Supplying, Erection , Testing Commissioning Of 250 Kva Platform Mounted Distribution Substation Near Bank Post Office Telecommunication Centre 100 Kva Pole Mounted Distribution Substation Along With Tapping Point In The Premises Of Adm Block At 1
BOQ
| Sl. No. | Item Description |
| 1 | Supplying/Errection/Testing/ Commissioning of 250 KVA Distribution SubstationS/E/T/C of 250 KVA Distribution substationnearBank/Post office/Telecommunication Centre of CFC Building atIndustrial Growth Centre Samba Phase-IIIa) 250 KVA Distribution Transformer 11/433 KVA Level-2 copper wound with filling of fresh T-oil as required -1Nob) P/F of steel tubular pole 410-SP-33 the pole shall be amount which shall be painted with red oxide & two coats of simmer paint cemented upto 5 feet in the ratio of 1:3:6 with 1 feet of Muff above the grand level with surface plastering etc. as required -2 Nos.c) Gapless surge arrester 9 KV, 10KV L.A with polymer/ porcelain Housing station type-1Setd) 11 KV G.O AB Switch 3 3 pole 400A – 1 Sete) 11 KV DO fuse 3 phase 400 Amp – 1 Setf) 11 KV Disc insulators (Polymer/ Porcelain) complete with fitting (45 KN) – 3 No.g) GI Chanel/ Angle/ Flat of size including damps – 200 Kg.h) 11 KV Pin insulators (polymer/porcelain) with pins (5 KN) – 3 No.i) Galvanized stay set with 50 x8 mm stay clamp, guy insulator (2 Nos), Anchor plate ( 200x 200 x 6 mm) Nut Bolts 2 No. turn Buckles 1.8m long 16 mm Dia meter solid GS stay rod 2 7/3.15 mm Dia GI stranded wire complete -2 Set.j) Wedge connector/ PG clamps – 6 Nos.k) P/F of 1x 240 unarmored Aluminum cable with thumbing to end terminals – 15 Mtr.l) Galvanized Nut & Bolts – 8 Kg.m) Danger plate with clamp – 1 No.n) G.I Barbed wire for Anti climbing- 15 Kg.o) P/F of 0.05 ACSR Conductor – 10 Mtrp) P/L of Chemical earthing with Main Holes -3nosq) P/F of 25 x 5 mm G.I strip on surface or in recess for connection etc as required.r) Sundry items like Aluminium lugs, Jumpess Binding tape etc - LSs) P/F of fuse link Bus Bar on Angle iron for protection of transformer – 1 No. |
| 2 | Construction of Platform for 250 KVA DistributionSubstation Construction of platform (7x7x 4.5 ft) (Lengthx Breadth x Width) is 1.5 feet below the ground level in the Ratio of 1:2:4 (1 Cement : 2 send :4 graded stone aggregated 40 MM nominal) size for Errection of 250 KVA Transformer along with steel tubular poles on platform. The job also includes providing and fitting of chain link fencing on platform and covered from all four sides with Entry gate at front side and shall be provided with locking arrangement. The fencing should be 3 feet above the platform surface. Complete job includes cost of material, labour charges, Painting charges, white washing charges etc. as requiredComplete job in all respect. |
| 3 | Tapping Point for 250KVA& 100KVASubstation along with HT Line:- Providing and laying of tapping point for 250KVA Distribution Substation comprising of following items.i) 120 Sq.mtr HT AB Cable-------75 Mtr.ii) Steel Tubular poles 11 Mtr.-------04 Nos.iii) Clamps/Hook for supporting of HT Cable-4 Nos.iv) HT Connection kit -2 Nos.v) Nut Bolt with washer. -------------lump sumvi) Go/Do Switch to disconnect the HT Line----1No vii) Misc items as per site requirements.? The items increase/ decrease as per site requirement |
| 4 | Supplying/Errection/Testing/ Commissioning of 100 KVA Distribution SubstationS/E/T/C of100 KVA Distribution substation in the premisesofADM Block atIndustrial Growth Centre Samba Phase-IIIa) 100 KVA Distribution Transformer 11/433 KVA Level-2 copper wound with filling of fresh T-oil as required -1Nob) P/F of steel tubular pole 410-SP-33 the pole shall be amount which shall be painted with red oxide & two coats of simmer paint cemented upto 5 feet in the ratio of 1:3:6 with 1 feet of Muff above the grand level with surface plastering etc. as required -2 Nos.c) Gapless surge arrester 9 KV, 10KV L.A with polymer/ porcelain Housing station type-1Setd) 11 KV G.O AB Switch 3 3 pole 400A – 1 Sete) 11 KV DO fuse 3 phase 400 Amp – 1 Setf) 11 KV Disc insulators (Polymer/ Porcelain) complete with fitting (45 KN) – 3 No.g) GI Chanel/ Angle/ Flat of size including damps – 200 Kg.h) 11 KV Pin insulators (polymer/porcelain) with pins (5 KN) – 3 No.i) Galvanized stay set with 50 x8 mm stay clamp, guy insulator (2 Nos), Anchor plate ( 200x 200 x 6 mm) Nut Bolts 2 No. turn Buckles 1.8m long 16 mm Dia meter solid GS stay rod 2 7/3.15 mm Dia GI stranded wire complete -2 Set.j) Wedge connector/ PG clamps – 6 Nos.k) P/F of 1x 185 unarmored Aluminum cable with thumbing to end terminals – 15 Mtr.l) Galvanized Nut & Bolts – 8 Kg.m) Danger plate with clamp – 1 No.n) G.I Barbed wire for Anti climbing- 15 Kg.o) P/F of 0.05 ACSR Conductor – 10 Mtrp) P/f of prodigy meter with required cable – 1Noq) P/L of Chemical earthing with Main Holes -3nosr) P/F of 25 x 5 mm G.I strip on surface or in recess for connection etc as required.s) Sundry items like Aluminium lugs, Jumpess Binding tape etc - LSt) P/F of fuse link Bus Bar on Angle iron for protection of transformer – 1 No. |
| 5 | Chain Link Fencing for 100KVA D/st substation:-Providing and fitting of chain link fencing and covered from all four/Three sides with Entry gate at front side and shall be provided with locking arrangement. The fencing should be 4.5 feet above ground level surface. Complete job includes cost of material, labour charges, Painting charges etc. as requiredComplete job in all respect. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender