Tender For Repair /Routine Maintenance Of Dg Set, Amf Panels And Repair / Replacement Of Various Capacity Lt Switch Gear, Mccbs, Acbs, Contactor, Apfc Panels And Other Misc Installation Work At Af Stn Chandinagar In Aor Of Ge (Af) Faridabad, Baghpat-Uttar Pradesh

Military Engineer Services-MES has published Tender For Repair /Routine Maintenance Of Dg Set, Amf Panels And Repair / Replacement Of Various Capacity Lt Switch Gear, Mccbs, Acbs, Contactor, Apfc Panels And Other Misc Installation Work At Af Stn Chandinagar In Aor Of Ge (Af) Faridabad. Submission Date for this Tender is 23-06-2023. Switch Gear Tenders in Baghpat Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

37798380
Corrigendum : Tender For Repair /Routine Maintenance Of Dg Set, Amf Panels And Repair / Replacement Of Various Capacity Lt Switch Gear, Mccbs, Acbs, Contactor, Apfc Panels And Other Misc Installation Work At Af Stn Chandinagar In Aor Of Ge (Af) Faridabad
Open Tender
Indian
Uttar Pradesh
Baghpat
23-06-2023

Tender Details

Repair /Routine Maintenance Of Dg Set, Amf Panels And Repair / Replacement Of Various Capacity Lt Switch Gear, Mccbs, Acbs, Contactor, Apfc Panels And Other Misc Installation Work At Af Stn Chandinagar In Aor Of Ge (Af) Faridabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 02-Jun-2023 Date Date 16-06-2023
2 02-Jun-2023 Tender Documents Terms and Conditions 16-06-2023
3 02-Jun-2023 BOQ BOQ 16-06-2023
4 16-Jun-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 23-06-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 80000.0 /-
Tender Value
INR 40 Lakhs /-

BOQ Items

Name of Work:REPAIR /ROUTINE MAINTENANCE OF DG SET, AMF PANELS AND REPAIR / REPLACEMENT OF VARIOUS CAPACITY LT SWITCH GEAR i.e MCCBS, ACBS, CONTACTOR, APFC PANELS AND OTHER MISC INSTALLATIONWORK AT AF STN CHANDINAGAR IN AOR OF GE (AF) FARIDABAD
Sl. No. Item Description
1M&L forDisconnecting / taking down / dismantling Solar flat plate collectorof 100/125 LPD capacity for servcing , cleaning and repairing, brazing oftubescomplete and reassembling the same after repair complete all as specified and directed by Engineer-in-Charge.
2M & L for De-scaling, cleaning of hot water and cold water tanks incl heat collecting units with heat absorbing sheet etc of solar heating system of capacity 500 LPD complete all as specified and directed by Engineer-in-Charge.
3M & L for De-scaling, cleaning of hot water and cold water tanks incl heat collecting units with heat absorbing sheet etc of solar heating system of capacity 1000 LPD complete all as specified and directed by Engineer-in-Charge.
4Supply and fixingin replacement electric Heating element 3 KW( for solar water heater)with thermostat for electrical Back up complete all as specified and directed by Engineer-in-Charge
5Supply and Install SS Hot Water Tank of Capacity 500 Ltrs ( suitable for existing) double wall insulated with PUF Insulation machine injectedinner shell SS 316 and Outer Shell SS 304 Stucco Aluminium alloy coated coloured steel complete on roof tops at aheight of 7 ftincl connection of inlet and outlet water connections ccomplete all as specified and directed by Engineer-in-Charge. Make Neropure /Nectar
6All as per item No 5 above but capacity of 1000 ltrs complete all as specified and directed by Engineer-in-Charge.
7M&L for hot water pipe duly insulated with glass wool and aluminium cladding20 mm bore including taking down complete all as specified and directed by Engineer-in-Charge.
8M&L for hot water pipe duly insulated with glass wool and aluminium cladding25 mm bore including taking down complete all as specified and directed by Engineer-in-Charge.
9M&L forreplacement of Gunmetal gate valve with iron wheel head screwed both ends for iron pipe and fixed 25 mm dia including taking down complete all as specified and directed by Engineer-in-Charge.
10M&L for replacement of Gunmetal gate valve with iron wheel head screwed both ends for iron pipe and fixed 20mm dia including taking down complete all as specified and directed by Engineer-in-Charge.
11M&L for replacement of unservicable parts of solar water heater complete with servicable partsand making it servicable complete testing and commsioning and brazing of tanks for arrresting leakages complete all as specified and directed by Engineer-in-Charge. Note : parts will be measured here after as supply only.
12S&F following items (Ser No 13 to 19) for solar water heater 500/1000 LPD complete all as specified and directed by Engineer-in-Charge.
13Absorber Plate made of copper sheet, laser or ultrasonically welded to copper tubes ( Solar flat plate collector as per existing type) with FlangesL-1860 W-1240 H-100, weight 35-42 kg working pressure 490 KPA complete all as specified and directed by Engineer-in-Charge.
14Absorber Plate made of copper sheet, laser or ultrasonically welded to copper tubes ( Solar flat plate collector as per existing type) with Flanges L-1860 W-1240 H-100, weight 35-42 kg working pressure 1300 Kps complete all as specified and directed by Engineer-in-Charge.
15Single pane 3.2 mm tempered low iron glass collector as per existing size and type complete all as specified and directed by Engineer-in-Charge.
16Supply & install 500 Ltr Cold water Tank of material SS-304( as per existing type) with Manhole & Stand complete all as specified and directed by Engineer-in-Charge.
17Supply & install 1000 Ltr Cold water Tank of material SS-304 ( as per existing type) with Manhole & Stand complete all as specified and directed by Engineer-in-Charge.
18Supply & install Makeup Tank for heat exchanger of 5 Liter with ball cock complete all as specified and directed by Engineer-in-Charge.
19Supply & install Back Plact Collector complete all as specified and directed by Engineer-in-Charge.
20M & L for Servicing of OLD/ UNSV -SOLAR street light fittingincluding servicing and Cleaning of solar panel , Low maintenance tubular batteryby filling of Distilled water and first charging including replacement of damaged battery terminals, securingof all electrical wire circuit and connections, reparing of damaged foundation complete all as specified and directed by Engineer-in-Charge. Note:- 1. All type of T & P, Distilled water, control cable upto battery terminal, PCC, ladder & tripod etc required at site will be arranged by the contractor and rates for the same will be deemed to be included in the quoted rate. (Spares required to make functional of solar light shall be measured and paid seperately under relevent items )
21Spares of Solar security light (Ser No 22 to 25) complete all as specified and directed by Engineer-in-Charge.
22(a) Replacement of Solar PV Module 74W(As per existing)
23(b)Replacement of White LED based light source 12W (As per existing)
24(c) Replacement of Driver of solar street Lights (As per existing)
25(d) Replacement of Battery rating of 12V & 100 AH (As per existing)
26Supply & fixbattery compartment box made up of MS sheet 2mm thick size suitable for battery with MS cover, locking arrangements & fixing accessories with inside weather proof coated & out side Aluminium paint incl writing pole number in black colour paint etc complete all as specified and directed by Engineer-in-Charge.
27S & F in replacement of Integrated all in one Solar Street light (Inbuit Solar PV module and Lithium battery ) 24 watt, secondary optics, LED driver efficiency>92%, battery type LiFePO-04, IP66, colour temperature 6000K-6500K , 140 Lumens per watt Auto On/Off, overcharging protection incl taking down old unser and complete fixing and connection complete all as specified and directed by Engineer-in-Charge.
28Servicingof DG Set 200 KVA of anyMake ,checking entire system as per manufacturer"s catalogue such aschecking all parts for serviceability, taking down defective parts such as fuel filter assembly, by pass filter assembly, lube oil filter assembly, air cleaner assembly lube oil hose flexible pipe, hose turboetc including replacement the same with same size, make and capacity of parts Such as Fuel filter, Lube oil filter, Air filter, coolant and Engine oil ,hose pipe,Diesel filter with gasketetc and draining out the old used burnt engine oil from the oil sump and cleaning oil sump with suitable cleaning solution such as petrol and diesel or anyother cleaning solution and refilling new engine oil required grade up to required level and including checking of AMF control panel, tightening of loose connections and testing to DG Set to the entire satisfaction of the Engineer-in-Charge Make -Greaves Cotton Note :(i)Engine oilshall be measured and paid for separately under successive items here-in-after. However, labour charge are deemed to be included in item rate above.(ii) Servicing shall be carried out by authorised dealer of manufacturer. (iii) Minimum 6 months gap/200 Hrs of run whichever is earlier shall be considered for next service.(iv) Repair Guarantee forreplaced parts/servicing ofDG Set shall be for six month from the date of service.
29All as per item No. 28 but DG set of capacity 180 KVA complete all as specified and directed by Engineer-in-Charge.
30All as per item No. 28 but DG set of capacity 110 KVA complete all as specified and directed by Engineer-in-Charge.
31All as per item No. 28 but DG set of capacity 75 KVA complete all as specified and directed by Engineer-in-Charge.
32All as per item No. 28 but DG set of capacity 62.5 KVA complete all as specified and directed by Engineer-in-Charge.
33All as per item No. 28 but DG set of capacity 15 KVA complete all as specified and directed by Engineer-in-Charge.
34S & F for Fan belt set suitable as per existing for 15 kVA to 200 kVA DG Setof any type any makecomplete all as specified and directed by Engineer-in-Charge.
35S& F for New dehydrated Engine oil as required grades suitable as per existing for 15 kVA to 200 kVA DG Set of any type any makecomplete all as specified and directed by Engineer-in-Charge. NOTE: Engine oil will be suppied in manufacturer sealed barrel Make :- Indian oil / Hindusthan petrolium / Castrol / Pride /Servo
36Taking down of radiator from DG set (15 kVA to 200 kVA DG) of any type any make carefully cleaning of tubes and fins complete with thehelp of proper cleaning agent and wire brush soldering of tubes and fins at required places testing and refilling complete all as specified and directed by Engineer-in-Charge.
37Taking down of defective water pump from DG set (15 kVA to 200 kVA DG) of any type any make repair the same bywater pump repair kit removing of leakage refitting after testing complete all as specified and directed by Engineer-in-Charge.
38Repair and Replacement of water pump body assemblysuitable for 15 kVA to 200 kVADG Set of any type any make complete all as specified and directed by Engineer-in-Charge.
39Repair and replacement of self starter motor and charging alternator 24 volts complete set incl dismantling and taking down old unser from DG setsuitable for 15 kVA to 200 kVA DG set of any make any type complete all as specified and directed by Engineer-in-Charge.
40Repair and replacement of self starter motor and charging alternator 12 volts complete set incl dismantling and taking down old unser from DG setsuitable for 15 kVA to 200 kVA DG set of any make any type complete all as specified and directed by Engineer-in-Charge.
41S&F in replacement of solenoid switch suitable for existing DG including all necessary arrangement for kirloskar CUMMINS Gen set of capacity 15 to 200 KVA complete all as specified and directed by Engineer-in-Charge.
42Supply only distilled water of best quality in 05 litrs sealed gallon packing complete all as specified and directed by Engineer-in-Charge.
43M&L for servicing of AMF panel of DG set of capacity upto to 75 KVA cleaning of AMF panel, rectification of defect rewiring replacement of D/S indicator with new indicator of complete AMF panel and replacement of U/S relays under respective item of this schedule complete all as specified and directed by Engineer-in-Charge.
44All as per item No 43above herein but DG Set of capacity above 75 KVAand upto 200 KVA complete all as specified and directed by Engineer-in-Charge.
45M&L for Replacement to unserviceable batteries of 12 volts180 AH with new batteries of 12 volts 180 AH maintenance free complete all as specified and directed by Engineer-in-Charge. Make Exide/Amaron Note: Rate for initial charging are included in unit rate
46Supply & fix Automatic voltage regulator relay 415V AC complete all as specified and directed by Engineer-in-Charge.
47Supply & fixElectronic timer 240V AC, adjustment time 6-120Sec complete all as specified and directed by Engineer-in-Charge.
48Supply & fix reverse power relay, 415V AC complete all as specified and directed by Engineer-in-Charge.
49S&F PVC insulate copper heavy duty 1 mtr long as battery lead suitable for batteries of capacity 24V 180AH complete all as specified and directed by Engineer-in-Charge.
50S&F in replacement of digital multi function meter to read voltage current and power factor including set of CT-1 each complete all as specified and directed by Engineer-in-Charge.
51S&F in replacement of indicating lamp RYB complete all as specified and directed by Engineer-in-Charge.
52S&F in replacement of Auto manual switch complete all as specified and directed by Engineer-in-Charge.
53S&F in replacement of push button switch red with element complete all as specified and directed by Engineer-in-Charge.
54S&F in replacement of push button switch green with element complete all as specified and directed by Engineer-in-Charge.
55S&F in replacement of 3 pole power contactor LT MNX 95 CONTcomplete all as specified and directed by Engineer-in-Charge.
56S&F in replacement of 3 pole power contactor LT MNX 140 CONT complete all as specified and directed by Engineer-in-Charge.
57S&F in replacement of 3 pole power contactor LT MNX 225 CONTcomplete all as specified and directed by Engineer-in-Charge.
58S&F in repair of Autocut Electrical Battery Charger 12V DC, 5 Amp Unit SMPS with Constant Voltage Output with Battery Charging Transformer and Moulded Type Rectifier Unit etc complete all as specified and directed by Engineer-in-Charge.
59All as per item No 58 above but Battary Charger 24V DC, 10 Amp complete all as specified and directed by Engineer-in-Charge.
60M&L for Chemical earthing , Design development supply commissioning and testing EHCC certified ground terminal earthing system hollow tube solid bar CCPRI tested for sensitive signal/Electrical equipments highly anti corrosive long life severe wear conditions in the earth pit and of standardsize ISI marked copper tube out side secondary conductor of 50mm dia and main primary conductor inside 25mm dia 3000mm length ready to install with suitable connecting terminal confirming to IS:3043 1987 specification highly conducive packing material to be filled in earth pits for providing uniform low resistivity anti corrosive hygroscopic medium around the earth system for improving the efficency of current dissipation 20 Kg per bag (3 bag per kit) min or sufficeient quantities required as per site complete incl PCC pits of inside dimension 0.5x0.5x0.5m and suitable cover complete all as specified and directed by Engineer-in-Charge. Note:(i) Rate of Earth work, Earthing electrode, all connections, nut-bolts, washers, complete labour, testing, Earth lead/strip upto 7.5 mtr, char coal dust, common salt, porcelain insulator,PCC earth Pit, CI frame ,RCC cover, funnel with wire mesh are incl in quoted rate andwatering pipe, earth lead protection pipe, test poit, and earth lead exceeding 7.5 mtr are measured and paid separately.
61M&Lfor Providing,PCC 1:3:6 type C-1 using 20 mm graded stone aggreat,for damaged earth pit chamber with fair finish internal surface of concrete chamber of earthcomplete all as specified and directed by Engineer-in-Charge.
62S&F in replacement of80 mm thick PCC pit cover 320 mm x 320 mm of PCC 1:2:4 TYPE B-1 using 20 MM graded stone aggregate including necesssary form work and handle for removing the cover from pit with fair finishcomplete all as specified and directed.
63S&F in replacement of Ceramic insulator of standard size for ligthning strip protection fixed in wall of one mtr distance with suitable size screws complete all as specified and directed by Engineer-in-Charge.
64S&F in replacement Copper strip 20 x 3.0 mm fixed with top of insulator/saddles, fixing with screws , washer etc with help of drill machine for roof conductors and down conductors above ground and and making good disturbed surfaces of walls, floors, etc complete all as specified and directed by Engineer-in-Charge.
65S&F in replacement for Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specified and directed by Engineer-in-Charge.
66Material and Labour for preparing surfaces of DG set of capacity up to 200 KVA by rubbing old paint and applying two coats of spray painting with (existing colour)deco paintfrom outside, complete all as specified and directed by Engineer-in-Charge. Note.(i)Painting of DG will be carried out for plinth mountedDG set .Necessary tools and plants shall be arranged by the contractor.(ii) MES No / SM No has to be written with 3" letters on each DG set after painting with white colour on black background without any extra cost.
67M&L for carrying out repair of complete DG set by taking each and every parts carefully carrying out necessary repairs ofComplete Engine set ( 200 KVA DG Set )in workshop including machining work of parts like of pump nozzle, turbo charger (reconditioning and servicing), head of DG set,cleaning and repairing of radiator, oil pump and refilling of coolant , engine oil as per requirement and guidelines of respective OEMs and replacement of following spares suitable for diesel engine (prime mover) of DG setof capacity 200 KVA including testing complete all as specified and directed by Engineer-in-Charge. Note : Transporting Cahrges of Stn to Workshop and back to stn deemed to beincluded in the rate quoted . (a) Piston ring (m) Mashroom taper (b) Main Bearing(n) Diesel pipe complete set (c) Piston(o) Air filter (d) Packing Kit(p) Water pump (e) "O" ring (q) Fly wheel ring gear (f) Liner (g) Exhaust valve (h) Inlet valve (j) Head gasket kit (k) CR Bearing (l) Diesel filter
68Excavation in trenches in soft/loose soil not exceeding 1.5 Mtr wide and not exceeding 1.5 Mtr depth for laying of cables/poles or foundation etc and getting out complete all as specified and directed by Engineer-in-Charge.
69Returning, filling, including spreading levelling and well ramming in layers not exceeding 25cm apart all as specified and directed by Engineer-In-Charge.
70Removing of surplus excavated soil to a distance not exceeding 50 Mtr from starting point and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and directed by Engineer-in-Charge.
71M&L for sand cushoning with a layer of sand 80mm thick before laying of cable and 150mm thick after laying of cable to trenches complete all as specified and directed by Engineer-In-Charge.
72M&L for sub class `B` bricks for cable protection all as specified and directed by Engineer-In-Charge.
73Taking down UNSV LT Under Ground cable of any size complete all as specified and directed by Engineer-in-Charge.
74Supply and laying, connecting and testing XLPE underground cableinsulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 16 sqmm 4 core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on walletc complete all as specified and directed by Engineer-in-Charge. Note:(i) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highwaysand Aluminium thimbles/lugs are incl in the quoted rates. (ii) All equipments , machinery or toolsif required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
75All as per itemNo 90 here in before but for 3.5 core 25 Sqmm complete all as specified and directed by Engineer-in-Charge.
76All as per itemNo 90 here in before but for 3.5 core 50 Sqmm complete all as specified and directed by Engineer-in-Charge.
77All as per itemNo 90 here in before but for 3.5 core 70 Sqmm complete all as specified and directed by Engineer-in-Charge.
78All as per itemNo 90 here in before but for 3.5 core 95 Sqmm complete all as specified and directed by Engineer-in-Charge.
79All as per itemNo 90 here in before but for 3.5 core 120 Sqmm complete all as specified and directed by Engineer-in-Charge.
80All as per itemNo 90 here in before but for 3.5 core 240 Sqmm complete all as specified and directed by Engineer-in-Charge.
81Supply & fixing or laying in replacement HDPE (DWC) tubing 100 mm dia of pressure rating 6Kgf/Cm2 fixing on poles, walls under floors, laying on surface etcas reqd at site and as per direction of Engr-in-Charge.Note: All items and accessories , bend, joints, nut bolts, clamps etc are incl in quoted rates.
82Supply& fixing in replacement MCCBTPN 63 Amps 415 Volts 16 kA complete all as specified and directed by Engineer-in-Charg
83Supply& fixingin replacement MCCBTPN 100 Amps 415 Volts 16 kA complete all as specified and directed by Engineer-in-Charg
84Supply& fixingin replacement MCCBTPN 125 Amps 415 Volts 16 kA complete all as specified and directed by Engineer-in-Charg
85Supply& fixingin replacement MCCBTPN 160 Amps 415 Volts 36 kA complete all as specified and directed by Engineer-in-Charg
86Supply& fixing in replacement MCCBTPN 200 Amps 415 Volts 36 kA complete all as specified and directed by Engineer-in-Charg
87Supply& fixing in replacement MCCBTPN 250 Amps 415 Volts 36 kA complete all as specified and directed by Engineer-in-Charg
88Supply& fixing in replacement MCCBTPN 450 Amps 415 Volts 36 kA complete all as specified and directed by Engineer-in-Charg
89Supply& fixingin replacement MCCBTPN 630 Amps 415 Volts 50 kA complete all as specified and directed by Engineer-in-Charg
90M&L for in replacment of MCCB 800 A , breaking capacity 65 KA at 415 V, four poleadjustable thermal andadjustable magnetic settings with extended terminals and separator links complete including doing connections with bus bar and outgoing cables , nuts bolts washers complete all as specified and directed by Engineer-in-Charge.Make Havells /L&T or equivalent
91M / L for checking electrical /electronic circuit for finding out fauilty capacitorsandreplacement with Ultra heavy duty box type capacitor suitable for 440 volt50 Hz operation of rated capacity 20 kVAr including taking down old unserviceablecapacitor andand making all circuit connectionand testing for smooth functioningas directed by Engineer in charge.
92All as per item No 107above but 10 kVAr complete all as specified and directed by Engineer-in-Charge.
93All as per item No 107 above but 5 kVAr complete all as specified and directed by Engineer-in-Charge.
94Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 25 to 50 sqmm,Indoor/Outdoor type complete all as specified and directed by Engineer-in-Charge.
95All as item serNo 110 abovebut for cable of size 70 to 120 sq mm complete all as specified and directed by Engineer-in-Charge.
96Supply and fixing in replacementof on loadchangeover switches 4 pole 400 Amps , 415 volts , open type fixed in existing panelallows changeover from main supply to generator supply & vice versacomplete all as specified and directed by Engineer-in-Charge.
97Supply and fixing in replacementof on loadchangeover switches 4 pole 200 Amps , 415 volts , open type fixed in existing panelallows changeover from main supply to generator supply & vice versacomplete all as specified and directed by Engineer-in-Charge.
98S&F on load Change Over switch 415V in sheet metal enclosures 4 pole of capacity 400 Amps 415 Voltinclmaking suitable arrangement to fix on wall/panel as requiredcomplete all as specified and directed by Engineer-in-Charge.Make Havells/L&T/Legrand
99S&F on load Change Over switch 415V in sheet metal enclosures 4 pole of capacity 200 Amps 415 Voltinclmaking suitable arrangement to fix on wall/panel as requiredcomplete all as specified and directed by Engineer-in-Charge.Make:Havells/L&T/Legrand
100S & F in replacement of hot pressedmoulded SMC boxes with hinged door fixing of size 325mm x 220 mmx 150 mm with MS clamp 25 x 3mm made to shape with necessry nuts bolts clamps and washers complete comprising of Aluminium bus bar 63 Amps capacity of suitable size -04 nos mounted over Porcelain insulator with nuts & bolts washers incl MCB SP 6 amps and making incoming and outging connections by taking out loops of cable of any size incl necesary excavations and other civil works complete all as specified and directed by Engineer-in-Charge.Make :- Sintex /Universal/ SMS
101M&L for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common saltin alternate layersof 15 cm depth and earth plate electrode connected to galvanised earth lead wire of 4.0mm dia at two points by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through GI pipe for protection of earth lead wire and arrangement of watering pipe incl PCC earth pit (1:3:6) type C-2 with CI frame andRCC cover all as shown in electrical Plate No 3 on SSR Part-Iincluding testing and dismantling ,taking down old unser earthing complete all as specified and directed by Engineer-in-Charge. Note:(i) Rate of Earth work, Earthing electrode, all connections, nut-bolts, washers, complete labour, testing, Earth lead upto 7.5 mtr, char coal dust, common salt, porcelain insulator, PCC earth Pit, CI frame ,RCC cover, funnel with wire mesh are incl in quoted rate andwatering pipe, earth lead protection pipe, test poit, earth lead exceeding 7.5 mt are measured and paid separately.
102All as per item No 117 above but using GI Strip 25x4 mm as earthing lead complete all as specified and directed by Engineer-in-Charge.
103M&L for Chemical earthing , Design development supply commissioning and testing EHCC certified ground terminal earthing system hollow tube solid bar CCPRI tested for sensitive signal/Electrical equipments highly anti corrosive long life severe wear conditions in the earth pit and of standardsize ISI marked copper tube out side secondary conductor of 50mm dia and main primary conductor inside 25mm dia 3000mm length ready to install with suitable connecting terminal confirming to IS:3043 1987 specification highly conducive packing material to be filled in earth pits for providing uniform low resistivity anti corrosive hygroscopic medium around the earth system for improving the efficency of current dissipation 20 Kg per bag (3 bag per kit) min or sufficeient quantities required as per site complete incl PCC pits of inside dimension 0.5x0.5x0.5m and suitable cover complete all as specified and directed by Engineer-in-Charge. Note:(i) Rate of Earth work, Earthing electrode, all connections, nut-bolts, washers, complete labour, testing, Earth lead/strip upto 7.5 mtr, char coal dust, common salt, porcelain insulator,PCC earth Pit, CI frame ,RCC cover, funnel with wire mesh are incl in quoted rate andwatering pipe, earth lead protection pipe, test poit, and earth lead exceeding 7.5 mtr are measured and paid separately.
104Supply and fixing in repair of Earth continuity GI wire of 4 mm dia or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required complete all as specified and directed by Engineer-in-Charge.
105Supply and fixing in repair of Earth continuity strip or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or fixed on wall with porcelain insulator or any other indicated situation for loop earthing etc. as required 25x4 mm GI strip complete all as specified and directed by Engineer-in-Charge.
106All As per item No 121 above but Copper Strip 20x3 mm complete all as specified and directed by Engineer-in-Charge.
107Supply installation,testing commissioning in replacement of horizontal single mounted single phase 220 V/250 V 6000 RPM 50 Hz, AC siren audible range 2 Km 1/4 HP complete incl necessary grounting on wall/roof etc incl connections complete all as specified and directed by Engineer-in-Charge.
108Surface dressing in soft/loose soil not exceeding 15 cm deep complete all as specified and directed by Engineer-in-Charge.
109M&L Broken stone or boulders Hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick inclspreading lime stone powder under stones complete all as specified and directed by Engineer-in-Charge.
110Repair and replacement of Digital Clamp meter for measuring current, voltage and other parameters , AC current range 600 A, AC voltage range 600 Volt,data hold , Auto range, low battery indicator,Auto power offand buzzer, CAT II 600 V safety category incl batteries and complete accessories and complete all as specified and directed by Engineer-in-Charge.
111Repair and replacement of hydraulic crimping machinewith crimping range from 10 sqmmto 400 sqmm with standard dies from 10 mm to 400 mm complete all as specified and directed by Engineer-in-Charge.
112S&F Busbar Chambersuitable size forset of 04 aluminium busbar 400 Amps rating ,supported with suitable size as per direction, each of heavy duty porcelin stand lock with suitable sizeof brass nut, bolts and washer with heat shrinkable PVC sleeving.The bar shall be colour coded (red, yellow and blue) for three phases and black for neutral, The Chambershall be fixed30 cm above the normal ground level complete with PCC foundation (1:2:4 )type B2complete all as specified and directed by Engineer-in-Charge.
113Repair and replacement ofsynthetic insulating mat of thickness not less than 3.0 mm size 2.0 mtr X 1.0 mtr suitable for system voltage 3.3 kVand break down voltage 45 kV confirming IS 15652 : 2006 complete all as specified and directed by Engineer-in-Charge.
114S&F in repair LED Street Light Luminaries 70/ 75 watt fitting aesthetically designed for road lighting, having secondary optics with uniform distribution of light. Pressure die cast aluminum housing powder coated in grey and toughened glass, IP 66 protection, class I with operating voltage range 120 to 270 V including LED driver complete all as specified and directed by Engineer-in-Charge.
115S&F in repair LED Street Light Luminaries 60 watt fitting aesthetically designed for road lighting, having secondary optics with uniform distribution of light. Pressure die cast aluminum housing powder coated in grey and toughened glass, IP 66 protection, class I with operating voltage range 120 to 270 V including LED driver complete all as specified and directed by Engineer-in-Charge.
116S&F in repair LED Street Light Luminaries 35/45 watt fitting aesthetically designed for road lighting, having secondary optics with uniform distribution of light. Pressure die cast aluminum housing powder coated in grey and toughened glass, IP 66 protection, class I with operating voltage range 120 to 270 Vincluding LED driver complete all as specified and directed by Engineer-in-Charge.
117M&L for detecting of fault in LT UG cable any sizewith fault locator equipmentto locate the fault in HT cable of length not less than 50 RM complete all as specified and directed by Engineer-in-Charge. Note :- (a) The fault which is detected through cable fault locater will only be paid under this item (b) Charges of cable fault locator including transportation charges deemed to be included in the quoted rate.(c ) Earth fault locator will be provided by the contractor for even singlefault and no dealy on this account will be acceptable otherwise penality will levied Rs 500/- per day. (d) Necessarytesting of cable after making joint will be deemed to be including in the cost of relevent item.However necessary earth work cable cutting , joint makingJointwill be paid under relevant item.
118Supply and fixing in replacement of Mushroomshaped decorative LED bollard with IP 65 protection and9 watt capacity warm white , 240 Volts AC, 50 Hz, incl make proper connection complete includingPCC, cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engineer-in-Charge.
119Supply and fixing in replacement of Cylindricalshaped (FLUTE)LED bollard with opal acrylic diffuser and IP 65 protection and9 watt capacity warm white , 240 Volts AC, 50 Hz, incl make proper connection complete includingPCC,cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engineer-in-Charge.
120Supply and fixing in replacement of Tulip shapedLED bollard with opal acrylic diffuser and IP 65 protectionand9 watt capacity warm white , 240 Volts AC, 50 Hz, incl make proper connection complete includingPCC, cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engineer-in-Charge.
121Supply and fixing in replacement of Rectangular shaped victorian design (TETRIS) LED bollard with opal acrylic diffuser and IP 65 protectionand9 watt capacity warm white , 240 Volts AC, 50 Hz, incl make proper connection complete including PCC, cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engineer-in-Charge.
122Supply and fixing in replacement of LED post top 20 W in made in die-cast aluminium housing with decorative clear opal acrylic diffuser IP 65 protection, warm white , 240 Volts AC, 50 Hz, incl make proper connection complete including cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed by Engineer-in-Charge.
123M&L for surface cleaning of LT electric panel(cubicle type ,size /capacity as per existing) installed at different location in the Stn including scrubbing /rubbing (old paint)all body surface to get all foregin particals removed off and applying two coat of spray painting withsynthetic enamel paint(deco paint and existing colour )overa coat of metal primer(red oxide primer ) and disconnecting of all electrical connectionlike bas bar, CTs,MCCBs and all wirings,equipments and refix ( reconnection) with new Gun metal nut,bolt and washer complete with new copper lead wiring complete all as specified and directed by Engineer-in-Charge.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail