs, Starters, relay, timer required for replacement will be measures separately. |
169 | Schedule of Credit |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail