Tender For Repair/Maint Dg Sets, Amf Panel And Allied Works At Chnc And Generation Section Under Ge (Utilities) Udhampur., Reasi-Jammu And Kashmir

Military Engineer Services-MES has published Tender For Repair/Maint Dg Sets, Amf Panel And Allied Works At Chnc And Generation Section Under Ge (Utilities) Udhampur.. Submission Date for this Tender is 12-07-2023. Diesel Generators Tenders in Reasi Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

38115697
Corrigendum : Tender For Repair/Maint Dg Sets, Amf Panel And Allied Works At Chnc And Generation Section Under Ge (Utilities) Udhampur.
Open Tender
Indian
Jammu And Kashmir
Reasi
12-07-2023

Tender Details

Repair/Maint Dg Sets, Amf Panel And Allied Works At Chnc And Generation Section Under Ge (Utilities) Udhampur.

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 26-Jun-2023 BOQ REVISED BOQ 05-07-2023
2 05-Jul-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 12-07-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 96000.0 /-
Tender Value
INR 48 Lakhs /-

BOQ Items

Name of Work: Repair/maint DG sets, AMF Panel and allied works at CHNC and Generation Section under GE (Utilities) Udhampur.
Sl. No. Item Description
1Carry out servicing from authorised rep or service engineer from the manufacturer of DG set of 100 KVA to 200KVA,capacity complete all as per OEM instructions and directed by Engr in Charge . Note : All the spare , parts , lubrication oil etc. has been measured and paid saperatly under respective item of schedule "A".
2All as per item No.1.00 here-in-before but of capacity 40 KVA to 75 KVA DG set complete all as specified and directed by Engr-in-Charge.
3All as per item No.1.00 here-in-before but of capacity upto 31.25 KVA DG set complete all as specified and directed by Engr-in-Charge.
4Fuel filter (primary and secondary) (in replacement) of DG Set of capacity 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge.
5Fuel filter (primary and secondary) ( in replacement) of DG Set of capacity40KVAto 75KVA complete all as specified and directed by Engr-in-Charge.
6Fuel filter (primary and secondary) (in replacement) of DG Set of capacity10KVAto 31.25KVA complete all as specified and directed by Engr-in-Charge.
7Oil filling body(in replacement)for DG Set capacity of 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge.
8Oil filling body ( in replacement) for DG Set capacity of 40KVA to 75KVA complete all as specified and directed by Engr-in-Charge.
9Oil filling body (in replacement ) for DG Set capacity of 10KVA to 31.25KVA complete all as specified and directed by Engr-in-Charge.
10Hose (H.Exchanger to W.Pump) ( in replacement) complete all as specified and directed by Engr-in-Charge.
11Engine start push button ( in replacement ) Green colour "NO" contact( vasihno make,cat no.2xvaf,flush type) complete all as specified and directed by Engr-in-Charge.
12Engine stop push button (in replacement)Red colour "NO" contact( vasihno make,cat no.2xvaf,flush type) complete all as specified and directed by Engr-in-Charge.
13Disconnected and opening of self starter assemlly 12 volt for repair from DG set upto 125 KVA, repair unserveceable part of self starter suitable size as required on sitecomplete all as specified and directed by Engr-in-Charge. Note :- Rate are deemed tobe include all worn out part including gear & winding.
14Disconnected and opening of self starter assemlly 24 volt for repair from DG set upto 200 kva, repair unserveceable part of self starter suitable size as required on sitecomplete all as specified and directed by Engr-in-Charge. Note :- Rate are deemed tobe include all worn out part including gear & winding complete all as specified.
15Stop solenoid assembly 12V DC(in replacement)for micro pump (two coil) heavy duty electrical control make energise to stop of DG Sets complete all as specified and directed by Engr-in-Charge.
16Battery cable assembly ( in replacement) ( -ve & +ve ) 4 lengthsuitable complete all as specified and directed by Engr-in-Charge.
17Supply and fixing in replecement of 110 Amp,4pole, 415 Volts, 50 Hz Power contactor (MNX110) auxilary contact 2 NO + 2 NC, of coil voltage 240 Volts, complete all as specified and directed by Engr-in-Charge.
18Supply and fixing in replecement of 160 Amp,4pole, 415 Volts, 50 Hz Power contactor (MNX140) auxilary contact 2 NO + 2 NC, of coil voltage 240 Volts, complete all as specified and directed by Engr-in-Charge.
19Supply and fixing in replecement of 70 Amp,4pole, 415 Volts, 50 Hz Power contactor (MNX70) auxilary contact 2 NO + 2 NC, of coil voltage 240 Volts, complete all as specified and directed by Engr-in-Charge.
20Supply and laying in trenches/wall/air armoured cable 1100 Voltmulti stranded copper conductor cable of size 2.5 sqmm X 8 core for connection of AMF panel to DG set complete all as specified and directed by Engr-in-Charge.
21Inter connection battery cable lead (copper)(in replacement ) with terminal size 35 sq mm (30 cm long) complete all as specified and directed by Engr-in-Charge.
22Supply and filling coolent for radiators. K Cool super Plus -50-50 premix.Cat part No.82.020.35.1.25. 25ltrs Packing complete all as specified and directed by Engr-in-Charge.
23AVR S/F variable speed DCDG (in replacement ) suitabler for DG Sets of capacity 100KVA to 200KVA complete all as specified and directed by Engr-in-Charge.
24AVR S/F variable speed DCDG ( in replacement) suitabler for DG Sets of capacity 10KVA to 75KVA complete all as specified and directed by Engr-in-Charge.
25Disttled water for battery complete all as specified and directed by Engr-in-Charge.
26Flexible pipe of M30 X 1.5 union (replacement) both side,1400mm long complete all as specified and directed by Engr-in-Charge.
27Supply only Engine Oil 15W 40 in sealed drum complete all as specified and directed by Engr-in-Charge.
28Drain Pipe of DG Sets (in replacement) of capacity 10KVA to 200KVA complete all as specified and directed by Engr-in-Charge.
29Over hauling of Fuel injector pump of DG set by taking down carefully, transprotation of the same to civil work-shop for repair & complete service of FIP pump and calibration on automatic setting machine, shifting of FIP pump from civil work-shop to worksite and re-fixing the same to DG set and testing 100KVA to 320KVA complete all as specified and directed by Engr-in-Charge.
30Over hauling ofFuel injector pump of DG set by taking down carefully, transprotation of the same to civil work-shop for repair & complete service of FIP pump and calibration on automatic setting machine, shifting of FIP pump from civil work-shop to worksite and re-fixing the same to DG set and testing 10KVA to 63KVA complete all as specified and directed by Engr-in-Charge.
31Dismantling / Taking down the 31.25KVA DG Set (Engine and Alternator ) assembly / parts for carrying out / replacement of following spare parts at site and re-assembling the DG Set after repair and testing complete. Note: Spare parts replaced shall be measured and paid as supply only .
32Piston Ring set complete all as specified and directed by Engr-in-Charge.
33Cylinder liner with joints rings complete all as specified and directed by Engr-in-Charge.
34Valve cylinder head assly complete all as specified and directed by Engr-in-Charge.
35Valve seat insert (inlet) complete all as specified and directed by Engr-in-Charge.
36ValveGuideCyl head complete all as specified and directed by Engr-in-Charge.
37Valve collet (3-grove)lock complete all as specified and directed by Engr-in-Charge.
38Cylinder headgasket complete all as specified and directed by Engr-in-Charge.
39Sets of Jointst(Engine Gasket set complete) complete all as specified and directed by Engr-in-Charge.
40Crank oil seal front complete all as specified and directed by Engr-in-Charge.
41Crank oil seal rear complete all as specified and directed by Engr-in-Charge.
42Thrust washer complete all as specified and directed by Engr-in-Charge.
43Connecting rod bearing(cell) complete all as specified and directed by Engr-in-Charge.
44Main general bearing(cell) complete all as specified and directed by Engr-in-Charge.
45Supply only Connecting rod bush complete all as specified and directed by Engr-in-Charge.
46Supply only Piston assembly complete all as specified and directed by Engr-in-Charge.
47Supply only Fan Belt complete all as specified and directed by Engr-in-Charge.
48Supply only Copper Washer complete all as specified and directed by Engr-in-Charge.
49Supply only Fuel pipe set complete all as specified and directed by Engr-in-Charge.
50Supply onlyAir Cleaner Element complete all as specified and directed by Engr-in-Charge.
51Repair /Turner job ofCylinder head assly (valve set fitting,valve guide fitting,valve grinding and fitting (turner job) by taking outfrom DG set carefully, transportation of the same to civil work-shop for repair & complete serviceand calibration on automatic setting machine andcivil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
52Repair /Turner job of Crank shaft by taking outfrom DG set carefully, transportation of the same to civil work-shop for repair & complete serviceand calibration on automatic setting machine andcivil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
53Repair /Turner job ofAlternator assly 12volt,taking outfrom DG set carefully, transportation of the same to civil work-shop for repair rewinding , replacae bearing & complete serviceand calibration on automatic setting machine andcivil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
54Repair /Turner job ofFuel injector pump(FIP),Injector assly,Pump element,delivery valve,and i nozzel,taking outfrom DG set carefully, transportation of the same to civil work-shop for repair & complete serviceand calibration on automatic setting machine andcivil work-shop to worksite complete all as specified and directed by Engr-in-Charge.
55Dismantling of radiator and repair by welding/soldering of radiator and re-fixing the same after cleaning of radiator with soda and acid including replacement of radiator foundation nuts, bolts complete all as specified and directed by Engr-in-Charge.
56Oil pressure Sensor(in replacement) complete all as specified and directed by Engr-in-Charge.
57Water temperature Sensor ( in replacement) complete all as specified and directed by Engr-in-Charge.
58M&L for replacement of Solenoied switch sutaible for DG Set upto 200 kva completeall as specified and directed by Engr-in-Charge.
59M&L for replacement of Temprature Gauge for DG set of capacity 31.50 KVA of any make complete all as specified and directed by Engr-in-Charge.
60M&L for replacement of RPM meter for DG set of capacity 31.50 KVA of any make complete all as specified & directed by Engr-in-Charge.
61M&L for replacement of Ring gear of Flywheel suitable for DG set up to 320 KVA complete all as specified & directed by Engr-in-Charge.
62Supply, Fix & test run the DG set after replacing Diesel feeder Pumpof existing model,sizesuitable for DG Set of capacity 15 to 320 KVA including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge.
63Drain out the fuel from the fuel tank of DG set of any size/capacity and keeping it in separate container safely, disconnecting all the fuel lines and other mechanical connections and taking out the fuel tank for cleaning, internally and externally by removing all the accumulated dirt/ sediment, leak testing the tank and welding/ brazing including one coat ofsynthetic enamel paint, refixing the tank in its original position, replacing the drain plug and PVC pipe, calibrating the fuel tank, refilling the drained out fuel back into the tank and marking of liters in gauge and provision of locking arrangements ccomplete all as specified and directed by Engr-in-Charge.
64Dismantling existing U/S battery charger & S/F of SMPS type battery charger suitable for 12 V/24V DC with auto cut off from trickle to boost alongwith AC lead to charge the battery when DG Set is not in use complete all as specified and directed by Engr-in-Charge.
65Material & labour for carrying out complete overhauling / servicing of DG set panel / AMF panel / control panel,including checking and rewiring faulty electrical circuit using 2.5 sqmm FRLS copper conductor, for DG Set of any type / make / capacity, making all electric connections and testing for smooth operation, complete all as specified and directed by Engr-in-Charge.
66Supply and fixing of "under/over voltage relay, 3 phase, 415 volts", for DG sets of capacity upto 250 KVA complete all as specified and directed by Engr-in-Charge.
67Supply and fixing in replacementof battery voltage relay 12 VDC complete all as specified and directed by Engr-in-Charge.
68Supply and fixing in replacement Battery 12volt 180 AH Code :- FXPO-MHD 1800.complete all as specified and directed by Engr-in-Charge.
69Supply and fixing in replacement Battery 12volt 65/75 AH Code :- EP.15-12(12M15).complete all as specified and directed by Engr-in-Charge.
70Supply and fixing in replecement of Electronic Microprocessor based controller unit suitable to DG set controlls & commands of DG set upto 62.5 KVA capacity with all listed parameters as per recomendation including testing complete all as specified and directed by Engr-in-Charge.
71Supply and fixing in replecement of Electronic Microprocessor based controller unit suitable to DG set controlls & commands of DG set 75 kva to 200 kva capacity with all listed parameters as per recomendation including testing complete all as specified and directed by Engr-in-Charge.
72Attendingofanybreakdown of standby supply in any location ,whenever required round the clock ,rectify the fault and restore the standby supply within three hour after receipt of complaint of any nature i.e. Engine, alternator,control panel,AMF panel etccomplete all as specified and directed by Engr-in-Charge. Note -(i) The cost ofreplaced spare parts will be paid and measured seperatly.(ii)If complaint is not attended by contractorwith in five hour the penality of Rs 500 / per hourto be imposed and amount of penality will be deducted from RAR. (iii) Thecost of transportation (to and fro) for all kind ofnecessary equipment / T&P shall be arranged/brought by contractor to complete the job at site or at E/M yard and no extra cost shall be paid to the contractor to this effect. (iv) Complaint shall be lodged by telephonically ,so contractor to specifythe telephone no who willreceive the complaint round the clock.
73Supply & Fix in replacement of change over switch FP200 Amps, side handle, 415 Volt, 4 pole completeall as directed by Engr-in-Charge.
74Supply & Fix in replacement of change over switch FP100 Amps, side handle, 415 Volt, 4 pole complete all as directed by Engr-in-Charge.
75Supply & Fix in replacement of change over switch FP63 Amps, Front handle, 415 Volt, 4 pole complete all as directed by Engr-in-Charge.
76MCCB 4 Pole, 415 V, fixed type, 100 Amps with breaking capacity 16 KA complete all as specified and directed by Engr-in-Charge.
77MCCB 4 Pole, 415 V, fixed type, 125 Amps with breaking capacity 16 KA complete all as specified and directed by Engr-in-Charge.
78MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge.
79MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and directed by Engr-in-Charge.
80Supply & fix in replacement for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 25 x 4 mmas earthing lead by means of bolts,nuts,chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common salt including PCC pit in PCC 1:2:4 type B-1,RCC covermade out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle andangle iron 40x40x5mm frame,GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 40 mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by Engr-in-Charge. Note: - (i)On testing after completion of earthing,if desired earth resistance is not obtained,the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge. (ii) Item includes the cost of 7.5 m GI pipe for protection of earth strip. (iii) PCC pits extra cost of addtional length of watering pipe, bends elbows etc.shall be deemed to be included in the quioted rate. (iv) Item includes the cost of 7.5 mtr length copper earth strip 25x4 mm.
81Supply & fix in replacement for earth continuity conductor or main earthing lead fixed to wall on batton or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to pole or any other indicated situation for loop earthing etc as required with 25X4mm galvanised iron strip complete all as specified and directed by Engr-in-Charge
82Dismantling /opening of alternator of DG Set by disconnection of cable connections and flexible coupling, nuts/boltsand alternator foundation nut, bolts including strip opening of alternator and checkingout burnt out parts of DG Sets of capacity10 KVA to 100 KVA and taken back in temporary platform complete all as specified and directed by Engr-in-Charge.
83Taking out burnt armature, winding wire and rewinding of armature with super enameled copper winding wire of existing gauge for10 KVA to 320 KVA set wire DG sets complete all as specified and directed by Engr-in-Charge.
84Taking out burnt field coil and rewinding of field coil with super enameled copper winding wire of existing gauge for10 KVA to 320 KVA sets complete all as specified and directed by Engr-in-Charge.
85Insulation of armature with Class ‘B’ insulation and Varnishing of armature winding and drying up to desired temperature for10 KVA to 100 KVA DG Sets complete all as specified and directed by Engr-in-Charge.
86Insulation of field coils with Class ‘B’ insulation and varnishing of field coils and drying up to desired temperature for10 KVA to 100 KVA Alternator ofDG Sets complete all as specified and directed by Engr-in-Charge.
87Burnt rectifier of size 2” x 2” x 24 plate (In replacement) set of three complete all as specified and directed by Engr-in-Charge.
88Re-assembling of rotor and stator after rewinding and re-fixing of Alternator with Engine by assembling flexible coupling with alternator mounting with nuts, bolts including making cable connection complete including testing and commissioning at desire load of DG Set of capacity10 KVA to 100 KVA complete all as specified and directed by Engr-in-Charge..
89Supply & Fix Anti vibration mounting pad for DG set upto 31.10 kva (set of 4) complete all as specified and directed by Engr-in-Charge.
90Supply & Fix Anti vibration mounting pad for DG set from 40 kva to 125 kva (set of 4) complete all as specified and directed by Engr-in-Charge.
91Carry out servicing from authorised rep or service engineer from the manufacturer of DG set of 320KVA,capacityMake : Cummins complete all as per OEM instructions and directed by Engr in Charge. Note : All the spare , parts , lubrication oil etc. has been measured and paid saperatly under respective item of schedule "A".
92All as per serial item No.95.00 here-in-before but of capacity 320 KVA DG set complete all as specified and directed by Engr-in-Charge.
93All as per serial item No.95.00 here-in-before but of capacity 250 KVA DG set complete all as specified and directed by Engr-in-Charge.
94Fuel filter primary and secondary suitablefor DG Set capacity 250KVA to 320KVA complete all as specified and directed by Engr-in-Charge.
95Supply onlylub oil filterbodysuitable for DG Setcapacity 250KVA to 320KVA complete all as specified and directed by Engr-in-Charge.
96Supply only Air cleaner elementsuitable DG Set for capacity 10KVA to 320KVA complete all as specified and directed by Engr-in-Charge.
97Inner Air cleaner elementsuitable DG Set for capacity 10KVA to 320KVA complete all as specified and directed by Engr-in-Charge.
98Supply only water filterbodysuitable for DG Setcapacity Upto 10KVA to 320KVA. complete all as specified and directed by Engr-in-Charge.
99Supply only Air cleander element suitable DG set for capacity upto 125KVA complete all as specified and directed by Engr-in-Charge.
100M&L for replacement of water circulating pump, for DG set of capacity 320 KVA including air supply connection pipe, clip, replacement of repair kit, calibration/ testing system complete, fitted with DG set properly in original position, checking the allignment, making proper all connection, testing for smooth opreation from authorised rep or service engineer from the manufacturer complete all as specified and directed by Engr-in-Charge.
101Material & labour for complete control wiring for connect all safety to controller/ AMF panel of 250 kva DG set & 320 KVA DG set carrying out complete servicing control panel,including checking and rewiring electrical circuit using FRLS copper conductor, for DG Set of any type / make / capacity, making all electric connections and testing for smooth operation, complete all as specified and directed by Engr-in-Charge.
102Supply and fixing in replacement of AVR S/F VARIABLE SPEED DCDGsuitable for DG set with input voltage range 415 Volt AC with neutral & Out put DC voltage suitable for DG set above 250 KVA to 320 KVA complete all as specified and directed by Engr -in-Charge.
103Supply & fix the following items of DG Set of various capacity :-
104Battery terminal, lug, bolts type suitable for heavy duty battery complete all as specified and directed by Engr-in-Charge.
105Battery leads for copper conductor multiwired 50 Sqmm Single Core complete all as specified and directed by Engr-in-Charge.
106Hinges for DG set door of any size, any type as required on site complete all as specified and directed by Engr-in-Charge.
107M&L for replacement of Lub oil pipe for DG set for capacity 15 KVA to 320 KVA complete all as specified and directed by Engr-in-Charge.
108M&L for replacement of tappet valve DG Set for capacity 15KVA to 320 KVA complete all as specified and directed by Engr-in-Charge.
109M&L for replacement of Fuel Pipe for filter (7.5,14x14B,700PB) for BIO Diesel DG Set for capacity 15KVA to 320KVA complete all as specified and directed by Engr-in-Charge.
110M&L for replacement of Fuel Pipe return( FIP TO TANK) for BIO Diesel DG Set for capacity 15KVA to 320KVA complete all as specified and directed by Engr-in-Charge.
111M&L for replacement of Residential Silencerfor DG Set for capacity upto 320KVA complete all as specified and directed by Engr-in-Charge.
112M&L for replacement of three phase Digital Voltmeter 0-500V AC complete all as specified and directed by Engr-in-Charge.
113M&L for replacement of three phase Digital Ammeter 30/5A(CTR) complete all as specified and directed by Engr-in-Charge.
114M&L for replacement of voltmeter selector switch complete all as specified and directed by Engr-in-Charge.
115M&L for replacement of Ampere meter selector switch complete all as specified and directed by Engr-in-Charge.
116M&L for replacement of V belt for fan pulley (set of 2Nos) for DG set upto 320 KVA DG Set complete all as specified and directed by Engr-in-Charge.
117M&L for replacement of V belt for alternator and water pump assembly for DG set upto 320 KVA complete all as specified and directed by Engr-in-Charge.
118M&L in replacement of unsv thermostat with new thermostat alongwith complete assy for DG set connection testing complete all as specified and directed by Engr-in-Charge.
119Material & labour for complete overhauling,servicing of turbo charger, opening /taking out of turbo charger of DG set of 15 KVA to 320 KVA capacity ,disconnection of air supplyconnection pipe etc, including replacement of turbo charger repair kit, calibration/ testing of turbo charger system complete and re-assembling the same ,fitted with DG set properly in original position, checking the allignment, making proper all connection, testing for smooth opreation from authorised rep or service engineer from the manufacturer complete all as specified and directed by Engr-in-Charge.
120M&L for replacement of Copper tube (Thimbles) terminal heavy dutyof size 185 Sq.mm complete all as specified and directed by Engr-in-Charge.
121M&L for replacement of Copper tube (Thimbles) terminal heavy dutyof size 150Sqmm complete all as specified and directed by Engr-in-Charge.
122M&L for replacement of Copper tube (Thimbles) terminal heavy dutyof size 120 Sq.mm complete all as specified and directed by Engr-in-Charge.
123M&L for replacement of Copper tube (Thimbles) terminal heavy dutyof size 95 Sq.mm complete all as specified and directed by Engr-in-Charge.
124M&L for replacement of Copper tube (Thimbles) terminal heavy dutyof size 70 Sq.mm complete all as specified and directed by Engr-in-Charge.
125Supply & fixing main switch with sheet steel enclosure 400 amps TPN, 415 volts with HRC/ re-wireable fuses complete all as directed by Engr-in-Charge.
126Supply & Fix in replacement of change over switch FP400 Amps, side handle, 415 Volt, 4 pole complete all as directed by Engr-in-Charge.
127Actuator ( in replacement)with spring (sedemac make) complete all as specified and directed by Engr-in-Charge.
128Dismantling /opening of alternator of DG Set by disconnection of cable connections and flexible coupling, nuts/boltsand alternator foundation nut, bolts including strip opening of alternator and checkingout burnt out parts of DG Sets of capacity125 KVA to 320 KVA and taken back in temporary platform complete all as specified and directed by Engr-in-Charge.
129Insulation of armature with Class ‘B’ insulation and Varnishing of armature winding and drying up to desired temperature for 125 KVA to 320 KVA DG Sets complete all as specified and directed by Engr-in-Charge.
130Insulation of field coils with Class ‘B’ insulation and varnishing of field coils and drying up to desired temperature for 250KVA to 320 KVA Alternator ofDG Sets complete all as specified and directed by Engr-in-Charge.
131Burnt rectifier of size 2” x 2” x 24 plate (In replacement) set of three complete all as specified and directed by Engr-in-Charge.
132Re-assembling of rotor and stator after rewinding and re-fixing of Alternator with Engine by assembling flexible coupling with alternator mounting with nuts, bolts including making cable connection complete including testing and commissioning at desire load of DG Set of capacity 125 KVA to 320 KVA complete all as specified and directed by Engr-in-Charge.
133Supply & Fix in replacement Single core, copper cable,70 sqmm, 1100 Volt suitable for existing DG set including propper connection from DG set to AMF Panel / Changeover complete all as specified and directed by Engr-in-Charge.
134Supply and laying in trenches/wall/airXLPE armoured under ground cable 1100 Voltmulti stranded aluminium conductor of 240 sqmm 3.5 core(excavation and earth work will be measured and paid seperately) complete all as specified and directed by Engr-in-Charge.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail