Tender For Repair To Services Distribution Feeder Pillar Terminating Junction And Services Mains In Domestic And Technical Area At Af Station Chandigarh, Chandigarh-Chandigarh

Military Engineer Services-MES has published Tender For Repair To Services Distribution Feeder Pillar Terminating Junction And Services Mains In Domestic And Technical Area At Af Station Chandigarh. Submission Date for this Tender is 07-07-2023. Feeder Pillar Tenders in Chandigarh Chandigarh. Bidders can get complete Tender details and download the document.




Tender Notice

38102490
Corrigendum : Tender For Repair To Services Distribution Feeder Pillar Terminating Junction And Services Mains In Domestic And Technical Area At Af Station Chandigarh
Open Tender
Indian
Chandigarh
Chandigarh
07-07-2023

Tender Details

Repair To Services Distribution Feeder Pillar Terminating Junction And Services Mains In Domestic And Technical Area At Af Station Chandigarh

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 17-Jun-2023 BOQ Corrigendum BOQ 30-06-2023
2 30-Jun-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 07-07-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 36000.0 /-
Tender Value
INR 18 Lakhs /-

BOQ Items

Name of Work: REPAIR TO SERVICES DISTRIBUTION FEEDER PILLAR TERMINATING JUNCTION AND SERVICES MAINS IN DOMESTIC & TECHNICAL AREA AT AF STATION CHANDIGARH
Sl. No. Item Description
1Excavation in trenches in soft/ loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation of pole, laying of cable etc. and getting out complete all as specified and directed.
2Excavation in trenches in hard/ dense soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation of pole, laying of cable etc. and getting out complete all as specified and directed.
3Returning and filling in excavated soil including spreading levelling, watering and well ramming in layers each not exceeding 25mm thick in soft/ loose soil all as specified and directed.
4Removing excavated surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5mtrs above the starting points complete all as specified and directed.
5M&L for sand cushioning to cables with a layer of sand 8cm deep before laying the cable and 15cm depth after laying & stretching of cable) complete all as specified. Note: Punned thickness overall 18cm shall be measured & paid.
6Supply and laying old size sub class ‘B’ bricks as in protection of cable laid dry flat perpendicular to direction of cable abutting each other complete all specified and directed.
7M&L for boring hole horizontally under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including supply & laying 150mm dia HDPE pipe suitable for 0.4 mpa working pressure complete all as specified and directed.
8Supply and laying GI tubing 50mm bore light grade GI tubing with all fitting laid in trenches or fixed to well etc. complete all as specified and directed.
9Supply and laying GI tubing 80mm bore light grade GI tubing with all fitting laid in trenches or fixed to well etc. complete all as specified and directed.
10Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 150 sqmm 3½ core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
11Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 sqmm 3½ core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
12Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 sqmm 3½ core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
13Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 sqmm 3½ core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
14Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sqmm 3½ core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
15Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 sqmm 3½ core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
16Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sqmm 4 core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
17Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm 4 core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
18Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm 2 core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
19S&F steel tubular swaged pole type 410 SP-31 (9.00 metre long) complete with cast iron base plate, finial, taper plug, bolts, nuts & screws including painting the pole upto 1.50m height above PCC with two coats of synthetic enamel paint in alternate layer of black & yellow colour of 30cm height each and the remaining portion of pole including swan neck with two coats of aluminium paint complete all as specified and directed.
20S&F in repairs street light bracket made out of 40mm dia medium grade GI tubing, 1.50m long, fabricated to required shape and angle as per site requirement with and including MS clamps size 30mm x 6mm with nuts, bolts, washers etc. complete all as specified and as directed.
21M&L for cement concrete (1:4:8) type D-2 using 40mm graded crushed stone aggregate in foundation filling & mass concrete for poles/ struts/ stays assembly including provision of necessary form work finishing the exposed surface even and smooth in cement mortar (1:3) and applying two coats of white wash to the portion of PCC muffs above ground level complete all as specified and directed.
22M&L for plain cement concrete (1:3:6) type C-1 using 20mm graded crushed stone aggregate for coping of poles including weathering, slightly rounded or chamfered angles and throating complete all as specified and directed.
23M&L for painting of electric pole upto 9m high complete with cross arm, clamps, channel etc. after cleaning exposed surfaces with two coat super enamelled paint as per existing colour i.e. Silver (Aluminium paint) and writing letters and pole Nos or figures (Block. Roman, Italic or Indian) n. exc. 30 cm high complete all as specified and directed.
24S&F in repairs digital type voltmeter 0 to 500 volts panel mounted with inbuilt selector switch complete all as specified and directed.
25Supply and fixing digital type ammeter 0 to 300 ampere panel mounted with inbuilt selector switch complete all as specified and directed.
26S&F in replacement LED indicator lamps in RBY colour complete all as specified and directed.
27Supply, install, test & commissioning factory made LT feeder pillar box of size 75cm x 75cm x 60cm with set of 4 strip copper bus bar 200 Amp, 1100 volt grade, 60cm long duly sleeved with relevant colored sleeved cubical outdoor type, weather proof, fabricated out 14 SWG MS sheet, welded on 40mm x40mm x 6mm angle iron frame & having four Nos 120cm long legs made out of 40mm x 40mm x 6mm angle iron below frame grouted on ground in concrete block of size 80cm x 80cm x 20cm built in PCC (1:2:4) of suitable size with front & rear openable door having locking arrangements, bottom space for cable entry with duly internally and externally painted with two coats of dark grey synthetic enamel paint over a coat of red oxide primer including dismantling and taking down existing feeder pillar box complete all as specified and directed.
28S&F in replacement of MCCB, 4 pole, 400 Amps, 36 KA, 50Hz, 415 volts with Ics= 100% of Icu complete with adjustable thermal & adjustable magnetic type relays completeall specified and directed.
29S&F in replacement of MCCB, 4 pole, 250 Amps, 25 KA, 50Hz, 415 volts with Ics= 75% of Icu complete with adjustable thermal & adjustable magnetic type relays completeall specified and directed.
30S&F in replacement of MCCB, 4 pole, 200 Amps, 25 KA, 50Hz, 415 volts with Ics= 75% of Icu complete with adjustable thermal & adjustable magnetic type relays completeall specified and directed.
31S&F in replacement of MCCB, 4 pole, 160 Amps, 25 KA, 50Hz, 415 volts with Ics= 75% of Icu complete with adjustable thermal & adjustable magnetic type relays completeall specified and directed.
32S&F in replacement of MCCB, 4 pole, 125 Amps, 25 KA, 50Hz, 415 volts with Ics= 75% of Icu complete with adjustable thermal & adjustable magnetic type relays completeall specified and directed.
33M&L for danger notice plate of size 20cm x 15cm fabricated out of 1.6mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size fixed in replacement complete all as specified and directed.
34S&F stainless steel (SS-304 grade) friction hinges of size 200mm long fixed to LT panels of approved quality, fixed by welding/ stainless steel screws etc. complete all as specified and directed.
35M&L for preparation of steel surface of panels and painting with two coat super enameled smoke grey paint complete all as specified and directed.
36S&F in repairs water proof ABS electric distribution box, whether proof IP-65 protection suitable for outdoor use, pole mounted, factory made of size 300mm x 250mm x 150mm comprising one No. MCB SP 6 Amps, 240 volts, TPN bus bar not less than 25mm x 5mm aluminium strip and fixing two No. clamps of size 25mm x 5mm including necessary nuts, bolts and locking arrangement with lock, pressure type, four No. connection holes in each bus bar with nuts, bolts and washers made of galvanized iron and connection thimble etc. complete all as specified and directed.
37S&F in replacement 2.5 sqmm FRLS PVC insulated copper conductor multistranded with cable thimble/ lugs made of copper in surface/ recessed as required for LT panel repair with necessary fixtures as required at site complete all as specified & directed.
38S&F in replacement ofaluminium thimbles/ lugs for LT cablesof following sizes :
3925 sqmm to 35 sqmm
4050 sqmm to 70 sqmm
4195 sqmm to 120 Sqmm
42120sqmm to 185 Sqmm
43240sqmm to 300 Sqmm
44Supply, installation, testingand commissioning in replacement LT cubical panel (CPRI Approved) of size 1000mm x 900mm x 650mm with set of 600 Amp, 4 strip bus bars duly sleeved with relevant colored insulation heavy duly mounted on insulators; factory made, compartment type, dust and vermin proof(IP-55) duly powder coatedoutdoor type suitable for 1100 volts grade, 3 phase, 4 wire supply, floor mounted fabricated out 3.15 mm MS Sheet on 50mm x 50mm x 6mm angle iron frame, 120cm long angle iron legs for grouting in floor with cement concrete PCC foundation of suitable size in (1:2:4) and front & rear double door type inclusive locking arrangement with provision of all incoming/ outgoing cable entries alongwith suitable size of double compression type cable gland for incoming & out going cable complete all as specified and comprising the following:-
45Incoming: (a) Digital MCCB AC, 4 pole, 400 Amps, 36 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 75% of ICu)- 01 No. Outgoing : (b) Digital MCCB AC, 4 pole, 200 Amps, 25 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 100% of ICu)- 01 No. (c) Digital MCCB AC, 4 pole, 100 Amps, 16 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 100% of ICu)- 01 No. (d) Digital MCCB AC, 4 pole, 63 Amps, 10 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 100% of ICu)- 02 Nos (e) Digital LED ammeter with CT’s 400/5 amps and selector switch- 01 No. (f) Digital LED voltmeter 0-500 volts with selector switch- 1No.. (g) Phase indicator lamps RYB- 01 Set. (h) Internal connections with colour code copper cable multistranded of suitable size copper thimbles etc. as per manufacturers design and specifications. (j) Danger notice plate 440 V with conventional skull and bones in red signal colour- 01 No. (k) Spare space for mounting 01 No. extra MCCB.
46Supply, installation, testingand commissioning in replacement LT cubical panel (CPRI Approved) of size 1000mm x 750mm x 550mm with set of 400 Amp, 4 strip bus bars duly sleeved with relevant colored insulation heavy duly mounted on insulators; factory made, compartment type, dust and vermin proof(IP-55) duly powder coatedoutdoor type suitable for 1100 volts grade, 3 phase, 4 wire supply, floor mounted fabricated out 3.15 mm MS Sheet on 50mm x 50mm x 6mm angle iron frame, 120cm long angle iron legs for grouting in floor with cement concrete PCC foundation of suitable size in (1:2:4) and front & rear double door type inclusive locking arrangement with provision of all incoming/ outgoing cable entries alongwith suitable size of double compression type cable gland for incoming & out going cable complete all as specified and comprising the following:-
47Incoming: (a) Digital MCCB AC, 4 pole, 200 Amps, 25 KA, 50 Hz, 415 volts with microprocessor release capacity(ICs = 75% of ICu)- 01 No. Outgoing: (b) Digital MCCB AC, 4 pole, 100 Amps, 16 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 100% of ICu)- 01 Nos. (c) Digital MCCB AC, 4 pole, 63 Amps, 10 KA, 50 Hz, 415 volts with microprocessor release capacity (ICs = 100% of ICu)- 02 No. (d) Digital LED Amps meter with CT’s 400/ 5 amps and selector switch- 01 No. (e) Digital LED Voltmeter 0-500 volts with selector switch- 1 No. (f)Phase indicator lamps RYB- 01 Set. (g) Internal connections with colour code copper cable multistranded of suitable size copper thimbles etc. as per manufacturers design and specifications. (h) Danger notice plate 440 V with conventional skull and bones in red signal colour- 01 No. (j)Spare space for mounting 01 No. MCCB.
48S&F indoor/ outdoor type heat shrinkable type cable jointing kit for LT 1100 volts grade cable for straight through joint complete with accessories suitable for 3½/ 4 core XLPE armoured aluminium conductor cable of size 25 to 50 sqmm complete all as specified and directed.
49All as per item No. 41.00 above but for cable of size 70 to 95 Sqmm.
50All as per item No. 41.00 above but for cable of size 120 to 150 Sqmm.
51M&L for replacement of earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5mtr below normal ground level connected to galvanised Iron strip of size 25mm x 4mm by means of bolts, nut check nuts and washers earth strip protected by galvanized steel pipe 40mm bore (light grade) connected to test point all as shown in electrical plate No. 3 of SSR (Part-I) and including necessary excavation and earth work in any type of soil, 20mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6) type C-1 chamber, pit cover of precast RCC (1:2:4) type B-1 reinforced XPM of weight not less than 4 Kg/ Sqm and MS frame etc, complete & connected to earthing test point all as specified or indicated including brazing/ testing on completion. Notes:- (i) The unit rate shall be deemed to include cost of galvanised iron strip and protection pipe upto 7.5 metre from earth plate to earth point/ test point. (ii) The complete earth system shall be guaranteed to give result less than 2 ohm resistance. (iii) Complete earthing will be redone at no extra cost to department, if result is found above 2 ohm.