Tender For Electrification Work Of New Multistoried Godown At State Warehouse Muthalamada In Palakkad District Under Nabard Wif Scheme
Tender Value
7.38 Lakhs
Estimated cost
Bid Submission
09 Jun 2023
0 days left
EMD
18500
Bank guarantee accepted
Document Fee
1770
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
muthalamada → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Electrification Work Of New Multistoried Godown At State Warehouse Muthalamada In Palakkad District Under Nabard Wif Scheme
BOQ
| Sl. No. | Item Description |
| 1 | ELECTRIFICATION |
| 2 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLSPVC insulated copper conductor single core cable etc as required.Group C |
| 3 | Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire |
| 4 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm |
| 5 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm |
| 6 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire |
| 7 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or inrecess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 ampsmodular switch, connection etc. asrequired. (For light plugs to be used in non residentialbuildings). |
| 8 | 1x20 W LED box type tube fitting .The fittings shall be made from CRCA MS sheet of minimum thickness 0.50mm nominal thickness inside & outside (including LED Tube) |
| 9 | Supply ,installation ,testing and commissioning of 450mm 18 inch sweep heavy duty ,1400rpm ,230 v ,410w ,4 nos blades and metal frame ,single phase exhaust fan . |
| 10 | Supply, testing and fixing of 150mm 240v exhuast fan |
| 11 | Supplying and fixing 9Watt LED Bulb |
| 12 | Supply of 1200 mm sweep electric Ceiling fan capacitor type with double ball bearing with canopies, <br> shackles, blades suitable for operation on 240volt, 50Hz, single phase AC supply conforming to IS-<br>374/1979 class I (without regulator) LMR |
| 13 | Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required. |
| 14 | 10 sqmm 4 core PVC/XLPE insulated armoured cable with aluminium conductors for working voltages up to and including 1100 volts conforming IS 1584/part I/1988 for PVC IS 7098 part I for XLPE |
| 15 | Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB\"s (butwithout MCB\"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)12 way (4 + 36), Double door |
| 16 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator)8 way (4 + 24), Double door |
| 17 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door |
| 18 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.100 amps |
| 19 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 20 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 21 | Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps |
| 22 | Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps |
| 23 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole |
| 24 | Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole and netural |
| 25 | Fabrication supply and installation of dust and vermin proof /wall mounting synthetic meter box of suitable size for fixing KSEB meter ,fuse unit etc .hinged and door construction for the front size with compartment if necessory providing vision panel for the meter compartment , knock outfor cable energy and exit required quantity of rubber beeding painting the entire board with 2 coatsof synthentic enamel paint over a coat of zink chromate primer fixing it on the wall making good the damages colour washing etc. as required. 63A 415V Porcelain unit-3 nos<br>63A MCB ISOLATOR 4 POLE<br>63A 415V neutral link - 1 no. |
| 26 | Supply, installation,testing and commissioning of vertical type 230 V single phase energy meter box , vision panel,dust protected ,sintex box ,common neutral link, earth bar,63 A bakelight fuse unit HRC,32A neutral link,40A isolator |
| 27 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providingmasonry enclosure with cover plate having locking arrangement and watering pipe etc. withcharcoal/ coke and salt as required |
| 28 | Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing asrequired. |
AI Tender Summary
Tender Timeline
Jun 02, 2023
11:30 IST
Tender Published
Tender notice published.
CompletedJun 09, 2023
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedJun 12, 2023
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer