}

Tender For Replacement Of Old Fluroscent Fittings And Additional Led Fittings In Class Rooms And Corridors And Other Electrical Works Etc As Reqd At Govt. Girls Secondary School, Tigri, (Dr. Ambedkar Nagar, Sec-Iv) New Delhi-110062 (School Id-1923080, Delhi-Delhi

Public Works Department-PWD has published Tender For Replacement Of Old Fluroscent Fittings And Additional Led Fittings In Class Rooms And Corridors And Other Electrical Works Etc As Reqd At Govt. Girls Secondary School, Tigri, (Dr. Ambedkar Nagar, Sec-Iv) New Delhi-110062 (School Id-1923080. Submission Date for this Tender is 13-06-2023. Flurocent Light Tenders in Delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

38030764
Tender For Replacement Of Old Fluroscent Fittings And Additional Led Fittings In Class Rooms And Corridors And Other Electrical Works Etc As Reqd At Govt. Girls Secondary School, Tigri, (Dr. Ambedkar Nagar, Sec-Iv) New Delhi-110062 (School Id-1923080
Open Tender
Indian
Delhi
Delhi
13-06-2023

Tender Details

Replacement Of Old Fluroscent Fittings And Additional Led Fittings In Class Rooms And Corridors And Other Electrical Works Etc As Reqd At Govt. Girls Secondary School, Tigri, (Dr. Ambedkar Nagar, Sec-Iv) New Delhi-110062 (School Id-1923080).

Key Value

Document Fees
Refer document
EMD
INR 41913.0 /-
Tender Value
INR 20.95 Lakhs /-

BOQ Items

Name of Work: RMO of E.I. & Fans in Main Court Building at District Court Saket, New Delhi.(SH: Providing Services of Computing and official work)
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
2Group C
3Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.
4Group C
5Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.
6Group C
7Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
83 x 1.5 sq. mm
93 x 4 sq. mm
10Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
113 Module (100 mmX75 mm)
126 Module (200 mmX75 mm)
1312 Module (200 mmX150 mm)
14Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
1520 mm
1625 mm
17Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
1815/16 A switch
196 pin 15/16 A socket outlet
20Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
21Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
2212 way, Double door
23Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
248 way (4 + 24), Double door
25Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
26Single pole
27Single pole and neutral
28Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required
29SITC of surface/ wall mounted 2x18/20 W LED 4 feet MS CRCA box type batten fitting with 2 nos. 18/20 Watt LED tubes should have polycarbonate housing for better heat desipation to work more than 50000 hours at 70% light output. Total system Lumen of 18/20 Watt LED should be 100 lumen per watt or more in cool day light (5700K to 6500K), power factor>0.95,CRI>80, THD should be less than 10%, high bright white power LED of Nichia/ osram/ cree/philips with LM 80 test reports, LM 79 test reports and LED photo biological safety report for fittings complete with mounted brackets & accessories as required i/c fixing, connections etc. complete as required.
30Supply and fixing of 10 watt LED Bulk Head fitting of PDC deffiuser material-glass the LED bulk head shall have color rendering index: 70, color temp: 5000 - 6000 k, Power factor > 0.95, CRI>70%, driver efficiency > 85%, IP66, Color: cool white, LED efficiency shall be less than 100 Lumens per watt with minimum burning of 50000 etccomplete as reqd.
31SITC of surface/ wall mounted Blackboard 1 X18 watt LED Tube 4 feet long MS CRCA box type batten fitting including protection cover with 1 no. 18 Watt LED tube should have polycarbonate housing for better heat dissipation to work more than 50000 hours at 70% light output. Total system Lumen of 18/20 Watt LED should be 100 lumen per watt or more in cool day light (5700K to 6500K), power factor>0.95, CRI>80, THD should be less than 10%, high bright white power LED of Nichia/ osram/ cree/ philips with LM 80 test reports, LM 79 test reports and LED photo biological safety report for fittings complete with mounted brackets & accessories as required i/c fixing, connections etc. complete as required.
32Supplying, installation, testing & Commissioning of pre-wired 150 Watt LED Flood light luminaire with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion with minimum lumens of 110 per watt suitable for cool day white light having minimum Color temp in the range 6000K to 7000K, Power factor > 0.95, CRI>70%, driver efficiency > 85%, Surge protetion line to line - 5 KV & line to ground 10 KV, Working lifetime: >50000hours , IP rating = IP 66 ,Thermal & impact registance > IK-06complete with all accessories etc directly on ceiling/wall/pole including connections with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and earthingetc as required.
33Suppyling, Installation, Testing and commissioning S.M.C junction box GS-JB-3020 complete withterminal block suitable for 25 sq. mm conductor, SP MCB with suitable. M.S. clamp on the existing pole for street light cable as reqd.
34Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required
35Supplying, laying and fixing of following size PVC insulated and PVC sheathed/ XLPE aluminum conductor armoured power cable of 1.1 KV grade in following manner etc. as reqd.
36a) 3 x10 sq.mm on wall surface
37Fabrication, Installation, Testing and Commissioning of floor mounting compartmentallised cubical panel boardminimum 300 mm depth with locking arrangement front openable, totally enclosed,dust & vermin prooffabricated out of 2mm thick cold rolled carbon annealed, sheet steel, with 400 Amp 4 strip Al. bus bar, cable alley on both sides, powder coated paint of approved shade and 2 nos 25x5mm copper strips throughout the width of panel consisting of two earth studs on each strip complete with following incoming and outgoing switchgears including making connections/ inter connections with lugs/ thimble for switchgears and control wiring with 2.5 sq.mm PVC insulated FRLS copper conductor cable, including providing 50mm X 50mm X 6 mm thick Angle base upto 300 mm above ground level including necessary grouting / fixing on floor ( Drawing shall be got approved from Engineer-incharge before fabrication complete etc as required.
38Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required
39200 A, 25 kA,TPMCCB (Ics=100%Icu)
40100 A, 16 kA,TPMCCB (Ics=100%Icu)
41Supply & fixing of following accessories in the existing cubical type M.S. panel board i/c drilling holes in cubical panel, making connections etc as reqd.
4263 A, 10 kA,TPN MCB C-Curve
43Digital Ammeter, 36 mm sq. CT operated with Selector switch 1 set, CT"s of Suitable ratio, VA burden and accuracy of class 1.0
44Digital Volt Meter (0-500 V) 96 mm. Sq. with Selector Switch-1 Set
45LED type indicating light (RYB)
46Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required
47Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
48Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required
49Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail