Tender For Modification, Renovation And Rewiring Of Sub-Division Office, Street Lights And Gate Lights At Maynaguri Teesta Colony, Jalpaiguri.
Tender Value
4.39 Lakhs
Estimated cost
Bid Submission
31 May 2023
0 days left
EMD
8788
Bank guarantee accepted
Document Fee
Ref. Documents
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
maynaguri → West Bengal
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Tender For Modification, Renovation And Rewiring Of Sub-Division Office, Street Lights And Gate Lights At Maynaguri Teesta Colony, Jalpaiguri.
BOQ
| Sl. No. | Item Description |
| 1 | Supplying of following xlpe insulated aluminium conductor armoured cables of 1.1kv grade as per is 7098 (part 1) 1988 with up to date Amendments. (Rate in Rs. per mtr). |
| 2 | 2 CORE 16 SQ MM |
| 3 | 2 CORE 25 SQ MM |
| 4 | Laying of one No. cable upto 35 sqmm in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed. |
| 5 | Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish.From 2.5 sqmm to 35 sqmm at an average depth of 75 mm in floor/pavement/wall etc. |
| 6 | Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below :(a) For 2 core (upto 35 sqmm) |
| 7 | Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials. |
| 8 | 2 core 16 sqmm cable |
| 9 | 2 core 25 sqmm cable |
| 10 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection.63A SPN (Make :-Havells) |
| 11 | Supplying and fixing MCB SS enclosure with IP-20/30protection, powder coated provision for two/four poleMCB, concealed in wall after cutting the wall & mendinggood the damages to original finish incl. painting,connection & provision for earthing attachment2 Way |
| 12 | Supplying and fixing Sheet steel Main Switches onangle iron frame on wall |
| 13 | 60/63 A(Make:-Havells) |
| 14 | Supplying and fixing double-door SPN MCB DistributionBoard with IP-42/43 protection, concealed in wall aftercutting the wall & mending good the damages tooriginal finish incl. Inter connection with suitable size ofcopper wire and neutral link & provision for earthingattachment. |
| 15 | 2+12 way Enclosure Enclosure (A9HSND12)(Make :- Schneider) |
| 16 | Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection. |
| 17 | 6-32 A ,DP (Make :- Havells) |
| 18 | Supplying and fixing 240/415 V MCB Isolator ondin rail of existing DBs and necessary connection. |
| 19 | 40 A DP (Make:- Havells) |
| 20 | Wiring in 1.1 KV grade single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 25mm PVC casing-capping (Precision make) incl. necy. PVC clips, fittings etc.2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) |
| 21 | Distribution Wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm)single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire for ECC, incl. necy. PVC clips, fittings etc. to 5A3pin flush type plug socket with piano key type switch (Anchor make) fixed on sheet steel fabricated CRC MS switch board with bakelite/perspex (wall matching color) top cover of 3 mm thick flushed in wall by housing the board after cutting brick wall incl. necy. connection making earthing attachment,painting and mending good damages to building works |
| 22 | On Board |
| 23 | Average run 4.5 mtr |
| 24 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded \"FR\" PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. to light/fan/call bell point with Modular type switch (Brand approved by EIC) fixed on Modular GI / PVC switch board with top cover plate on wall incl. mending good damages to original finish. [PVC casing capping and Switch board both on surface] |
| 25 | a)Average run 5 mtr |
| 26 | Supplying of different types of LED lamps (12W) |
| 27 | Make: Havells, NU Bulb Plus 12 W 865 B22 2 Star |
| 28 | Fixing only lamp |
| 29 | Ding Dong Call Bell (Anchor) |
| 30 | Fixing only Call Bell/Buzzer on single HWboard on wall incl. S&F single HW board. |
| 31 | Step Type Electronics Fan regulator |
| 32 | Danger board (20 cm. x 30 cm.) |
| 33 | Supply TMC501 Conventional industrial batten Philips LEDtube, model no : TMC 501 P 1xT-LED 22W P3241 with 1no Mas LEDtube 1200mm 18W865 T8 I – 2100lm including necessary connection. |
| 34 | Supply & Fixing 240 V, 2 nos. 6A, & 2 nos. 20A plug socket with separate 2 nos. 6 A & 2 nos. 20A Piano key type switch,indicator & 20A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. |
| 35 | Supply and fixing of smart bright street light (36 Watt) complete with all accessories to be fixed /projected from the wall of the building or on pole incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. |
| 36 | Make : Crompton, 36 watt |
| 37 | Supply and fixing of Havells Post top Luminaries model no : CORAL PT35WLED (35Watt) over the preinstalled GI Pipe over the gate structure or similar structure incl. connection by 1.5 sq mm cu wire from loop box to the light |
| 38 | Supply of 240VAC analog time switch for ON-OFF control of street light |
| 39 | Supply of 3 pole power contactor type ML 2, 40A current rating |
| 40 | Painting of Steel Tubular Pole of lengths and no. of coats of paint,as given below with ready mixed paint/primer of approved make,and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint.(a) Upto 9.0 mtr. long pole |
| 41 | (i) One coat of red lead/Zinc chromate priming |
| 42 | (ii) 1st coat of synthetic enamel paint over the primer |
| 43 | (iii) 2nd coat of synthetic enamel paint over the 1st coat |
| 44 | Supplying and Fixing GI water proof looping cable box having hinged GI Top Cover having 4 mm thick with rubber gasket lining, railway type mechanical locking arrangement, earthing terminal with lug etc. of the following sizes as indicated below,Comprising of one 250 V, 15 A Kit-Kat fuse unit, one NL on porcelain insulator etc. and housing the same in pole muffing incl. addition and alteration to the existing CC muffing (6:3:1) after dismantling the damaged looping cable box etc. where necy. incl. painting. |
| 45 | (a) 200 x 150 x 100mm |
| 46 | Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl.drilling holes, with bolts, nuts, washers etc |
| 47 | Earthing with Copper plate (610x610x3mm size) having weight of 9.84 Kg and 1 No. 25x5mm Copper strip (3.20 mt long) & 1 no. 6 sqmm PVC insulated stranded Copper wire (4 Mt long) incl. S & F 15 mm dia GI pipe (ISI-Medium) protection (4 mt. long) to be fillied with bitumen, partly under the ground level & partly above ground level to an average depth of 3.65 Mts. below the ground level and restoring the surface duly rammed incl. providing 3.0 mt long, 25 mm dia GI pipe (ISI-Medium) for periodic treatment, incl. providing masonery enclosure on the top of the earth electrode of overall size 86.36x86.36x46cm deep (below Ground level) complete with cemented brick work (1:6) of 25 cm width, duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56x35.56cm with locking arrangement, GI reducer and treatment of soil by using salt & charcoal or coke for plate electrode |
| 48 | Suppy and delivery of Copper Strip |
| 49 | Supply and fixing of GI conduit pipe for earthing wires.15mm dia GI pipe (ISI Medium) |
| 50 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts.long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below:(a) By TATA-Medium GI pipe |
| 51 | Supplying of approved make exhaust fan heavy duty with mounting frame,blades AC 230-250 |
| 52 | 225mm sweep RPM 900 / 1400 (9”) |
| 53 | Supplying of approved make high speed ceiling fan (ISI marked) offollowing sizes having double ball bearing complete with standard down rod, canopy, hanging shackle, Aluminium blades, without regulator, A.C. 230-250 volts. |
| 54 | 900mm/ 1050mm/ 1200mm |
AI Tender Summary
Tender Timeline
May 24, 2023
11:30 IST
Tender Published
Tender notice published.
CompletedMay 31, 2023
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedJun 01, 2023
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender