Tender For Repairs, Replacement, Maint Of Digital Water Level Indicator, Water Level Monitoring Panels, Communication Panels, Ultrasonic Level Sensors, Transmitters Along With Motor Actuated Butterfly Valves, Solenoid Valves Under Ge Belgaum, belgaum-Karnataka

Military Engineer Services-MES has published Tender For Repairs, Replacement, Maint Of Digital Water Level Indicator, Water Level Monitoring Panels, Communication Panels, Ultrasonic Level Sensors, Transmitters Along With Motor Actuated Butterfly Valves, Solenoid Valves Under Ge Belgaum. Submission Date for this Tender is 15-06-2023. Level Sensors Tenders in belgaum Karnataka. Bidders can get complete Tender details and download the document.




Tender Notice

37962113
Tender For Repairs, Replacement, Maint Of Digital Water Level Indicator, Water Level Monitoring Panels, Communication Panels, Ultrasonic Level Sensors, Transmitters Along With Motor Actuated Butterfly Valves, Solenoid Valves Under Ge Belgaum
Open Tender
Indian
Karnataka
belgaum
15-06-2023

Tender Details

Repairs, Replacement, Maint Of Digital Water Level Indicator, Water Level Monitoring Panels, Communication Panels, Ultrasonic Level Sensors, Transmitters Along With Motor Actuated Butterfly Valves, Solenoid Valves Under Ge Belgaum

Key Value

Document Fees
INR 500 /-
EMD
INR 96000.0 /-
Tender Value
INR 48 Lakhs /-

BOQ Items

Name of Work: REPAIRS, REPLACEMENT, MAINT OF DIGITAL WATER LEVEL INDICATOR, WATER LEVEL MONITORING PANELS, COMMUNICATION PANELS, ULTRASONIC LEVEL SENSORS, TRANSMITTERS ALONG WITH MOTOR ACTUATED BUTTERFLY VALVES, SOLENOID VALVES UNDER GE BELGAUM
Sl. No. Item Description
1Supply only Single phase PreventorModel 1-VSP D2, Supply Voltage:100-120/220-240/380-440 V AC ± 20% 50/ 60 Hz, Output Contacts- 2 CO, Phase Sequence: Possible complete all as specified and as directed .Note: Make: Minilec ( VSPD2) or Equivalentmodel in Schneider / Select / L&T
2Supply only Relay with base 4 C/O / 24 V DC, complete all as specified and as directed .Note :Make: OMRON/SALZER/SCHNEIDER/IDEC/LEONE
3Supply only Relay with base 4 C/O /240 V DC , complete all as specified and as directed .Note :Make: OMRON/SALZER/SCHNEIDER/IDEC/LEONE
4Supply only LED Indicator Colour/Red /yellow/Green. Supply Voltage: 230 V, complete all as specified and as directed .Note :Make:SCHNEIDER/ESBEE/TELEMECHANIC /L&T
5Supply only Programmable Logic Controller Power supply: 24VDC (-15%to ~ 20%) Inrush current: Max. 2.2A@24VDC Power consumption: 6 W Operation /storage:Operation: 0ºC ~ 55ºC (temperature); 5 ~ 95% (humidity); Pollution degree 2 Storage: -25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity) complete all as specified and as directed .Note :Make: : Delta/Mitsubishi/Siemens/ABB/UNITRONIC
6Supply only I/O module forProgrammable Logic Controller Input voltage (±10%): 24VDC, 5mA complete all as specified and as directed .Note :Make: Delta/Mitsubishi/Siemens/ABB/UNITRONIC
7Supply only HMI for Programmable Logic Controller Size: 4.3", RAM: 16 MB, Flash Memory:16 MB complete all as specified and as directed .Note :Make: Renu/ Mitsubishi/Siemens
8Supply only Push button with LED Indicator - 240 V A.C. Colour/Red/yellow/Green. complete all as specified and as directed .Note :Make: SCHNEIDER/ESBEE/TELEMECHANIC /L&T
9Supply only motorised Solenoid Valve25mm dia , 230 VAC.complete all as specified and as directed .Note :Make:Johnson control/ AVCON/Honeywell
10Supply only motorised Solenoid Valve10mmdia , 230 VAC. complete all as specified and as directed .Note :Make:Johnson control/ AVCON/Honeywell
11Supply only Coil for Solenoid Valve 25mm dia 230 V AC. complete all as specified and as directed .Note :Make: Johnson control/ AVCON/Honeywell
12Supply only Coil for Solenoid Valve 10 mm dia 230 V AC. complete all as specified and as directed .Note :Make:Johnson control/ AVCON/Honeywell
13Supply only Magnetic Level switch. Type: Magnetic Magnet: Ring type Switch: Reed Switch (Epoxy sealed) Connecting Cable: Teflon complete all as specified and as directed .Note :Make:Rkom/Techtrol/ Sapcon
14Supply only Pressure Transmitter Power supply: 10-36 V DC Process connection: G ½ “ Enclosure: whether proof Process temperature: up to 50 degree Accuracy: 1 % complete all as specified and as directed .Note :Make: Danfoss/ Siemens/ E+H/Indfoss
15Supply only Electric motor suitable for actuator of size 80 mm dia bore. Input Voltage : 230 V AC Out put watts: 90 to 250 Nominal Current: 0.5 to 1.2 A, Class of Insukation: F Ambient Temperature: 45 degree. complete all as specified and as directed .Note :Make: Rkom/SD Tork/Emtork/ Rotork
16All as per the description in item No.15 here in above but actuator of size 100 mm bore dia
17All as per the description in item No.15 here in above butactuator of size 150 mm bore dia
18All as per the description in item No.15 here in above butactuator of size 200 mm bore dia
19All as per the description in item No.15 here in above butactuator of size 250 mm bore dia
20Supply only Butterfly valvesize 80 mm dia bore. Designed line pressure: 10 kg/sq cm. Operating Angle: 90 degrees Disc Material: CI with nylon coating complete all as specified and as directed .Note :Make: AUDCO/ KBL/IVC/AVK
21All as per the description in item No.20 here in above but Butterfly valve of size 100 mm bore dia
22All as per the description in item No.20 here in above but Butterfly valve ofsize 150 mm bore dia
23All as per the description in item No.20 here in above but Butterfly valve ofsize 200 mm bore dia
24All as per the description in item No.20 here in above but Butterfly valve ofsize 250 mm bore dia
25Supply only Capacitor for Actuator suitable for 80 / 100 / 150 /200/250 mm dia Motorized Butterfly Valve as per samplecomplete all as specified and as directed .
26Supply only Resistor for Actuator suitable for80 / 100 / 150 /200/250 mm dia motorized Butterfly Valve as per sample complete all as specified and as directed .
27Supply only Hand Wheel for Actuator suitable for fallowing size Butterfly Valvefor the size 80/100 dia bore as per sample complete all as specified and as directed .
28Supply only Hand Wheel for Actuator suitable for fallowing size Butterfly Valvefor the size 150/200/250 dia bore as per sample complete all as specified and as directed .
29Supply only Limit switch for Actuator suitable for 80 / 100 / 150/200/250mm dia motorized Valve.complete all as specified and as directed . Note :Make :CHERRY / L&T / SIEMENS
30Supply only Ultrasonic Level Sensor. Range 200 mm - 6 Metre Input: 10-30 V dc Outputs: 2 Discrete NPN or PNP 2 m (6.5 ft) Cable. .complete all as specified and as directed . Note :Make : Bannar/ Siemens/ E+H / SBEM
31Supply only GPRS Comunnication Modem (ii) GPRS - Class 10. (iii) Voice/Data/FAX/SMS facility (iv) TCP/IP - Full ( FTP & E Mail add) Functional Features (i) Input/output Digital -01 (ii) Down load over the air (iii) At command set ( GSM 07.05, GSM 07.07 and Wave com)>300 (iv) Auto restore -time reset. Temp Range (i) Operating range - 20+55 degreec/ -25 to 70 degree C (ii) Power supply -5 to 32 V DC (iii) Protection Class-IP 55 (iv) Certification -CE Certification, GCG Certification, ROHS Compliance. .complete all as specified and as directed . Note :Make : ROBUSTEL / TELTONIKA / LEON / MAESTRO
32Supply only 9DB Antenna For GPRS Modem as per sample
33Supply only MCB 4P 6A. C series ,10 KA Make: Havells/Schneider/L&T
34Supply only MCB 2P 6A C series ,10 KA Make: Havells/Schneider/L&T
35Supply only Selector switch - 2Way Make: Esbee/Teknic/Schneider
36Supply only Selector switch - 3Way Make: Esbee/Teknic/Schneider
37Supply only SMPS AC Input Voltage: 170 ~ 270 V. Stable Output Voltage (V DC): 24. Output Current (Amp): 5. Output Power (Watt): 120. Make: NHP/Schneider/Telemecaniqee
38Supply and fix Motor Actuated Butterfly Valve consisiting of suitable single phase Actuator and butterfly valve of size 80 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. complete all as specified and as directed Specifications Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Material of Disk : CI Limit Switches : 02 Nos for open and close status. Mounting :Indirect Make: EMTORK/MARSH/RITETORK
39Supply and fix Motor Actuated Butterfly Valve consisiting of suitable single phase Actuator and butterfly valve of size 100 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure. Specifications Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Material of Disk : CI Limit Switches : 02 Nos for open and close status. Mounting :Indirect Make: EMTORK/MARSH/RITETORK
40Supply and fix Motor Actuated Butterfly Valve consisiting of suitable single phase Actuator and butterfly valve of size 150 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure complete all as specified and as directed Specifications Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Material of Disk : CI Limit Switches : 02 Nos for open and close status. Mounting :Indirect Make: EMTORK/MARSH/RITETORK
41Supply and fix Motor Actuated Butterfly Valve consisiting of suitable single phase Actuator and butterfly valve of size 200 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure complete all as specified and as directed Specifications Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Material of Disk : CI Limit Switches : 02 Nos for open and close status. Mounting :Indirect Make: EMTORK/MARSH/RITETORK
42Supply and fix Motor Actuated Butterfly Valve consisiting of suitable single phase Actuator and butterfly valve of size 250 mm dia with appropriate bracket/mounting arrangement including two nos. limit switches for open and closed condition and splash proof enclosure.complete all as specified and as directed Specifications Input Voltage: 230 V, A.C. Designed line pressure: 10 kg/sq cm. Material of Disk : CI Limit Switches : 02 Nos for open and close status. Mounting :Indirect Make: EMTORK/MARSH/RITETORK
43Supply, installation, testing and commisioning of PLC basedwater level monitoring panel with ultrasonic sensor(01 Nos) Non Contact type to monitor the water level for 1 No. OHT in percentage from 0% to 100% . The Panel should have the provision for 02 Nos motorized valve operation for the future .PLC based Panel should consist of 4" HMI for Local monitoring of the Level.The PLC should have the following feature: Inputs: 32 Nos, Outputs: 32 Nos Analog Input: 02 Nos . Panel Box fabricated from 1.6 mm thick CRCA sheet and properly powder coated to operate the water supply system.Panel also equipped with GPRS communication Modem along with suitable external antenna of suitable gain, patch chord and mounting accessories . The cost shall include the cost of communication for a period of 12 months from the date of completion of work complete all as specified and as directed Make : Rkom /Siemen/Schneider LOCATION: Parade Ground Pump House= 02 Nos, OHT at MLIRC= 01 No.
44Supply and fix on floor/roof/wall GalvanizedIron Cable Tray superior quality of size 100 mm x 50 mm including cost of all fixing arrangements as directed
45Supply only Float type point level sensor magnetic type as per sample
46Supply only Ultrasonic Level Transmitter fixing onOHT and UG sump including all fixing arrangement with IP 67 protection complete all as sopecified and as directed.Note : The Ultrasonic Level Transmitter shall consists of rhe following technical specifications : (i)Range : 0-6 metres (ii)Accuracy : 0.5 % minimum (iii)Supply Voltage : 24V dc (iv)Output : 4-20 mA Note :Make ofUltrasonic Level Transmitter: SCHNEIDER / SIEMENS /BANNER
47Maintenance, repairs, replacement of sparesincluding SCADA Server system, computer, printer as required for all the modernised water supply infrastructure but excluding spare parts and as described below under GE Belgavi as follows. (b) Repair/maintenance by disconnecting cleaning greasing for wear and tear complete servicing,refixing,lathing installing and commission as directed by Engr-in Charge of all motorised and solenoid valves, Pressure Transmitters , Ultrasonic and magnetic Level sensors, The scope of work also covers; (i)Any changes in the Programmable Logic Controller(PLC), e.g. Changes in ladder logic of programme, changes in operational timing, etc. (limited to the scope of items covered under this AMC) (ii)Any changes to the SCADA software, e.g. Changes in report format, changes in operational screens, creation of soft keys etc. (limited to the scope of items covered under this AMC) (iii) SCADA reports related to all the systems to be mailed to AGE/JE on every week. (1)To attend break down maintenance( within 4 hours of reported time) and replacement of unservicable spare parts as required at site
48Note (i) All components/spare parts mentioned in this BOQ replaced shall bepart of this work and does not comes under warranty period of original workand fixing charges of their of shall deemed to be include in this item,nothing extra shall be admissible on this account. (2) All the calls related to unservicability/ break down of the system should be attend with in 4 hours, if failed so a penalty of Rs 1000/- can be imposed on each day untill the system gets repaired.
49Note: a)The servicing of Motorised valve, PLC base control Panels shall be done by authorized representative of the Manufacturer only. The technician shall submit a letter from the manufacturer as proof of his being a authorized representative of the manufacturer. The technician shall also submit a signed report on original letterhead of the manufacturer that servicing as been carried out by him.b)Any changes to the Programmable Logic Controller(PLC), e.g. Changes in ladder logic of programme, changes in operational timing, etc. (limited to the scope of work covered under this AMC) shall be carried out by authorized representative of the Manufacturer of PLC based Panels only. The programmer shall submit a letter from the manufacturer as proof of his being an authorized representative of the manufacturer. The programmer shall also submit a signed report on original letterhead of the manufacturer that servicing as been carried out by him.
50c)Any changes to the SCADA software, e.g. Changes in report format, changes in operational screens, creation of soft keys etc. (limited to the scope of work covered under this AMC) shall be carried out by authorized representative of the Manufacturer of PLC based Panels only. The technician shall submit a letter from the manufacturer as proof of his being a authorized representative of the manufacturer. The technician shall also submit a signed report on original letterhead of the manufacturer that servicing as been carried out by him. (d) Memorandum of Understanding: The tenders shall submit memorandum of understanding (MOU) from the original equipment manufacturer of the PLC based control panels,to provide technical support and trained persons for maintenance and operation with the tender documents.If he fails to submit MOU along with the tender documents on date of receipt of tender and if he happens to be the lowest, he will be given 15 days time from the date of receipt of the tender to submit the same, if he further fails to submit the same with in 15 days from the date of receipt of the tender,his offer will be deemed revoked and Earnest money shall be forfeited/recovered , In addition such tenderer and his related firm/firms shall not be issued the subject tender in second call or subsequent calls . NOTE :- The spares required to replace against this item shall be not part of this work and comes under warranty period of original work
51Material and labour forRolled mildsteel framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering doors, sluice valve pitcover and frame, sheet, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings and hanging; also fastening and fixing confirming to Fe 290 E -165 including Preparation of new steel surfaces and applying two coats of metalic paint over a coat of metalic primer complete all as specified and as directed.
52Supply ,fix andtesting PVC insulated armoured copper cable of size4 core , 1.5 sqmmfor connecting power supply to digital box complete all as specified and as directed. Make -Polycab/Havells/ Finolex
53Supply ,fix andtesting PVC insulated armoured copper cable of size 6 core , 1.5 sqmm for connecting power supply to digital box a complete all as specified and as directed. Make -Polycab/Havells/ Finolex
54Supply and fix double compression steel gland ofsize 16 mm
55Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for foundation, laying pipe etc. and getting outin any type of soil complete all as specified and as directed.
56Returning filling in excavatedsoil including spreading levelling watering and well ramming in layers n.exc 25 cm thick complete all as specified andas directed.
57Removing excavated soilto a distance not exceeding 50 m and depositing where directed at a level n.exc. 1.5 m above the starting point complete all as specified and as directed.
58Material and labour forEarthing complete with galvanised earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly in ground in vertical position, earth pit not less than 2.25 Metre deep below ground level with top edge of the plate not less than 1.5 Metre below ground level connetced with galvanised iron earthing strip of size 25 mm x 4 mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead protected by galvanised iron pipe 40 mm bore (medium grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessaryexcavation & earth work, returning filling and removal of surplus earth upto a distance not exceeding 50 Mtr etc all as shown on electrical plate No. 3 ofMES Schedule Part-I complete to obtain less than 1 Ohm earth resistance, fiaxed in repairsincluding taking out existing old unservicableearthing materials of any description and taken as credit complete all as specified and as directed..
59NOTE : (i) Cost of this items includes the scope of earth work viz :charcoal, salt, PCC, RCC pit cover of required size. (ii) Unit rate of this items includes the cost of galvanised iron strip upto 7.5 metre. After 7.5 metre, strip shall be measured and paid for separately.
60Supply and fix Double wall corrugated high density polymer (SDR 17)of ISI marked 63 mm outer dia and 50 mm inner dia including necessary fittings like couplers,bends,end caps etc with ISI marked (IS 14930- 2001 ), laid in trenches /floors & fixed on wall/ pole withand including necessary fittings such as bends, sockets & other connected accessories etc forlaying of electric cables / road crossings etccomplete all as specified and as directed. Make - Duraline, Rex,Ketron.
61Material and labour forPlain cement concrete 1:3:6type C2, using 40mm graded stone aggregate in foundation, filling, mass concrete, levelling courses and sub bases complete all as specified and as directed.