| 1 | Material and labour for cleaning of following RCC tank/masonary sumps/water reservoirs, through 7 stages of cleaning and sterilization consisting of three stages of bacteriological screening done by Terbac-G10, Terbac-G5, Terbac-G65 and Ultra Violet ray process complete all as specified and as directed for the following :- Note 1 for cleaning stages:-(a) First stage is to drain out the water by using exit valve or our own high capacity dewatering system.(b) Second stage is cleaning all the algae formation inside the tank by using TERBAC G10 , a laboratory tested branded chemical of the company and scrubbing the walls of the tanks.(c) Third stage is fresh water cleaning by high speed jet pumpwith pressure 5 PSI.(d) Fourth stage and first bacteria screening is Sterilization by using TERBAC-G5 aLaboratory certified branded halogen compound.Test certificate of TERBAC-G5 from government laboratory mentioningsuitability for sterilization should be submitted to the office before using for sterilization.(e)Fifth stage is cleaning the floor of the water tank byheavy duty industrial vacuum cleaner.(f) Sixth stage is the second bacteria screening and sterilizing method by using ultra violet ray Ejector covering 360 degree with in the tank and kills all suspended bacteria.(g) Seventh Stage of cleaning and third bacteria screening is to sterilize the floor of the water tank by using laboratory certified branded strong oxidizing agent TERBAC- G65.Test certificate of Terbac- G65 From Government Laboratory mentioningsuitability for sterilization should be submitted to the office before using for Sterilization.Note 2: Cleaning shall be done at-least two times at an interval of six months or at an early period if directed by Engineer-in-Charge.Note 3: (a) Entire T&P shall be arranged by the contractor at his own cost. MES only supply electric and water with stipulated rate, if contractor demanded.(b) Company will submit Govt. laboratory test certificate of TERBAC-G5, TERBAC-G65, fix the stricker mentioning the date of cleaning & name of site and also provide certificate conforming the completion of sterilization of water tanks mentioning the name of station and date of cleaning. All the cleaning & sterilization staffs should be under accidental insurance coverage. |
| 2 | Semi under ground Clear water sump 50000 gallons capacity 3.5 m in depth. |
| 3 | Semi under ground Clear water sump 30000 gallons capacity 3.5 m in depth. |
| 4 | Semi under ground Clear water sump 10000 gallons capacity 3.5 m in depth. |
| 5 | P& S overhead tank of 9600 gallons capacity |
| 6 | SWT of 11000 gallons capacity |
| 7 | M & L for preparation of old or previously treated internal and external steel/iron surfaces of over head pressed steel tanks and all steel surfaces of staging and applying one coat of anticorrosive synthetic enamel paint complete including writing of capacity, tank cleaned date etc with white paint of letter size 15 cm on 60 cm x 90 cm size black paint background complete all as directed. |
| 8 | Supply of calcium based granular disinfectant (Calcium Hypo Chlorite) consisting 65%-70% Chlorine Content for Water Treatment Packed in 45 Kg Drum factory sealed delivered at store yard of E/M Office, Laitkor Peak Shillong.Make:- Any brand approved by E-in-C\"s or any other brand whose product fulfills the parameters specified in Manual on Water Supply and treatment (Third Edition May 1999) issued by CPHEEO,Ministry of Urban Dovelopment, New Delhi.Note :- The brand must contain corrosion inhibitor & Anti Scalling agent to prevent damage of distribution pipelines & accessories. |
| 9 | Excavation in trenches, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr deep in soft / loose soil for removing old and laying new pipes , complete all as specified and directed at site. |
| 10 | Returning, filling in, excavated soil including leveling, watering and well ramming in layers of thickness not exceeding 25 cm in each layer complete all as specified and directed. |
| 11 | Removing excavated surplus soil to a distance not exceeding 50 mtr and depositing the soil where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 12 | Disconnecting and taking up or down old existing GI / DI /PPR pipe and connections of any description / grade and in any position in trenches / under floors etc including connected fittings/accessories and fixtures , all as specified and directed for the following sizes :- |
| 13 | 100 mm bore |
| 14 | 150 mm bore |
| 15 | 80 mm bore |
| 16 | Supply, Laying, jointing & testing of Ductile iron (DI), pressure pipes Centrifugally Cast (Spun) Ductile Iron Pressure Pipes with Spigot & Socket end, Class K-7 conforming to IS: 8329/2000 (latest revision) -blast furnace slag cement with Portland cement properties suitable for (push-on) rubber gasket jointing with inside cement mortar lining and Black bitumen external coating, duly ISI marked suitable for push on joint(rubber gasket joint) in any length with inside cement mortar lining, 100 mm bore laid in trenchesMake: Tata Metaliks/ Electrosteel Casting Ltd./ Jindal Saw Ltd. Note:- (i) Excavation & Earthwork, shall be measured and paid separately. (ii) The quoted rate shall deemed to include for provision of joints and jointing material for laying pipes and for jointingpipe fittings or taking branch connection, provision of joints and jointing material shall be measured and paid separately. |
| 17 | Supply, Laying, jointing & testing of Ductile iron (DI), pressure pipes Centrifugally Cast (Spun) Ductile Iron Pressure Pipes with Spigot & Socket end, Class K-7 conforming to IS: 8329/2000 (latest revision) -blast furnace slag cement with Portland cement properties suitable for (push-on) rubber gasket jointing with inside cement mortar lining and Black bitumen external coating, duly ISI marked suitable for push on joint(rubber gasket joint) in any length with inside cement mortar lining, 150 mm bore laid in trenchesMake: Tata Metaliks/ Electrosteel Casting Ltd./ Jindal Saw Ltd. Note:- (i) Excavation & Earthwork, shall be measured and paid separately. (ii) The quoted rate shall deemed to include for provision of joints and jointing material for laying pipes and for jointingpipe fittings or taking branch connection, provision of joints and jointing material shall be measured and paid separately. |
| 18 | Taking up or down steel tubingand connections and Supply and fix 100 mm bore size steel water tubing, galvanized, medium grade, with all fittings like bends, sockets, reducers etc as required in new or old alignment, on floor, vertically on overhead reservoir,complete all as specified and directed. Make: Jindal/ Prakash/ Tata |
| 19 | Taking up or down steel tubingand connections and Supply and fix 80 mm bore size steel water tubing, galvanized, medium grade, with all fittings like bends, sockets, reducers etc as required in new or old alignment, on floor, vertically on overhead reservoir,complete all as specified and directed. Make: Jindal/ Prakash/ Tata |
| 20 | Supply and fix in repairs Cast Iron Air Valves with single air outlets, conforming to IS 14845 of size 150 mm dia bore and fixing up in Cast Iron Water supply mains of size 150 mm dia complete all as specified and directed.Make:-Zoloto/Kirloskar/ Leader |
| 21 | Supply and fix as in repairs and testing cast iron non return (reflux) valve in repairs suitable for 150 mm dia pipe, heavy duty, flanged ends with gun metal seat, class PN 1.6, IS - 5312 marked including all jointing materials such as leather gasket, bolts nuts washers etc complete all as specified and directed.Make:-Zoloto/Kirloskar/ Leader |
| 22 | Supply and fix as in repairs 150 mm bore CI Sluice valve PN-1.6 IS 14846-2000 with Spindle bronze (Heavy duty) Wheel head and both ends flanged and MS nut bolts and washers and pair of rubber/fiber gasket and fixed in position. Make:-Zoloto/Kirloskar/ Leader |
| 23 | Supply and fix as in repairs 100 mm bore CI Sluice valve PN-1.6 IS 14846-2000 with Spindle bronze (Heavy duty) Wheel head and both ends flanged and MS nut bolts and washers and pair of rubber/fiber gasket and fixed in position. Make:-Zoloto/Kirloskar/ Leader |
| 24 | M&L for repairing150mm size pipe leaking flanged joints by opening the joints, replacing the rubber/ leather gasket including cleaning the joints and refixing the fittings complete all as directed. |
| 25 | Dismantling old rusted/unserviceable mild steel sheet/plate and Supply & Fixing mild steel sheet/plates plain or chequered including angle iron andwith riveted, bolted or welded attachment as required at site, of size and thickness as per existing for repair of PS tanks and forming holes for nuts and bolts, cutting, welding, bending cold or hot and necessary gasket for prevention of leakage and necesssary testing after fixing complete all as specified and asdirected. |
| 26 | S&F FRP solution prepration tank with lid, port hole, inlet / outlet / drain connection, level gauge etc and fitted with speed reducing motor & SS-316 agitator combined with dosing tank with lid, port hole, inlet / outlet / drain connection, level gauge etc. Prepration tank - 170 ltrs, Dosing tank - 100 ltrs complete all as specified and directed by Engr-in-Charge. |
| 27 | Material and labour for water proofing coating, inside of the filter shell shall be painted with back anticorrosive paint and outside shall be painted with two coats of epoxy. |
| 28 | Supply and fix LED Post top lantern of 40 Watts, 240V, 50Hz , IP65 protection,5700 K anti corrosive die cast aluminium bodyMake: Century LED Product Code APBY040C/ Crompton Cat No LPTO-40-CDL / Bajaj Cat No BGCL 40W LED WHNote:- (a) LM-79 and LM-80 certificate from NABL accredited Lab shall be submitted for LED light fittings.(b) Warranty certificate shall be submitted for LED light fitting as per standered format for minimum 50000 Hrs.(c) LED light fitting and drivers shall be of same make. |