Tender For Repair And Maint Of Standby Power Supply System, Amf Panel, Earthing, Internal Wiring Of Installations And Connected Works In The Area Of Age E/M Ext(Elect) Under Ge E/M Lucknow, lucknow-Uttar Pradesh

Military Engineer Services-MES has published Tender For Repair And Maint Of Standby Power Supply System, Amf Panel, Earthing, Internal Wiring Of Installations And Connected Works In The Area Of Age E/M Ext(Elect) Under Ge E/M Lucknow. Submission Date for this Tender is 26-06-2023. Electrification Work Tenders in lucknow Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

37870566
Corrigendum : Tender For Repair And Maint Of Standby Power Supply System, Amf Panel, Earthing, Internal Wiring Of Installations And Connected Works In The Area Of Age E/M Ext(Elect) Under Ge E/M Lucknow
Open Tender
Indian
Uttar Pradesh
lucknow
26-06-2023

Tender Details

Repair And Maint Of Standby Power Supply System, Amf Panel, Earthing, Internal Wiring Of Installations And Connected Works In The Area Of Age E/M Ext(Elect) Under Ge E/M Lucknow

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 10-Jun-2023 Corrigendum1 Date 19-06-2023
2 14-Jun-2023 Corrigendum2 Other 19-06-2023
3 19-Jun-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 26-06-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
INR 45 Lakhs /-

BOQ Items

Name of Work: REPAIR AND MAINT OF STANDBY POWER SUPPLY SYSTEM, AMF PANEL, EARTHING, INTERNAL WIRING OF INSTALLATIONS AND CONNECTED WORKS IN THE AREA OF AGE E/M EXT(ELECT) UNDER GE E/M LUCKNOW.
Sl. No. Item Description
1Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 250/350 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, cleaning of radiator inside with solution i.e restore plus and outside thoroughly with solution(caustic soda with water) incl trial and testing etc complete entire satisfaction of Engr-in-charge, complete all as specified and directed.
2Supply only lubrication oil filter for 250/320 KVA DG setsas per existing make/model/type, complete all as specified and directed.
3Supply only paper bypass filter for 250/320 KVA DG sets as per existing make/model/type, complete all as specified and directed.
4Supply only fuel filter for 250/320 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
5Supply only air cleaner inner for 250/320 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
6Suply only air cleaner outer for 250/320 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
7Supply Filter screen for 250 /320 KVA DG Sets as existing make/model/type, complete all as specified and directed.
8Material and Labour for checking of fan hub including minor repairs if any for 320/250 KVA DG set and checking for alignment complete all as specified and directed.
9Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 200 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, cleaning of radiator inside with solution i.e restore plus and outside thoroughly with solution(caustic soda with water) incl trial and testing etc complete entire satisfaction of Engr-in-charge, complete all as specified and directed.
10Supply only lubrication oil filter for 200 KVA DG sets as per existing make/model/type, complete all as specified and directed.
11Supply only paper bypass filter for 200 KVA DG sets as per existing make/model/type, complete all as specified and directed.
12Supply only fuel filter for 200 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
13Supply only air cleaner inner for 200 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
14Supply only air cleaner outer for 200 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
15Supply only Filter screen for 200 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
16Material and Labour for checking of fan hub including minor repairs if any for 200 KVA DG set and checking for alignment complete all as specified and directed.
17Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 100/110/125 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, cleaning of radiator inside with solution i.e restore plus and outside thoroughly with solution(caustic soda with water) incl trial and testing etc complete entire satisfaction of Engr-in-charge, complete all as specified and directed.
18Supply only lubrication oil filter for 100/110/125 KVA DG sets as per existing make/model/type, complete all as specified and directed.
19Supply only paper bypass filter for 100/110/125 KVA DG sets as per existing make/model/type, complete all as specified and directed.
20Supply only fuel filter for 100/110/125 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
21Supply only air cleaner inner for 100/110/125 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
22Supply only air cleaner outer for 100/110/125 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
23Supply only Filter screen for 100/110/125 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
24Material and Labour for checking of fan hub including minor repairs if any for 100/110/125 KVA DG Sets and checking for alignment complete all as specified and directed.
25Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 62.5/63/82.5 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, cleaning of radiator inside with solution i.e restore plus and outside thoroughly with solution(caustic soda with water) incl trial and testing etc complete entire satisfaction of Engr-in-charge, complete all as specified and directed.
26Supply only lubrication oil filter for 62.5/63/82.5 KVA DG sets as per existing make/model/type, complete all as specified and directed.
27Supply only paper bypass filter for 62.5/63/82.5 KVA DG sets as per existing make/model/type, complete all as specified and directed.
28Supply only fuel filter for 62.5/63/82.5 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
29Supply only air cleaner inner for 62.5/63/82.5 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
30Supply only air cleaner outer for 62.5/63/82.5 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
31Supply only Filter screen for 62.5/63/82.5 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
32Material and Labour for checking of fan hub including minor repairs if any for 62.5/63/82.5 KVA DG Sets and checking for alignment complete all as specified and directed.
33Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 30/40 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, cleaning of radiator inside with solution i.e restore plus and outside thoroughly with solution(caustic soda with water) incl trial and testing etc complete entire satisfaction of Engr-in-charge, complete all as specified and directed.
34Supply only lubrication oil filter for 30/40 KVA DG sets as per exissting make/model/type, complete all as specified and directed.
35Supply only paper bypass filter for 30/40 KVA DG sets as per existging make/model/type, complete all as specified and directed.
36Supply only fuel filter for 30/40 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
37Supply only air cleaner inner for 30/40 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
38Supply only air cleaner outer for 30/40 KVA DG Sets as per existingmake/model/type, complete all as specified and directed.
39Supply only Filter screen for 30/40 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
40Material and Labour for checking of fan hub including minor repairs if any for 30/40 KVA DG Sets and checking for alignment complete all as specified and directed.
41Servicing/ maintenance of DG Set from authorised rep or service engineer from the manufacturer of DG set of capacity 15/20/25 KVA such as injector & valve tappet setting, checking of vibration damper, checking turbocharger, oil leakage, tightening mounting screws & nuts, replacment of filters & oil, checking inlet & Exhaust manifold capscrews, checking of fan hub & water pump, removing the existing engine oil, clean the oil sump and refilling with directed quantity of new oil & coolant top up, cleaning of radiator inside with solution i.e restore plus and outside thoroughly with solution(caustic soda with water) incl trial and testing etc complete entire satisfaction of Engr-in-charge, complete all as specified and directed.
42Supply only lubrication oil filter for 15/20/25 KVA DG sets as per existing make/model/type, complete all as specified and directed.
43Supply only paper bypass filter for 15/20/25 KVA DG sets as per existing make/model/type, complete all as specified and directed.
44Supply only fuel filter for 15/20/25 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
45Supply only air cleaner inner for 15/20/25 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
46Supply only air cleaner outer for 15/20/25 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
47Supply only Filter screen for 15/20/25 KVA DG Sets as per existing make/model/type, complete all as specified and directed.
48Material and Labour for checking of fan hub including minor repairs if any for 15/20/25 KVA DG Sets and checking for alignment complete all as specified and directed. NOTE FOR ITEM NO 1 to 47 :- (i) The "C" Check maint spares parts and engine oil etcshall be measured and paid separately in relavent items of schedule and any other check as per menufacturer"s instructions & minor repair as directed by Engineer-in-charge also deem in the quoated rate of schedule.
49Taking down radiator from Gen set of capacity 200/250/320 KVA after disconnecting the water connecting pipe and descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as specified and directed.
50Taking down radiator from Gen set of capacity 100/110/125 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as specified and directed.
51Taking down radiator from Gen set of capacity 62.5/63/82.5 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as specified and directed.
52Taking down radiator from Gen set of capacity 30/40 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as specified and directed.
53Taking down radiator from Gen set of capacity 15/20/25 KVA after disconnecting the water connecting pipe, descaling, cleaning properly with high pressure wash to remove greasy substances from water tubes, tank and outer fins and re-fixing the same after servicing complete and replacement of coolant solution and hose radiator with clips complete all as specified and directed.
54Dismantling and taking out Dynamo/alternator assembly of 12 Volts/24 Volts from the DG sets replacing the spare parts such as carbon brushes, springs, spring holders, brushes, bearings or any other part required for full functioning of machine and fixing and testing complete all as specified and directed.
55Dismantling and taking outdynamo/alternators from DG set for rewinding and taking out the old coil, cleaning thoroughly and wound with new super enameled copper cord of existing size and gauge, varnishing, drying, heating as per manufacturer norms and fixed with dynamo/alternator properly testing and commissioning complete all as specified and directed.
56S&F in replacement of radiator hoses of any size and any capacity of DG set and fixed properly with new jublee clips, clamps, nuts and testing complete all as specified and directed.
57Dismantling and taking out the FIP (PT Pump Assy) forrepairing by replacing the worn out gasket, filter, suction valve, discharge valve and fixing the same after calibration and testing of capacity 200 KVA / 250 KVA/320KVA DG set, complete all as specified and directed. Note : Repairing & Calibration shall be carried out by authorised dealers only.
58As per item No 57 above but for DG set of capacity 125KVA/110KVA/100KVA
59As per item No 57 above but for DG set of capacity 82.5KVA/63KVA/62.5KVA
60As per item No 57 above but for DG set of capacity 40KVA/30KVA/25KVA/20KVA /15KVA
61M&L in repair overhauling/calibration of injector assembly for any make/model/capacity of DG sets including renewal of wornout parts such as copper gasket, injector nozzle and testing complete all as specified and directed. Note :- Repairing/Calibration shall be carried out by authorised dealer only.
62Supply and fixing of oil pressure gauge as per existing make/model/ capacity of any type ofDG sets incl taking down old one etc complete all as specified and directed.
63Supply and fixingin repair AVR unit /CVR –II for 320/250/200 DG Set &testing etc complete all as specified and directed. Make : Kirloskar/Cummins
64Supply and fixing in repair AVR unit /CVR –II for 125KVA/110KVA/100KVA DG Set and testingetc complete all as specified and directed. Make :Kirloskar/Cummins
65Supply and fixingin repair AVR unit /CVR –II for 82.5KVA/63KVA/62.5KVA DG Set and testingcomplete all as specified and directed. Make : Kirloskar/Cummins
66Supply and fixing in repair AVR unit /CVR –II for 40KVA/30KVA/25KVA/20KVA/15 KVA DG Set and testing etc complete all as specified and directed. Make : Kirloskar/Cummins
67Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fixnew water pump assembly for the DG sets of capacity 320/250KVA/200KVA incl testing complete all as specified and directed.
68Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fixnew water pump assembly for the DG sets of capacity 125KVA/110KVA/100KVA incl testing complete all as specified and directed.
69Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fix in repairs new water pump assembly for the DG sets of capacity 82.5KVA/63KVA/62.5KVA incl testing complete all as specified and directed.
70Dismantling and taking out of defective water pump assembly from the the DG sets and supply and fix in repairs new water pump assembly for the DG sets of capacity 40KVA/30KVA/25KVA/20KVA/15 KVA incl testing complete all as specified and directed.
71Dismantling and taking out the water body pump assembly complete from the DG set upto capacity 62.5 KVA at site and transporting to the work shop for repair and refixed the same after repiar & testing complete afterreplaement of the followingparts:-. (a) Over hauling of water body pump complete - 01 Job, (b) Supply and fix water body kit complete- 01 Set, (c) water body bearing - 02 Nos, (d) water body Hose- 01 Set
72Dismantling and taking out the water body pump assembly complete from the DG set upto capacity 82.5 KVA to 125 at site and transporting to the work shop for repair and refixed the same after repiar & testing complete afterreplaement of the followingparts:-. (a) Over hauling of water body pump complete - 01 Job, (b) Supply and fix water body kit complete- 01 Set, (c) water body bearing - 02 Nos, (d) water body Hose- 01 Set
73Dismantling and taking out the water body pump assembly complete from the DG set upto capacity 200 to 320 KVA at site and transporting to the work shop for repair and refixed the same after repiar & testing complete afterreplaement of the followingparts:-. (a) Over hauling of water body pump complete - 01 Job, (b) Supply and fix water body kit complete- 01 Set, (c) water body bearing - 02 Nos, (d) water body Hose- 01 Set
74Supply & fixbattery terminals made of brass superior quality incl taking down old oneetc complete all as specified and directed.
75Dismantling and taking out the dfective self starter assembly of any capacity (12V/24V) form the DG set and re-fixing the same after repair works including replacing the spare parts such as carbon brushes, springs, spring holder bushes, bearings, or any other spare part not mentioned herein but essentially required for proper functioning of the starter assembly complete all as specified and directed.
76Dismantling and taking outself starter from DG set and taking out unserviceable old coil , cleaning thoroughly slot and rewinding the starter with super enameled copper conductor of existing size and gauge inclvarnishing drying, heating and re-fixing the same after repair incl testing complete all as specified and directed.
77Supply & Fixingflexible pressure hose for lubricant oil and fuel for any size/capacity/model/makeof DG set incl taking down old one etc complete all as specified and directed.
78S & FPVC heavy duty transparent pipe of size 10 mm dia for Diesel tank indicator with suitable clamps fixed on any type of tank incl taking down old one etc complete all as specified and directed.
79S & F oil pressure cut out suitable for any model/make of DG set upto 320 KVA incl takding down old one, complete all as specified and directed.
80S & F water temperature cut out suitable for any model/make of DG set upto 320 KVA.incl taking down old complete all as specified and directed.
81Supply and fixignition switch and key for DG sets of 250/200 KVA capacity incl taking down old one complete all as specified and directed.
82Dismantling the radiator of 320/250/200 KVA DG set its position and soldering of copper pipes, where leakage inclrectifying leaks & cleaning radiator and PVC hose and fitting the same place and testing complete all as specified and directed.
83Dismantling the radiator of 125/110/100 KVA DG set its position and soldering of copper pipes, where leakage inclrectifying leaks & cleaning radiator and PVC hose and fitting the same place and testing complete all as specified and directed.
84Dismantling the radiator of 82.5 to 15 KVA DG set its position and soldering of copper pipes, where leakage inclrectifying leaks & cleaning radiator and PVC hose and fitting the same place and testing complete all as specified and directed.
85Material and labour for draining out old engine/lubrication oil from chamber of the DG sets, cleaning of chamber thoroughly and filling new engine/lubrication oil of grade 15W40 complete all as specified and directed.
86Material and labour for draining out old engine/lubrication oil from chamber of the DG sets, cleaning of chamber thoroughly and filling new engine/lubrication oil of grade 20W40 complete all as specified and directed.
87Supply and fixing in repair rotating rectifier assembly for 320/250/200 KVA DG set of any make and model, complete all as specified and directed.
88Supply and fixing in repair rotating rectifier assembly upto 125/110/100 KVA DG set of any make and model, complete all as specified and directed.
89Supply and fixing in repair rotating rectifier assembly upto 82.5/63/62.5 KVA DG set of any make and model, complete all as specified and directed.
90Dismatling defective coupling assembly from thealternator & engine any capacity and make of DG set and carrying out the repair works/renewal of spare for proper functioning of the alternator and re-fixing the same to the entire satisfaction of Engineer-in-Charge, complete all as specified and directed.
91Material and labour for repairing/renewal of the existing broken/leaking PVC fuel over flow pipe of the DG sets of any capacity upto fuel tank placed externally from the DG sets complete all as specified and directed.
92Supply and fixingrectifier diode for 250/200 KVA DG sets as per exising make/model/ size incl taking down old one etc complete all as specified and directed.
93Supply and fixing rectifier diode for 125/110/100 KVA DG sets as per exising make/ model /size incl taking down old one etc complete all as specified and directed.
94Supply and fixing rectifier diode for DG sets upto 82.5 KVA capacity as per exising make/size/ model incl takding down old oneetc complete all as specified and directed.
95Supply and fixing voltmeter square/ round upto 500 Volts of existing size. Make : MECO/AE incl taking downold one complete all as specified and directed.
96Supply and fixingammeter 0-300A as per existing size/make/model incl taking down old one etc complete all as specified and directed.
97Supply and fixing indicator lamp assembly 230/110 Volts as per existing make/model/size etc complete all as specified and directed.
98S & F battery leads 95 Sqmm copper cable 1.5 Mtr long with brass terminals etc complete all as specified and directed.
99S & F techometeras per existing size/make/model incl taking down old one etc complete all as specified and directed.
100S & F techometer cable in and out with adopters etc complete as per exisiting size/make/model complete all as specified and directed.
101S & F asbestos rope 20mm dia for tightly coveredthe silencer exhaust pipe etc complete all as specified and directed.
102Supply only coolant concentrate, complete all as specified and directed. Pert No SK 802 OIC Make : Valvoline
103Material and labour for dismantling and taking out the alternator upto 40 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holderand re-assembling the rotor & stator complete with applying suitable greasing & oiling of bearing & moving parts and refixing the same on existing position and testing complete all as specified and directed.
104Material and labour for dismantling and taking out the alternator above 40 KVA but upto 82.5 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holderand re-assembling the rotor & stator complete including applying suitable greasing & oiling of bearing & moving parts and refixing the same on its position and testing complete all as specified and directed.
105Material and labour for dismantling and taking out the alternator and taking out above 82.5 KVA but upto 125 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holderand re-assembling the rotor & stator complete including applying suitable greasing & oiling of bearing & moving parts and refixing the same on its position and testing complete all as specified and directed.
106Material and labour for dismantling and taking out the alternator above 125 KVA but upto 250 KVA capacity from the DG sets from coupling and opening the stator & rotor including cleaning of dust from windings for proper ventilation, renewal of carbon brushes with brush holderand re-assembling the rotor & stator complete including applying suitable greasing & oiling of bearing & moving partsand refixing the same its position and testing completeall as specified and directed.
107Supplying and fixingincluding testing of fuel feed pump for DG set of capacities upto 250 KVA all as specified incl taking down old onecomplete all as specified and directed.
108Supplying, fixinglead acid battery 12 volts, 180 AH suitable for DG set including initial charging (Model No. FXPO-MHD1800 Exide New express or equivalent of other specified make) including connection & testingand taking down old one etc complete all as specified and directed.
109Supplying, fixinglead acid battery, 12 volts, 150 AH suitable for DG set terminals including initial charging (Model No. FXPO-MHD1500 Exide New express or equivalent of other specified make) includingconnection & testing incl taking down old one etc complete all as specified and directed.
110Supplying, fixinglead acidbattery, 12 volts, 110 AH with lead acid suitable for DG setincluding initial charging (Make- EXIDE / AMRON ) including connction and testing incl taking down old one complete all as specified and directed.
111Supply only distill water for batteries, complete all as specified and directed.
112Supply and fixnew battery charger heavy duty type with volteter and ammeter, with copper wound transformer, suitable for charging 12 Volts 180 AH battery complete all as specified and directed.
113Supply and fix battery charger heavy duty type with volteter and ammeter, with copper wound transformer, suitable for charging 02 Nos 12 Volts 180 AH battery complete all as specified and directed.
114Supply and fixing turbo kit suitable for 250/200 KVA DG sets, complete all as specified and directed.
115Supply and fixing turbo kit suitable for62.5 to 125 KVA DG sets, complete all as specified and directed.
116Supply and fixingturbo kit suitable for 15 to 40KVA DG sets, complete all as specified and directed.
117Supply, fixing and testingSelf Starter 12 Volt, DC for DG Set of capacity upto 125 KVA (Make of DG Set Kirloskar/Cummins as per existing size and make) complete all as specified and directed.
118Supply, fixing and testing Self Starter 24 Volt, DC for DG Set of capacity upto 320 KVA (Make of DG Set Kirloskar/Cummins) complete all as specified and directed.
119Supply only DC 6/12 VOLT battery cell tester upto 180 AHbattery complete all as specified and directed.
120Supply only DC 6/12 VOLT battery hydrometer upto testing oof elecrolite specific grevity 180 AHbattery complete all as specified and directed.
121Supply & chelating cleaner Restore Plus solution Part No. AX1001098 Make : Cummins for engines cooling system complete all as specified and directed.
122Dismantling the defective, unserviceable Radiator opening as inlet/outlet water cooling system connectionand Supplying & fixing new one Radiator Part No. 123200521096 for Engine DG Set Cap 125 KVA, Engine Model - TBD2 V8 MkI, Make : Greaves including all required accessories/hoses with tightening clamps etc as required inlet & outlet cooling system complete all as specified and directed.
123Supplying & fixing ExhaustManifold as per exisitng make/model/type of capaicty 250/200 KVA DG set incl taking down old one complete all as specified and directed.
124Supplying & fixing ExhaustManifold as per exisitng make/model/type of capaicty 100/110/125 KVA 100/110/125 KVA DG set incl taking down old one complete all as specified and directed.
125Supplying & fixing ExhaustManifold as per exisitng make/model/type of capaicty 62.5/63/82.5 KVA DG set incl taking down old one complete all as specified and directed.
126Supplying & fixing ExhaustManifold as per exisitng make/model/type of capaicty 30/40 KVA DG set incl taking down old one complete all as specified and directed.
127Supplying & fixing ExhaustManifold as per exisitng make/model/type of capaicty 15/20/25 KVA DG set incl taking down old one complete all as specified and directed.
128Supplying & fixing ExhaustGasket as per existing make/model/type of capacity of DG set 250/200 KVA DG Set incl taking down old one etc complete all as specified and directed.
129Supplying & fixing ExhaustGasket as per existing make/model/type of capacity of DG set 100/110/125 KVA 100/110/125 KVA DG Set incl taking down old one etc complete all as specified and directed.
130Supplying & fixing ExhaustGasket as per existing make/model/type of capacity of DG set 62.5/63/82.5KVA DG Set incl taking down old one etc complete all as specified and directed.
131Supplying & fixing ExhaustGasket as per existing make/model/type of capacity of DG set 30/40KVA DG Set incl taking down old one etc complete all as specified and directed.
132Supplying & fixing ExhaustGasket as per existing make/model/type of capacity of DG set 15/20/25KVA DG Set incl taking down old one etc complete all as specified and directed.
133Supplying & fixing Pipe water pipe of manifold A bankof capacity of DG set 250 to 15 KVAas per existing make/model/type incl taking down old one etc complete all as specified and directed.
134Supplying & fixing Pipe water pipe of manifold B bankof capacity of DG set 250 to 15KVAas per existing make/model/type incl taking down old one etc complete all as specified and directed. Note : 1 to 133 - (i) DG set should be repair within 1 to 2 hours after receiving the massage from department.If the contractor fail the repair of DG set within perioud, the penality should be paid 2500/per hours to department. (ii) If any material not covered in the contract, the contractor repair the DG set on own cost and department will be paid as per rule and regulation.
135Taking down carefully copper/aluminium point wiring (light, fan, socket, bell or power) completeincluding all electrical fittings & fixtures(DBs, submain,cables etc) and making good disturbed surfaces of wall , floor etc and matching wth original colour of wall, complete all as specified and directed.
136M&L Point wiring One light/fan point controlled by one way switch 6 amps 240 volts with 1.5 sq mmcopper conductor FRLS(multistrand) PVC insulatedISI marked unseathed cable 1100 volt grade in and including concealed/surface , non metalic rigid pvc medium grade ISI marked conduit not less than 19 mm with all fittings& other accessories and also includingPVC insulated ISI marked unseathed FRLS cable 1100 volts grade of size 1.5 sq mm copper conductor as earth wire to common earth dolly including concealed in wall/ceiling,MS box 1.6 mm thick with hylum sheet 3 mm thick (approved colour) suitable size for switches, sockets, fan regulatoretc for the following :- Note - (i) Colour code of cable Phase-Red Neutral- Black and Earth -Green) (ii) MS box painted with two coat of synthetic enamelled paind and over coat of red oxide both side.
137As per item No 136 above but One 3 pin 6 Amps switch socket out let point on independent Board
138As per item No 136 above but One 3 pin 6 Amps switch socket out let point on same board
139M&L Point wiring with 2.5 sq mmcopper conductor FRLS(multistrand) PVC insulatedISI marked unseathed cable 1100 volt grade in and including concealed/surface , non metalic rigid pvc medium grade ISI marked conduit not less than 19 mm with all fittings& other accessories and also includingPVC insulated ISI marked unseathed FRLS cable 1100 volts grade of size 2.5 sq mm copper conductor as earth wire to common earth dolly including concealed in wall/ceiling,MS box 1.6 mm thick with hylum sheet 3 mm thick (approved colour) suitable sizeswitches, sockets 16 Amps, 240 volts, complete all as specified and directed. Note - Colour code of cable Phase-Red Neutral- Black and Earth -Green) (ii) MS box painted with two coat of synthetic enamelled paind and over coat of red oxide both side.
140S&F switch piano flush type single pole, one way 6 Amps 240 ISI marked etc complete all as specified and directed.
141S&F socket outlet 2 in 1, 3 pin 5 A flush type ISI marked 240 volts ISI marked etc complete all as specified and directed.
142S&F switch socket combination 2 in 3 pin 5 and 15 Amps flush type ISI marked universal suitable for 240 volts etc complete all as specified and directed.
143M&L for ceiling rose with three terminal as per relevant IS complete all as specified and directed.
144Supply and fix decorative box type fitting with blue colour end cap for LED tube 20 watt luminaire for 230 volt AC incl LED tube 20 watt complete all as specified and directed.
145Supply & fixdecorative box type fitting with blue colour end cap for LED tube 10 watt luminaire for 230 volt AC incl LED tube 10 watt complete all as specified and directed.
146S&F stepped type fan electronic fan regulator flush type ISI marked on the existing fenolic laminated sheet etc complete all as specified and directed.
147S&F epoxy powder coated or polystrene insulated material sheet metal enclosure factory made (double door)8 way SPN suitable for MCB DB"s 240 Voltswith 200 Amps rated busbar, neutral & earthing link bar, flush/surface mounting complete all as specified and directed.
148S&F epoxy powder coated or polystrene insulated material sheet metal enclosure factory made (double door)4 way TPN suitable for MCB DB"s 415 Voltswith 200 Amps rated busbar, neutral & earthing link bar, flush/surface mounting complete all as specified and directed.
149S&F MCBsingle pole ISI marked`C" series working on 240 Volts 50 HZ AC supply for out goingcontrolling cercuit of capacity 6-32 Amp breaking capacity 10 KA etc complete all as specified and directed.
150S&F MCBsingle pole ISI marked `C" series working on 240 Volts 50 HZ AC supply for out going controlling cercuit of capacity 40-63 Amp breaking capacity 10 KA etc complete all as specified and directed.
151S&F MCBsingle pole and neutral ISI marked `C" seriesworking on 240 volts 50HZ AC supply for incomming controlling system of capaicty 40-63 Amps 10 KA breaking capacity etc complete all as specified and directed.
152S&F MCB triple pole and neutral ISI marked `C" seriesworking on 240 volts 50HZ AC supply for incomming & out going controlling system of capaicty 40-63 Amps 10 KA breaking capacity etc complete all as specified and directed.
153M&Lfor sub main wiring with two single core, PVC insulated,ISI marked, unsheathed, 1100 volts grade multistranded copper conductor FRLS cable drawn into and including suitable size non metalic rigid pvc conduit (ISI marked) concealed/surface with all accessories and including one single core pvc insulated multistranded unsheathed 1100 volts grade copper conductor FRLS cable as earth wire of the 2x6.0 sqmm + 1x6.0 sqmm earth wire size complete all as specified and directed.
154S&F LED flood light 150 watt IP66 high power flood light with pressure die cast aluminium housing complete all as specified and directed.
155M&L new generation energy saving and environmental friendly long life 45 W LED street light made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded pc cover having top opening separate driver compartment with IP 66 protection of IK07 in taking old one etc complete all as specified and directed.
156Supply and fix in repair heavy duty exhuast fan 600 mm, 900 rpm turbo force model three phase incl all accessories as per manufacturer norms incl suitable size 4 core pvc insulated unseathed copper cable cable from ceiling rose to connector of fan etc complete all as specified and directed.
157Supply and fix in repair heavy duty exhuast fan 450mm, 900 rpm turbo force model single phase incl all accessories as per manufacturer norms incl suitable size three core pvc insulated unseathed copper cable from ceiling rose to connectorfan etc complete all as specified and directed.
158M&L rewinding of exhaust Fan of600/450mm sweep and ceiling fan 1200 mm sweep of any make with super enameled copper wire (gauge/weight of copper coils shall be same as per existing dismantled fans), including varnishing,heating and replacement of capcitor & 3 core cable from ceiling rose to connector of equipment complete all as specified and directed.
159Supply and fix in repair ceiling fan 1200mm sweep with all accessories as per manufacturer norms incl 3 core copper cord from ceiling rose to connector of fan etc complete all as specified and directed.
160Supply flood light 30 watt LED flood light engergy saving, environmental friendly long life exclusive innovative die cast aluminium alloy flood light with high power led as lightsource suitable for highlighting architectural feature or area lighting also suitable to rough services /installation incl taking down old one etc complete all as specified and directed.
161Rewinding of armature of Dynamo/alternators dismantling the old coil, cleaning thoroughly and wound with new super enameled copper cord of existing size and gauge, varnishing, drying etc, and fixed with dynamo/alternator properly testing and commissioning all of any size complete all as specified and directed.
162Supply and fixing only off load changeover switch 63 Amps TPN with sheet metal enclosure ,side handle operated, 50 Hz, fixed to walls/ panels with suitable size clamps, nuts, bolts and washers complete all as specified and directed.
163All as per Item No 162 above but 100 Amps
164All as per Item No 162 above but 200 Amps
165Supply & Fixing in repairs "ON LOAD" type Change over switch 630 Amps TPN front handle operated, on existing LT/AMF Panels, suitable for three phase, 415V, 50 Hz AC complete all as specified and directed.
166All as per Item No 165 above but 315 Amps
167All as per Item No 165 above but 250 Amps
168All as per Item No 165 above but 200 Amps
169All as per Item No 165 above but 100 Amps
170All as per Item No 165 above but 63 Amps
171Supply and fix in repairs 4 pole power contactor MCX44 auxilary contacts 2NO + 2NC suiable for 320 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
172Supply and fix in repairs 4 pole power contactor MCX42 auxilary contacts 2NO +2NC suiable for 250 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
173Supply and fix in repairs 4 pole power contactor MCX41 auxilary contacts 2NO + 2 2NC suiable for 200 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
174Supply and fix in repairs 4 pole power contactor MCX33 auxilary contacts 2NO + 2NC suiable for 100 to 125 KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
175Supply and fix in repairs 4 pole power contactor MCX22 auxilary contacts 2NO + 2NC suiable for 63KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
176Supply and fix in repairs 4 pole power contactor MCX12 auxilary contacts 2NO + 2NC suiable for 30-40KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
177Supply and fix in repairs 4 pole power contactor MXC4 auxilary contacts 2NO + 2NC suiable for 15-25KVA DG set ,415 Volts, 50 Hz or existing make/type/rating/modelfor AMF panel boards etc complete all as specified and directed.
178Material and labour for dismantling the defective alternator of any capacity from the existing foundation and Engine after removing all electrical connections transporting to workshop, removing the old wornout burnt wiinding and rewinding the statorassembly with super enameled copper wire, applying insulating varnishing of ‘F’ class baking in oven re-assembling the alternator after transporting back tosite re-installing the same carrying out alignment of complete DG set connecting up all electrical connections testing and commissioning complete all as specified and directed. Note: - (a)The rates quoted by the contractor shall deemed to include any other item/spare not mentioned herein but essentially required for fully functional of the alternator. (b)Rate quoted shall be deemed to be inclusive of making good the disturbed surfaces of foundations. (c) The DG set shall be tested for the duration of 4 hours to the entire satisfaction of Engineer- in- Charge.
179S & F in repair controller for electronic control panel for DG Set upto 320 KVA complete all as specified and directed.
180M&L for repair ofDG set canopy by replacing of door hinges and locking arrangement complete all as specified and directed.
181S&F PVC pipe of size 25 mm dia heavy duty for FOL distribution complete all as specified and directed.
182Supply and spread river sand including removing of old diesel wetted sand from FOL store complete all as specified and directed.
183M&L for cleaningby desludging of fuel tank of DG Set byincluding out going and over flowing pipe and replacement offuel indicator pipe including make locking arrangement of tank ,painting of tank complete all as specified and directed.
184Supply and fixing of oil pressure gauge of existing size and model for any make/model/capacity of DG sets complete all as specified and directed.
185Material and labour for servicing/repair of AMF panel of DG set upto 320 KVA capacity for smooth functioning of the same with renewal / repairs of AMF panel wiring, control timer, engine starting relay, contact point relay, AMF relay, HRC fuse of existing rating etc complete forDG sets installed at various pokets under AGE E/M EXT(ELECT) complete all as specified and directed. Note:- 1. The rates quoted by the contractor shall deemed to include the cost of spares/relays or any other part not mentioned herein but essentially required to make the AMF Panel completely functional and no extra payments shall be made for the same.
186Supply and fix in repairs electronic control timer type ET-100 of suitable capacity as required at site, complete all as specified and directed. (Make:- L&T or equivalent as approved by GE)
187Supply and fix in repairs engine starter relay of suitable capacity as required at site, complete all as specified and directed. (Make:- L&T or equivalent as approved by GE)
188Supply and fix in repairs under voltage relay, complete all as specified and directed. (Make:- PIC / EC / Wader.)
189Supply and fix in repairs 8/11 pin relay, complete all as specified and directed. (Make:- PLA.)
190Supply and fix in repairs Auto Mains Failure (AMF) relay as per existing model and make of AMF panels of DG sets of any capacity, complete all as specified and directed.
191Supply and fixing crocodile clip for battery chargers of required size complete all as specified and directed.
192Supply and fixing MCCB 3 Pole of capacity 200 Amps, 50 Hz, 415V with rupturing capacity of 35 KA with fixed thermal magnetic protection settings including spreader terminal including taking down old one complete all as specified and directed.
193Supply and fixing only MCCB 3 Pole of capacity 250 Amps, 50 Hz, 415V with rupturing capacity of 35 KA with thermal magnetic protection settings including spreader terminals including taking down ole etc complete all as specified and directed.
194Supply and fixing MCCB 3 Pole of capacity 400 Amps, 50 Hz, 415V with rupturing capacity of 50 KA with hermal magnetic protection settings including spreader terminals incl taking down old one etc complete all as specified and directed.
195Supply and fixing MCCB 4 Pole of capacity 125 Amps, 50 Hz, 415V with rupturing capacity of16 KA with thermal magnetic protextion unit including spreader terminals complete incl taking down old one etc complete all as specified and directed.
196Supplying and fixingMCCB 4 Pole of capacity 160 Amps, 50 Hz, 415V with rupturing capacity of 25 KA with thermal magnetic protection unitincluding spreader terminals incl taking down old one etc complete all as specified and directed.
197M&L for in repair ofDG set fuel UPVC pipe15 mm bore by replacing including elbow, tee , socket etc complete all as specified and directed.
198M&L for making earthing high conductive, non corosive maintenance free, non fluctuation of ohmic value 80 mmX3000mm (inner strip-3000x50x6mm, connection terminal 100x50x6mm, therminal hole 16mm, Inner filling CCM lectrode pipe-B class) GI pipe in pipe filled with super conductive crysteline with earth plus 50 kg containing mixture of graphite, Sulfate, , Silica,ALumina , Iron Oxide, Titanium oxide, calcium oxide , Magnesium oxide , Sodium oxide , Zink oxide etc) back fill compound should be ROHS including heavy duty polymer Earth pit chember with coverand S&F of GI strip 32x6 mmrequired at site for connection of earthing with any type equipmentcomplete all accesories for design modification to achieve the earth terminal rod resistance value below 1 OHM complete all as specified and directed.
199M&L for Generator of capacity 15 KVA to 125 KVA painting of the Engine and Alternator of diesel Generator as existing complete by removing old paint by scraping and providing spary painting with approved synthetic enamelled paint complete all as specified and directed.
200As per item No 199 above but Generator of capacity 200 KVA to 320 KVA
201Supply ,laying, jointing, testing,XLPE insulated PVC sheathed stranded aluminium conductor, heavy duty, conforming to IS 1554 Part I / ISI marked, including suitabe size cable glands & lugs, cables to be laid in trenches, fixed along the poles /or through GI pipe laid under floors road etc complete of size 300 sqmm 3.5 coreincl taking down old one complete all as specified and directed.
202All as per Item No 201 above but 240 Sqmm 3.5 Core
203All as per Item No 201 above but 95 Sqmm 3.5 Core
204All as per Item No 201 above but 70 Sqmm 3.5 Core
205Supply only EMPTY BARRELheavy duty made of steelof 220 ltr capacity for collection of a FOL complete all as specified and directed.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail