| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 13-06-2023 | Corrigendum for BOQ and Tender Document | Other | 20-06-2023 |
| 2 | 13-06-2023 | Corrigendum for BOQ and Tender Document | BOQ | 20-06-2023 |
| Sl. No. | Item Description |
| 1 | M&L for roof treatment in order of precedence as given below complete all as specified and as directed:-(i) Taking out of existing water proofing treatment and including padding, cleaning the surface using wire brush, brooming down and washing down with water to remove dust etc, and brushing with neat cement slurry @ 3.00 kg of cement per Sqm.(ii) 15 mm thick screed bed in CM 1:4 on surface.(iii) Cleaning of plastered surface and applying one coat of bituminous primer @ 0.40 Ltr / Sqm.(iv) Supply and laying 3 mm (Minimum) thick APP based polymeric membrane of approved manufacturer with weight not less than 3.60 Kg per Sqm, reinforced with non-woven polyester fabric weight not less than 150 gms per Sqm. Polymeric membrane shall be taken to a height of 30 cm (minimum) and then inserted inside the groove of parapet wall and shall be finished by a membrane flashing.(v) Applying one coat of water proofing paint with aluminium finish over APP as per manufacturer\"s instruction.Note :- (a) Bituminous primer shall be \"ShaliTex Primer\" manufactured by M/s STP Ltd or equivalent in M/s Sika India Pvt Ltd or M/s Fosroc Chemicals or M/s Hindcon chemicals limited or M/s IWL India Limited(b) Laying APP based polymeric membrane shall be done by torch on method as per manufactures instructions. (c) A minimum overlap of 100 mm and 75 mm should be made at the end and sides of the polymeric membrane respectively and all overlaps and joints shall be sealed as per manufacturers instruction.(d) APP based polymeric membrane shall be “SUPER THERMOLAY” manufactured by M/s STP Ltd or “WP Shield” manufactured by M/s Sika India Pvt Ltd or equivalent of M/s Fosroc Chemicals or M/s Hindcon chemicals limited or M/s IWL India Limited(e) Water proofing paint shall be by M/s STP Ltd or M/s Sika India Pvt Ltd or M/s Fosroc Chemicals or M/s Hindcon chemicals limited or M/s IWL India Limited |
| 2 | S&Fin repairsSteel rolling shutters oflaths thicknes 1.25 mm, with out ball bearing, as specified incluidng top cover, anchrong rod, hasp and staple and one shop coat of primer; errected in position as indicated, complete; gear operated type with bevel gear box and crank handle etc. all as directed and specified by Engr-in-Charge. |
| 3 | Taking down by unfastening all part of steel rolling shutter of any size viz hood cover, curtain of steel lathe etc and oiling, greasing the pully, shaft incl adjusting the spring, V-clamp, bracket plate and manual operated box along with pipe ends arrangement and refixing the same in same opening for making operative complete all as specified and as directed |
| 4 | M&L making good broken / damaged RCC chajjas with PCC 1:2:4 type B1 or cement mortar 1:3 and including rendering 15 mm thick in CM 1:4 mixed with water proofing compound as per manufacturer\"s instruction to top, sides and soffits, including necessary scaffolding, formwork upto 3 storey height complete all as specified and directed.Note:- Water proofing compound shall be measured and paid seperately |
| 5 | M&L brick work withsub class\"B\" brick, straight or curved on plan exc. 6 m mean radius built in CM 1:6 including demolition complete all as specified and directed. |
| 6 | Taking down plastering on lathing (other than wire-netting), without removing lathing, in cement mortar |
| 7 | M&L Rendering 10 mm thick on concrete surfaces as in ceiling in cement mortar 1:3 for finished even and smooth (without using extra cement). |
| 8 | M&L Rendering 15 mm thick on other than fair faces of brick work or concrete sur-faces in cement mortar 1:6 for finished even and smooth (without using extra cement) . |
| 9 | M&L Rendering 15 mm thick on fair faces of brick work or concrete sur-faces in cement mortar 1:4 using water proofing compound (as per manufacturer instruction)finished even and fair(without using extra cement) (WPC will be measured and paid separately) |
| 10 | Supply only Liquid water proofing compound. |
| 11 | M&L for white washing 3 Coat on newly plastered ceiling surfaces incl preparation. |
| 12 | M&L for prepration of new plastered surfaces ofwall/ceiling applying two coat of oil emulsion distemper over a coat of primer over coat of wall care putty for obtained smoothness of wall surfaces complete all as specified and directed. |
| 13 | M&L Preparation of wall surfaces and applying two coats of Cement base paint over one coat of alkali resistant primer all as directed by Engr-in-Charge. |
| 14 | M&L preparing old wooden surfaces of any description, not otherwise describe over 10 cm width or girth and applyingone coat of synthetic enamel paint over pink primer all as specified. |
| 15 | Preparation of old decorated steel surfaces of any description, not otherwise description over 10cm widthor girth and applying one coat of synthetic enamelled paint complete all as specified. |
| 16 | M&L Machine cut kota stone slab flooring 20-25mm thickover and including 20 mm thick Screed bed/bedding layer of 1:6cement mortar laid as floor and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete incl necessary dismantling offloor tiles. |
| 17 | Taking down of LT cable XLPE insulated UG cable of sizes 10 Sqmm to 150 sqmm size complete all as specified and directed. Note:- Excavation, returning filling, removing paid seperately under relevent item. |
| 18 | Supply,laying testing and commissoningof LT cable in repair XLPE insulated with FRLS loading factor on inner and outer sheath of Extruded PVC andwire armoured electric power cables (hevy duty) with aluminium conductor 1100 volts grade of size 10 sqmm 4 corecomplete all as specified and directed.Make Havells/ Gloster/Finolex/PolyCab |
| 19 | Supply,laying testing and commissoningof LT cable in repair XLPE insulated with FRLS loading factor on inner and outer sheath of Extruded PVC andwire armoured electric power cables (hevy duty) with aluminium conductor 1100 volts grade of size 16 sqmm 4 corecomplete all as specified and directed.Make Havells/ Gloster/Finolex/PolyCab |
| 20 | Excavation in trenches in any type of soil (soft/loose soil) not exceeding 1.5 metre wide and not exceeding 1.5m in depthLT under ground cables/GI pipes for trenches, complete all as specified and directed. |
| 21 | Returning, filling in, including spreading watering and well ramming in layers not exc 25cm in layers, complete all as specified and directed. |
| 22 | Removal of surplus soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point, complete all as specified and directed. |
| 23 | M&L sand coushioning to UG cables (8cm deep before laying of cables and 15 cm over the cable)including spreading, levelling, well ramming in layersNOTE:- punned thickness of 18cm only will be considered for payment purpose. |
| 24 | Supply and fix sub class \"B\" bricks of standard sizefor cable protection in trenches/ all as specified and directed. |
| 25 | Supply and fixing GI tubing light grade 15 mm dia for protection pipe for fixing along the pole with necessary clamps, nut bolt washers including taking down old unsv ones complete all as specified and directed .Make Jindal steel/ Tata or equivalent. |
| 26 | Supply and fixing GI tubing light grade 40 mm dia for protection pipe including taking down old unsv ones complete all as specified and directed .Make Jindal steel/ Tata or equivalent. |
| 27 | Boring/Drilling (horizontally) manually under 2m deep in soilbelow existing road suitable for passing GI tubing of 40 to 80 mm bore complete all as specified. |
| 28 | S&F street light junction box made from CPRI approved factory having size 200 (Width) x 150 (Depth) x 250 (Height) mm (minimum dimensions) made out of 2.00 mm thick CRCA sheet, duly powder coated of approved shade over a coat of red oxide primer both internally and externally, with rain shed all side except back side, comprising of 02 nos copper bus-bar of size 20 x 4 mm mounted on suitable size spacer insulators, necessary cable entry / exit holes for upto 35 sqmm cables, nut-bolts, MS clamps of suitable size for fixing including dismantling complete all as specified & as directed.Make - Havells/L&T/Hager/Crompton/Surya Roshni Ltd. |
| 29 | S&F in repairs 6 KW, three phase, automatic street light control panel with and including digital timer switch for automatic switching on / off street light as per set time through programmable 24 hour switch, 32A, TP power contactor, 40A SPN MCB, wall / floor mountable, IP 54 (dust and vermin proof) enclosure made out of CRCA sheet duly powder coated, conforming to IS/IEC 60954-4-1, in-built- short circuit protection, locking arrangement with padlock and panel lock complete all as specified and directed.Make:- Havells / GE / Kakatiya energy system Pvt Ltd/Surya Roshni Ltd. |
| 30 | M&L PVC Insulated Weather proof multicore FRLS PVC sheathed multistranded cables with bright annealed copper conductor of size 1.5 sqmm 3 corefor connection oflight to pole boxcompleted all as specified and directed .Make Havells/ Gloster/Finolex/PolyCab |
| 31 | S&F in repair LED street light 70 watt made up of pressure die cast aluminium housing environment friendly with high efficiency LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07. System Lumen Efficasy =120 Lm/W, 10 kV Surge Voltage Protection, Operating Voltage range 140 V - 270 V, Make of LED - Cree/Nichia/Osram/Agilent/Lumileds etc and including fixing arrangement made out of 40 mm bore GI pipe light grade of length not less than 1.2 m, bent to shape, fixed with two pairs of 40 x 5 mm MS flat iron clamps, nuts, bolts & washers to fix the fitting with pole complete all as specified and directed.Note :Contractor have to submit LM 79 and LM 80 report from NABL accredited Lab,Test Certificate and other relevant documents as directed by Engr-inCharge before approval of product. Note: 1.Contractor have to submit LM 79 and LM 80 report from NABL accredited Lab,Test Certificate and other relevant documents as directed by Engr-inCharge before approval of product. 2. Cost of taking down old unsv fittings is deemed to be included in unit quoted rates.Make :- Havells/ Crompton/Philips/HPL /Surya Roshni Ltd. |
| 32 | S&F in repair LED street light 90 watt made up of pressure die cast aluminium housing environment friendly with high efficiency LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07. System Lumen Efficasy =120 Lm/W, 10 kV Surge Voltage Protection, Operating Voltage range 140 V - 270 V Make of LED - Cree/Nichia/Osram/Agilent/Lumileds and including fixing arrangement made out of 40 mm bore GI pipe light grade of length not less than 1.2 m, bent to shape, fixed with two pairs of 40 x 5 mm MS flat iron clamps, nuts, bolts & washers to fix the fitting with pole complete all as specified and directed.Note :1.Contractor have to submit LM 79 and LM 80 report from NABL accredited Lab,Test Certificate and other relevant documents as directed by Engr-inCharge before approval of product. 2. Cost of taking down old unsv fittings is deemed to be included in unit quoted rates.. Make :- Havells/ Crompton/ Philips/HPL/Surya Roshni Ltd. |
| 33 | S&F in repair Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium LED Flood Light 120 watt, Tempered protective toughened glass with IP66, and impact resistant with IK07, System Lumen Efficasy =120 Lm/W, 10 kV Surge Voltage Protection, , Operating Voltage range 140 V - 270 V including fixing arrangement fixed with two pairs of 40 x 5 mm MS flat iron clamps, nuts, bolts & washers to fix the fitting with pole complete all as specified and directed.Note: 1.Contractor have to submit LM 79 and LM 80 report from NABL accredited Lab,Test Certificate and other relevant documents as directed by Engr-inCharge before approval of product. 2. Cost of taking down old unsv fittings is deemed to be included in unit quoted rates.Make :- Havells/ Crompton/Philips/HPL/Surya Roshni Ltd. |
| 34 | S & F in repair LED Bulk Head fitting 10 watt with Injection molded polycarbonate housing IP66, IK10, 3.5kV inbuilt surge protection, PF =0.95,total System Lumens 1100 lm, 6500k CRI = 80, Operating Voltage range 140 V - 270 V. complete all as specified and as directed. Make- Havells, Cat No - RUGBYGENXFTS10WLED865SSYMBOPC or equivalent / Crompton/ Philips/ HPL/Surya Roshni Ltd. |
| 35 | S & F in repair LED Bldg Security Light ,30 watt made up of pressure die cast aluminiun housing with highly efficient LEDs and PC cover with integrated lens with IP66, IK07, System Lumen Efficasy =120 Lm/W,having unique air vent technology which keeps temperature low, 5 kV Surge Voltage Protection,Operating Voltage range 140 V - 270 V and includingbracket suitable for street light made out of GI pipe light grade of 25 mm bore & 0.75 mtr length (minimum), bend to shape including 2 pairs of MS flat iron clamps made out of 40 x 5 mm MS flat, nuts, bolts & washers etc,& painting the bracket with two coat of aluminium paint over a coat of red oxide primer complete all as specified and as directed. Make : Havells Cat No - VILUMINASL30WLED75PASYBOPC or equivalent Crompton/ Philips/ HPL/Surya Roshni Ltd. |
| 36 | S & F in repair Recess Mounted Round LEDDownlighter 15 watthaving slim edge with die cast aluminium housing finished in premium white powder coating& PC Opal diffuser with integral Electronic LED Driver. IP20, PF =0.95,total System Lumens Efficiency not less than110 lm/W and color temp 5700k CRI = 80, Operating Voltage range 140 V - 270 V.complete all as specified and as directed.Make : HavellsCat No - GLOWDLR15WLED830S or equivalentCrompton/ Philips/ HPL/Surya Roshni Ltd. |
| 37 | S & F in repair Surface Mounted Round LEDDownlighter 15 watthaving slim edge with die cast aluminium housing finished in premium white powder coating& PC Opal diffuser with integral Electronic LED Driver. IP20, PF =0.95,total System Lumens Efficiency not less than120 lm/W and color temp 5700k CRI = 80, Operating Voltage range 140 V - 270 V.complete all as specified and as directed.Make : Havells Cat No - GLOWDLS15WLED830S or equivalent Crompton/ Philips/ HPL/Surya Roshni Ltd. |
| 38 | S&F Recessed Mounted Square (2\"x2\") LED Panel light 36 wattsuitable for mounting with Armstrong/Grid ceiling with CRCA powder coated housing & high transmittance Opal diffuser for glare free with Electronic LED Driver. IP20, PF =0.95, System Lumens =120 lm/W, 5700k CRI = 80, Operating Voltage range 140 V - 270 V.complete all as specified and directed.Make- Havells Cat No- PLANO2X2PLR36WLED840S or equivalent Crompton/ Philips/ HPL/Surya Roshni Ltd. |
| 39 | S&F in repairs 20 watt LED post top lantern, IP-65, die cast aluminium housing, opal diffuser, electronic driver fixing arrangementetc complete all as specified and directed.Make:-Havells / Crompton/ Philips/ HPL/Surya Roshni Ltd |
| 40 | S&F 1 x 9/10 watt LED bollard light fitting, IP-65, including 1 metre hot dip galvanized pole, driver, all fixing arrangement etc. including electrically connecting & taking down complete all as specified and directed.Note: 1.Contractor have to submit LM 79 and LM 80 report from NABL accredited Lab,Test Certificate and other relevant documents as directed by Engr-inCharge before approval of product. 2. Cost of taking down old unsv fittings is deemed to be included in unit quoted rates.Make:-Havells / Crompton/ Philips/ HPL/Surya Roshni Ltd |
| 41 | S&F 50 Watt , 3 meter long LED Tri Colour Light Column with die-cast aluminium pipe housing with cylindrical opal polycarbonate diffuser designed for rugged outdoor usaseandIP-65 protection with Tricolour and tratic white output switch, driver, all fixing arrangement etc. including electrically connecting & taking down complete all as specified and directed.Note: 1.Contractor have to submit LM 79 and LM 80 report from NABL accredited Lab,Test Certificate and other relevant documents as directed by Engr-inCharge before approval of product. 2. Cost of taking down old unsv fittings is deemed to be included in unit quoted rates.Make:-Bajaj, Cat- BLSLC 50W LED TRI 3M or eqivalent Havells / Crompton/ Philips/ HPL/Surya Roshni Ltd |
| 42 | S&F Solar All in One system 30 WSmart Integrated Solar Street Light with Built in Mono Crystalline Panel, Lithium Ferro Phospate (LiFeP0 4 ) 12.8V 24Ah Battery, MPPT Charge Controller and PIR Sensor with Colour Temperature 6000-6500K Suitable LED efficacy to have system efficacy of not less than 125 Lumen/Watt and Life of LED light fitting Not less than 50000 burning hours including fixing accessories like clamps of suitable size at existing pole and dismentaling out old unsv ones complete all as specified and as directed.Note: 1.Contractor have to submit LM 79 and LM 80 report from NABL accredited Lab,Test Certificate and other relevant documents as directed by Engr-inCharge before approval of product.2. Contractor will undertaking about warranty certificate of 50000 hr burning life.3. Cost of taking down old unsv fittings is deemed to be included in unit quoted rates.Make:-Havells / Crompton/ Philips |
| 43 | S & F in repair 8 Watt Suspended Spot Light , having black powder coated aluminium housingand pressure die castheat sink having high efficiency opal diffuser with integral Electronic LED Driver. IP20, PF =0.95,total System Lumens Efficiency not less than110 lm/W and color temp 5700k CRI = 80, Operating Voltage range 140 V - 270 V.complete all as specified and as directed.Make : Havells Cat No- UNECOPENDDLP8WLED830S24BLK or equivalent Crompton/ Philips/ HPL/Surya Roshni Ltd |
| 44 | Supply onlyFlexible LED Stripsof length 5 meter with optimum brightnedd & uniformity of light for perfect cove lighting having high efficiency opal diffuser with integral Electronic LED Driver. IP20, PF =0.95,total System Lumens Efficiency not less than110 lm/W and color temp 5700k CRI = 80, Operating Voltage range 140 V - 270 V.complete all as specified and as directed.Make : Havells Cat No- FLEXISTRIP5MIP2024V/2ALED830MODV1 or equivalentCrompton/ Philips/ HPL. |
| 45 | M&L preparation of 9 m long old steel poles with connected cross arms, cable protection pipes, clamps, street light brackets etc, and including applying one coat of aluminium paint on complete height of the pole and including applying one coat of synthetic enamel paint upto 0.80 m height from the top of coping with multi colour strips as per existing colour code complete all as specified and directed. |
| 46 | All as above item but for 11 mtr long HT Pole |
| 47 | M&L repairs to existing LT panel / bus bar chamber / feeder pillar boxof any size by excavation of all loops and removing damaged UG cable, connecting new thimbles / lugs / cable glands and fixing of new neoprene rubber gasket to make it completely dust and vermin proof, fixing of new locking arragement and replacement ofLT panel wiring with appropriate size of copper conductor, repairing of rusted parts of panel frame and shutter with necessary welding works including preparation and applying one coat of synthetic enamel painton both internal and external surface of panel, PCC (1:3:6) type C2 (using 40mm crushed stone aggregate) work in foundation complete all as specified and directed.Note:-The unit rate quoted is deemed to include cost of earth work, PCC in foundation, new thimbles / lugs / cable glands, neoprene rubber gaskets, locking arrangement, Wiring, welding works, painting. |
| 48 | S & F in replacement of RCC pole with Steel Tubular Poles complete with and including cast iron base plate , finial taper plug, bolts , nuts & screws, type 410 SP-31(9 Mtr long), also including painting to the external exposed surfaces with 2 coats of aluminium paint over 1 coatof red oxide primer and with 2 coats of black bituminous paint over 1 coat of red oxide primer to the external exposed surfaces of steel poles embedded in the ground / concrete after preparation of the surfaces, numbering to the poles, including taking down of old damaged RCC pole complete all as specified and as directed, Make JINDAL STEEL/NATIONAL TUBING CO/BOMBAY TUBE & STORE/CALCUTTA POLES & TUBE)Note:- Excavation & Earth Work, concrete for foundation and coping shall only be measured and paid for separately. |
| 49 | Material and labour for PCC 1:4:8 type D2 (using 40 mm graded aggregate) as in foundation of poles including necessary form work, finishing the surface even and smooth without using extra cement complete all as specified and as directed. |
| 50 | Material and labour for PCC 1:3:6 type C2 (using 40 mm graded aggregate) as in foundation of poles including necessary form work, finishing the surface even and smooth without using extra cement complete all as specified and as directed. |
| 51 | Material and labour for PCC 1:2:4 type B2 (using 20 mm graded aggregate) as in coping/stay of poles including necessary form work, finishing the surface even and smooth without using extra cement complete all asspecified and as directed. |
| 52 | Supply,installing, testingand commissioningout door type LT feeder piller box of suitable size, padestal mounted, OEM own factory made, supplied by OEM, floor mounted, LT 415 V AC, 50 HZ, 3-phase 4 wire, AL Busbar chamber and PVC sheathed rating 400 Amps with color coding mounted on DMC insulator, confirming to protection class IP-54 weather and vermin proof. Panel will complianceIEC 61439, Mechanical Impact IK10. Double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet for outer portionand 2.0 mm CRCA sheet for inner portion, framing with 50 x50 x 6 mm thick MS angle iron and legs of size 0.90m long, duly fabricated and having front hingled opening, rubber lining locking arrangement in both front and rear door with 4 side slanting roof duly projected and painted internally and externally with powder coating (RAL -7032) suitable for 500 volts, 50 Hz, 3 phase 4 wire system, internal wiring with single copper conductor cable/PVC insulated tinned copper strip of suitable size for incoming to busbar and busbar to MCCBs/MCBs, fine wiring with single core copper conductor cable for instruments/indicating lamps and comprising with and includingfollowing accessories and mounted on PCC Plat form made out of PCC 1:3:6, 100 mm thick, 1 Mtr all round the panel board complete with the following items housed in including taking down old unsv one complete all as specified and directed by Engr-in-Charge. Note:(1) The OEM’s specified cannot authorize to any other partner/sub vendor to manufacturing the panel ontheir behalf. (2) The LT panel will manufactured by OEM own factory only will be accepted & factory acceptance test(FAT) will be carried out at OEM plant only. (3) Panel maker should be CPRI approved with 10 tank process & IK10.Make of Panel and Accessories: ABB / Seimens / Schneider / BCH |
| 53 | INCOMING:- |
| 54 | (a) MCCB 4 pole 415 volts 35 KA breaking capacity rating 250 Amps, Ics=100% Icu, adjustable overload and adjustable short circuit setting, thermal magnetic type along with spreader terminals including fixing accessories :- 01 No |
| 55 | BUSBAR:- |
| 56 | (b) Aluminium busbar suitable for 400 Amp including insulator with nuts & bolts - 04 Nos |
| 57 | OUTGOING:- |
| 58 | (c) MCCB 4 pole 415 volts 25 KA breaking capacity rating 100Amps Ics=100% Icu, adjustable overload and adjustable short circuit setting, thermal magnetic type along with spreader terminalsincluding fixing accessories - 01 No |
| 59 | (d) MCCB 4 pole 415 volts 16 KA breaking capacity rating 63 Amps Ics=100% Icu, adjustable overload and adjustable short circuit setting, thermal magnetic type along with spreader terminalsincluding fixing accessories- 02 No |
| 60 | (e) MCB TPN 40 Amps,10 KA, \"C\" curve 240 volts - 01 Nos |
| 61 | (f) MCB SPN 32 Amps, 10 KA, \"C\" curve 240 volts - 02 Nos |
| 62 | (g) Lexic indicator lamp with holder= 03 nos |
| 63 | (h) Digital Amp-meter with built in selector switch - 01 No |
| 64 | (i) Digital Voltmeter of range with built in selector switch - 01 No |
| 65 | (j) CT of ratio 250/5 |
| 66 | (k)Time switches 250 V single Phase of 20 Amp rating with contactor |
| 67 | Supply only electronic driver for LED light of folloeing specifications: - |
| 68 | For 9 to 12 W LEDlight indoor type. Make as per existing. |
| 69 | For 12 to 15 W LED light indoor type. Make as per existing. |
| 70 | For 34 to 36 W LED light indoor type. Make as per existing. |
| 71 | M&L for point wiring for light points / fan points controlled by one, one way switch with (FRLSH) PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sqmm, with PVC insulated unsheathed stranded copper conductor cable of size 1.5 Sqmm stranded for earth continuity wire, to be drawn in and including , PVC medium grade Concealed conduit not less than 20mm dia with modular flush box, modular plate and frame all necessarywall cutting and making good disturbed surface complete all as specified and as directed. Note 1: - Red/yellow/blue colour cable should used for phase connection,Black colour cable should be used for neutral connection and green cable should be used for earthing connection, separate cable for earthing and neutral to be used for each individual circuit from the distribution board/Switch board.Note 2: - Joints in wire/cable in between switch board and points are not allowed.Note 3: - Circuit from DB for 15 A points, light points and 5 A points shall be shall be separate and independent.Note 4: - All socket points shall be provided to Table top hight for easy of operation.Note 5: - All earth wire shall be terminated to DB\"s Earth Bus for further connection with earth pit. Make of wire and conduit pipe: - As per approved make list |
| 72 | All as per item No 71 here-in-before but for 5 pin 15 Amps switch socket combination on independent board with 2.5 Sqmm cable for phase neutral and earth. |
| 73 | All as per item No 71 here-in-before but for 3 pin 5 Amps S/Socket pt. on independent board with 1.5 sqmm cable for earth, neutral and phase. |
| 74 | All as per item No 71 here-in-before but for 3 Pin socket outlet 5 Amps same board with other switches with cable 1.5 Sq mm size |
| 75 | S & F Modular type switch piano 6 Amps single pole one way one moduleall as specified and as directed. |
| 76 | S & F Modular type switch piano 16 Amps single pole one way one module for 16A independent complete all as specified and as directed. |
| 77 | S & F modular type Socket outlet 6 Amps 2/3 pin combined 2 module complete all as specified and as directed. |
| 78 | S & F modular type Socket outlet 16 Amps-2/3 pin combined 2 module complete all as specified and as directed. |
| 79 | S & F for ceiling rose surface Bakelite 65 x 50mm three terminal.Make: - As per approved make list |
| 80 | S & F modular type electronic fan regulator flush type 230V, AC, 50 Hz not less than 100 W complete with connection |
| 81 | M &L for sub main wiringwithPVC insulated(FR-LSH) cable standard copper conductor 1100 volts grade with two run of of size 2.5 sqmm multistrand unsheathed (Red/yellow blue colour cable used for live connection & Black colour cable used for neutral connection) and one run of 2.5 sqmm copper multistrand conductor 1100 volts grade PVC insulated (Green colour cable used) cable for earth continuity wire connected from main earth through PVC casing capping/PVC concealed conduit of size 25 mm for including of all accessories complete all as specified and directed. Note :i)Three runs of 2.5 sqmm cable with conduit pipe/ casing capingshall constitute one unit |
| 82 | M &L for sub main wiringwithPVC insulated(FR-LSH) cable standard copper conductor 1100 volts grade with two run of of size 4.0 sqmm multistrand unsheathed (Red/yellow/blue colour cable used for live connection & Black colour cable used for neutral connection) and one run of 4.0 sqmm copper multistrand conductor 1100 volts grade PVC insulated (Green colour cable used) cable for earth continuity wire connected from main earth through PVC casing capping/PVCconcealed conduit of size 25 mm for including of all accessories complete all as specified and directed. Note :i)Three runs of 4.0 Sqmm cable with conduit pipe/ casing capingshall constitute one unit |
| 83 | Supply and fix in repair of surface & wall mounted LED tube light fittings 4 feet with 18/20 w indoor luminaries with and includingElectronic driverandLED lamp, pre-wired including necessary electric connection from ceiling rose to light fitting on existing point or new points all as directed by the Engr-in-Charge, conforming to the following specifications: - |
| 84 | System Watts/lumens: - 18- 20 W/Total system lumen not less than 2000 Lm. |
| 85 | Housing: - Extruded polycarbonate |
| 86 | IP rating: - IP 20 |
| 87 | Front cover: - Acrylic/polycarbonate cover frosted |
| 88 | Mounting: - Suitable for wall/ceiling mounting |
| 89 | Finish: - Smooth finish |
| 90 | Lamp: - High bright LED |
| 91 | System Efficacy (lm/Watt): - Not less than 100 lm/watt |
| 92 | Colour temperature: - Not less than 5700 K |
| 93 | Colour rendering index (CRI): - Not less than 80 |
| 94 | Life: - Not less than 25000 hrs of operation |
| 95 | Optics: - Designed for optimum light distribution |
| 96 | Control gear: - Inbuilt electronic driver with APFC, PF not less than 0.95, and THD not more than 20% of the standard operating voltage 180-270V Ac, 50 Hz |
| 97 | Surge protection: - Inbuilt surge protection minimum 2 KV |
| 98 | Heat sink: - As per OEM\"s design |
| 99 | M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to galvanised earth lead of GI strip 32x6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 connected to earthing test point and including dismantling complete all as specified and directed.Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, 20 mm bore medium grade GI watering pipe, 40 mm bore GI medium grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc. |
| 100 | Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level, connected to galvanized iron earth lead wire of 4 sqmmby means of bolts, nuts, check nuts and washers of galvanized iron or steel, all as shown in Electrical Plate No 3 of SSR Part - I, including necessary excavation and earth work, P.C.C (1:3:6) type C-I with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar),including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel and 20 mm bore galvanized iron watering pipe (medium grade), wire mesh, aluminium lugs, complete in all respect, GI earth wire protected by 15 mm bore (medium grade) galvanized iron pipe and other end connected with main switch board or Earthing test point as directed,including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion including dismentaling old unsv onescomplete all as specified and as directed by the Engineer-in-Charge. |
| 101 | Supply and fixing GI strip 32x6 mm with necessary nut and bolt etc for connection with existing Earting pit and electrical equipment including taking down old unsv one complete all as specified and directed by Engr-in-Charge. |
| 102 | S&F 4 mm dia GI wire for earth continuity conductor for making connection from earth test point to main DB including taking down old unsv one all as specified and directed by Engr-in-Charge |