| 1 | SH-I Man Power |
| 2 | Provision of Manpower for smooth functioning of Electrical Maintenance & Operation of E.I, Compound light of the offices, premises, canteen and other locations of the entire Sanchar Bhawan Building etc. The manpower will work as electrical enquiry to receive complaints from Officers/ Offices at different locations and to attend the fault/restore the Power supply/ breakdown maintenance against the supply of material either by the department/agency except minor modification/ alternate arrangement, etc. complete in all respect to the entire satisfaction of Engineer-in-charge.Note: Manpower may be asked to work at other locations also and in any shift without any extra cost as per requirement under the jurisdiction of EE(E) /SDE (E), BSNL. Decision of Engineer-in-charge will be final. Note : Staff required (not above the age of 55 years) : |
| 3 | Skilled Manpower having valid electrical licence/ permit – 06 nos. |
| 4 | Unskilled Manpower capable to assist inall type of electrical works – 06 nos. |
| 5 | SH-II (Supply of Material/Items) |
| 6 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required |
| 7 | Group C |
| 8 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required. |
| 9 | 2 x 1.5 Sq.mm + 1 x 1.5 Sq.mm earth wire |
| 10 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. |
| 11 | 3 x 1.5 sq. mm |
| 12 | 3 x 4 sq. mm |
| 13 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. |
| 14 | 20 mm medium class PVC conduit |
| 15 | 25 mm medium class PVC conduit |
| 16 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required |
| 17 | 5/6 amps switch |
| 18 | 15/16 amp switch |
| 19 | 3 pin 5/6 amp socket outlet |
| 20 | 6 pin 15/16 amp socket outlet |
| 21 | Bell push switch |
| 22 | Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. |
| 23 | 3 Module (100mmX75mm) |
| 24 | 4 Module (125mmX75mm) |
| 25 | 6 Module (200mmX75mm) |
| 26 | 8 Module (125mmX125mm) |
| 27 | 12 Module (200mmX150mm) |
| 28 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. |
| 29 | 1 run of cable |
| 30 | Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. |
| 31 | 4 Pair |
| 32 | Supply & fixing of following accessories etc. as required: |
| 33 | Call Bell Ding Dong type |
| 34 | S/F of following sizes of pvc casing and capping etc. complete as reqd. |
| 35 | 25mm x 16mm |
| 36 | 32mm x 16 mm |
| 37 | 50mm x 16mm |
| 38 | S/F of wooden type Extension board for operating of electrical apparatus having following polycarbonate electrical accessories including making inter-connection with suitable size of pvc insulated copper wire etc. complete as reqd. (Accessories make: Anchor/ Cona/ Finolex/Polycab)Wooden box of size 8\"x13\" with 3 mm thick phenolic laminated sheetSwitch 15 amp. - 2 Nos.Socket 15 amp. 6 pin - 2 Nos.Switch 5 amp. -2 Nos.Socket 5 amps. -2 Nos.3C x 2.5 Sqmm Cu Flexible cable - 2 Metre.Plug Top 15 amps. - 1 No. |
| 39 | S/F of following Flexible pipe etc. complete as reqd. |
| 40 | 25 mm PVC |
| 41 | S/F of following size PVC insulated, PVC sheathed copper conductor round flexible cable of 1.1 KV Grade etc complete as reqd. |
| 42 | 3 x 1.5 Sqmm |
| 43 | 3 x 2.5 Sqmm |
| 44 | 2 x 1.5 Sqmm Twin Flat Cable-White |
| 45 | S/F of following LED Fittings etc. complete as reqd. a) Wattage : As per detail below + 10%b) System lumens efficacy : Not less than 110 lumen per wattc) Driver efficiency : Not less than 85%, d) CRI : Not less than 80e) LED Life : Not less than 50000 hours @ LM 70%f) Colour temperature : 5500 - 6500 K g) Operating voltage range : 160 Volt to 270 Volth) Installation type : Wall / Ceiling surface installationi) Material of construction for housing : Polyuminum die cast j) Internal surge protection : Not less than 2.5 kVk) Ingress protection (IP): Not less than 20. |
| 46 | 9/10w, 6500K, 600mm long LED tube with batten/box |
| 47 | 5 watt, LED Down lighter fittings (surface/recess) ( In round / square shape) |
| 48 | 15 watt, LED Down lighter fittings surface type (In round shape) with white powder coated polycarbonate housing and pressure die cast sink with heavy duty driver having THD <10% etc complete as reqd. |
| 49 | S/F of fancy type engagement light fitting having three sides metallic casing and glass/ PVC sheet cover at front including red & green 0.5w LED lamps (B-22 base etc. complete as required. |
| 50 | S/F of 20 watt surface / suspended 1200mm long LED batten alongwith in built electronic driver suitable for operation on 230 V, 50 Hz A/c supply complete etc as reqd. |
| 51 | SITC of surface/recess mounting following sizeLED luminaries having high brightness SMD LED light source/recess suitable for operation on 230v 50Hz AC power supply complete with all accessories including connections with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthling as reqd (with 5 year wattenty)a) 18-42Wattb) System lumens efficacy : Not less than 120 lumen per wattc)Driver efficiency : Not less than 85%d)THD : Not more than 10%e)CRI : Not less than 80f)UGR : Less than 19%g)LED Life : Not less than 50000 hours @ LM 70%h)Colour temperature : 5500 - 6500 K i)Operating voltage range : 140 Volt to 270 |
| 52 | 34 W 2\" X 2\"LED Panel Recess type {M/s Phillips / Havells (VENUSNEOHE2X2PLR18-42WLED857MOD) or Wipro)} |
| 53 | 34 W 2\" X 2\"LED Panel Surface type |
| 54 | 36 W 4\" X 1\"LED Panel |
| 55 | SITC ofheavy duty Exhaust fan of 450 mm 1400 RPM suitable for operation on 230V, 50 Hz single phase AC Supply in the existing opening etc complete as reqd. (Make: Almonard/ Crompton/ Havells/ Usha/ Orient) |
| 56 | Supply and fixing of following type heavy duty exhaust/ wall/ ceiling/ pedestal fans suitable for operation on 230V, 50 Hz single phase AC Supply i/c dismentaling/ refixing, minor civil works if reqd. making connection testing and commissioning etc complete as reqd. (Make: Almonard/ Crompton/ Havells/ Usha/ Orient) |
| 57 | 400 mm sweep, 1350 rpm, Plastic body wall fan |
| 58 | 400 mm sweep, 1350 rpm, Padestal fan |
| 59 | 150 mm sweep, 1350 rpm, fresh air fan |
| 60 | 250 mm sweep, 1350 rpm, fresh air fan |
| 61 | 300 mm sweep, 1350 rpm, fresh air fan |
| 62 | Supplying and fixing of following sizes Aluminium raceway with accessories/fittings, on surface as required. |
| 63 | 100 x 50 mm |
| 64 | SITC of DP sheet steel enclosure on surface/recess along with 25/32 A, 240 V “C” curve DP MCB complete as required. |
| 65 | Supply & fixing 5 A to 32 A rating, 240/415 volts, 10 kA, \"C\" curve,MCBsuitableforinductiveloadof following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 66 | Single Pole |
| 67 | Double Pole |
| 68 | Supply & fixing following isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 69 | 40 A, Double Pole, 240 V |
| 70 | 63 A, Double Pole, 240 V |
| 71 | 63 A, Four Pole, 415 V |
| 72 | 100 A, Four Pole, 415 V |
| 73 | SITC of 100A, 16 kA, TP MCCB with terminal spreaders and thermomagnetic release in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
| 74 | Supply & fixing following sheet steel MCBDB,on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) |
| 75 | 6 way , 240v SPN, Double door |
| 76 | 12 way, 240v SPN, Double door |
| 77 | 16 way, 240v SPN, Double door |
| 78 | 4 way (4+12), 415v, Horizontal, TPN, Double door |
| 79 | 8 way (4+24), 415v, Horizontal, TPN, Double door |
| 80 | 4 way (4+12), 415v, Vertical, TPN, 200A tinned copperbusbar, Double door |
| 81 | Remarks:1.Manpower will be deployed by the agency at site to receive the complaints and for co-ordination for the work. For this, one mobile no. with whatsapp facility will be provided by the agency.2. Adequate inventory of material will be kept at site by the agency for prompt attending the complaint.3. Complaint received in Fore Noon will have to be attended by After Noon and complaints received in Afternoon will have to be attended by Forenoon of next day. Emergency complaints, if any, will have to be attended immediately at any time including odd hours.4. Penalty of Rs. 500/- per complaint per day will be imposed for non-compliance of the complaint. If at any stage, it is observed that the performance of agency is not adequate, work will be rescinded, and the agency will be debarred from doing any work for one year in Delhi region. The work will then be carried out at his risk and cost without serving any notice6.The Agency should quote amount keeping in view all Statutory requirements including minimum wages/ESI/EPF etc.n in column 17 are correct & credit of GST for the amount shown in column 14 above are admissible as per GST Laws. |
| 82 | Note:-1. 1. The Agency has to submit police verification record & ID proof of each staff.2. The firm shall provide each staff with working cell phone.3. The staff may be deputed for duty as per instruction of concerned SDE (E)/JTO (E).4. Penalty shall be imposed in case of absence of any staff as per T & C of contract.5.The GST / other Input Tax Credit (ITC) taxes shall be quoted by the firm as applicable as per latest amendments of GST Rules.6.The contractor shall provide correct tariff heads & other details to enable BSNL claim Input Tax Credit.7.Bidder must mandatorily quote for all GST components (CGST, SGST, and IGST) as required.8. If annual maintenance contract charges are required to be quoted as per SOW, basic charges should be shown in column 4 & the Goods and Service Tax (GST) in column 7 to 12.9. The bidder who submits the offer with concessional Goods and Service Tax (GST) shall submit the proof of applicable concessional GST. In case the Concessional GST is not creditable to BSNL it should be included in the price of the goods/services.10. In case, dealer is registered under compounding scheme or any rule/notification where the BSNL is not eligible for input tax credit then the bidder should not disclose any amount in column 7 to12 & 14.11. % age Rate of FF & Packing should be shown of basic unit price excluding all taxes & charges (i.e. as %age of col.4).12. The FF & packing amount quoted shall not be subject to change after bid evaluation /ordering on account of change of copper, lead base price, change in duties & taxes of item etc.13. Bidder must mandatorily mention HSN & SAC numbers.14. Evaluation of bids: - The evaluation and comparison of responsive bids shall be done on the basis of Net cost to BSNL on the prices of the goods & Services (i.e. complete work) offered along with all applicable Taxes, packing Forwarding Freight & Insurance charges etc. exclusive of GST.Declaration by Bidder1.We hereby declare that in quoting the above prices, we have taken into account the entire credit on inputs available under the GST Act introduced w.e.f. 1 July 2017 and further extended on more items till date.2. We hereby certify that HSN/SAC shown in column 17 are correct & credit of GST for the amount shown in column 14 above are admissible as per GST Laws.Name of bidder:Seal of Company: GST No./(s)ST Laws. |