Tender For Construction Of 110/11 Kv Substation And 11Kv Ug Cable Distribution Network At Kerala Rubber Limited, velloor-Kerala

KIIFCON Private Limited-agecode007 has published Tender For Construction Of 110/11 Kv Substation And 11Kv Ug Cable Distribution Network At Kerala Rubber Limited. Submission Date for this Tender is 30-05-2023. Substation Tenders in velloor Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

37701964
Tender For Construction Of 110/11 Kv Substation And 11Kv Ug Cable Distribution Network At Kerala Rubber Limited
Open Tender
Indian
Kerala
velloor
30-05-2023

Tender Details

Construction Of 110/11 Kv Substation And 11Kv Ug Cable Distribution Network At Kerala Rubber Limited Promotion Of Natural Rubber Based Industrialization In Kerala With Focus On Msme Sector_ Construction Of 110/11 Kv Substation And 11Kv Ug Cable Distribution Network_Package 3

Key Value

Document Fees
INR 17700 /-
EMD
INR 500000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Promotion of Natural Rubber based Industrialisation in Kerala with focus on MSME Sector - Package 3- 110/11KV, 12.5/16MVA substation and 11KV UG cable distribution network.
Sl. No. Item Description
1CLEARING JUNGLE 2.33.1 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 30 cm girth up to and including 60 cm girth
2CLEARING JUNGLE 2.33.2 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 60 cm girth up to and including 120 cm girth
3CLEARING JUNGLE 2.33.3 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyond 120 cm girth up to and including 240 cm girth
4CLEARING JUNGLE 2.31 Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared
5EARTHWORK 2.8.1 Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
6EARTHWORK 2.26.1 Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil
7EARTHWORK 2.34.1 Supplying chemical emulsion in sealed containers including delivery as specified.Chlorpyriphos / Lindane emulsifiable concentrate of 20%
8EARTHWORK 50.2.3.1 Pumping or Bailing out water and removing slush etc by using pump set including cost of labour, oil hire charges of pumpset, etc complete
9EARTHWORK 50.2.25.1 Filling with contractor"s own earth ( excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m as per direction of site Engineer-in-charge
10EARTHWORK 2.25 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
11EARTHWORK 2.35.1.1 Diluting and injecting chemical emulsion for POST -CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion):Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a depth of 300mm including excavation channel along the wall & rodding etc. complete:With Chlorpyriphos /Lindane E.C. 20% with 1% concentration
12PILING AND PCC WORK 4.1.8 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
13PILING AND PCC WORK 20.2.4 Boring, providing and installing bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring, with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. all complete, including removal of excavated earth with all lifts and leads (Length of pile for payment shall be measured upto bottom of pile cap).500 mm dia piles
14PILING AND PCC WORK 20.6.1.2 Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile upto 50 tonne capacityRoutine test
15PILING AND PCC WORK 20.6.2.1 Vertical load testing of piles in accordance with IS 2911( Part IV) including installation of loading platform and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of engineer -in-Charge.Single pile above 50 tonne and upto 100 tonne capacityInitial test
16PILING AND PCC WORK 5.33.1 Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work upto plinth level
17PILING AND PCC WORK 5.22.6 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
18PILING AND PCC WORK 2.20.1 Open timbering in trenches including strutting and shoring complete ( measurements to be taken of the face area timbered ):Depth not exceeding 1.5 m
19PILING AND PCC WORK 2.20.2 Open timbering in trenches including strutting and shoring complete ( measurements to be taken of the face area timbered ):Depth exceeding 1.5 m but not exceeding 3 m
20PILING AND PCC WORK od402005/2022_2023 Supplying, laying and compaction in layers in trenches not exceeding 15 cm, consolidating each deposited layer by ramming, lead up to 50 m and lift up to 3 m, of aggregate of size 20mm(60%) and 12mm (40%).
21PILING AND PCC WORK od9176/2023_2024 Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water proofing cement compound consisting of applying : a) after surface preparation, first layer of slurry of cement @ 0.488 kg/ sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. laying second layer of fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/ sqm mixed with water proofing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire treatment will be taken upto 30 cm on parapet wall and tucked into groove in parapet all around. (For the purpose of measurement the entire treated surface will be measured)
22RCC WORK 5.9.1 Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
23RCC WORK 5.9.3 Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
24RCC WORK 5.9.5 Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
25RCC WORK 5.9.6 Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
26RCC WORK 5.9.16.1 Centering and shuttering including strutting, etc. and removal of form for:Edges of slabs and breaks in floors and wallsUnder 20 cm wide
27RCC WORK 5.9.19 Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges
28RCC WORK 5.30 Add for plaster drip course / groove in plastered surface or moulding to R.C.C. projections
29RCC WORK 5.33.2 Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately.All work above plinth level upto floor V level
30RCC WORK 5.22A.6 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more
31RCC WORK od402043/2022_2023 Conveying the covering slab from the place of casting and place it properly over the already constructed cable trench etc. complete .
32RCC WORK Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size)
33BRICK WORK sand :3 graded stone aggregate 20 mm nominal size
34BRICK WORK sand :3 graded stone aggregate 20 mm nominal size
35BRICK WORK 50.6.3.1 Solid block masonry using pre cast solid blocks ( Factory made) of size 40x20x10cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth for 10 cm thick wall in CM 1:6 ( 1 cement : 6 coarse sand) including cost of scaffolding etc complete
36FINISHING 13.2.1 15 mm cement plaster on the rough side of single or half brick wall of mix:1:4 (1 cement :4 fine sand)
37FINISHING 13.4.1 12 mm cement plaster of mix:1:4 ( 1 cement : 4 coarse sand)
38FINISHING 13.16.1 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
39FINISHING 13.43.1 Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
40FINISHING 13.44.1 Finishing walls with water proofing cement paint of required shade:New work (Two or more coats applied @ 3.84 kg/10 sqm)
41FINISHING 13.46.1 Finishing walls with Acrylic Smooth exterior paint of required shade:New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
42FINISHING 13.48.1 Finishing with Deluxe Multi surface paint system for interiors and exteriors using primer as per manufacturers specifications:Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm
43FINISHING 13.80 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete
44FINISHING 22.5 Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
45FINISHING 10.17 Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete.
46FINISHING 8.3.2 Providing edge moulding to 18 mm thick marble stone counters, vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer -in-Charge.Granite work
47FINISHING 8.5 Extra for providing opening or required size & shape for wash basin/kitchen sink in kitchen platform, vanity counter and similar location in marble/granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
48FINISHING 22.23.1 Providing and applying integral crystalline slurry of hydrophilic in nature forwaterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 partsintegral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 partsintegral crystalline slurry : 1 part water) for horizontal surfaces and applying thesame from negative (internal) side with the help of synthetic fiber brush. The materialshall meet the requirements as specified in ACI-212-3R-2010 i.e by reducingpermeability of concrete by more than 90% compared with control concrete as perDIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystallineslurry shall be capable of self-healing of cracks up to a width of 0.50mm. The workshall be carried out all complete as per specification and the direction of the engineerin-charge. The product performance shall carry guarantee for 10 years against anyleakage.For vertical surface two coats @0.70 kg per sqm
49FINISHING 22.23.2 Providing and applying integral crystalline slurry of hydrophilic in nature forwaterproofing treatment to the RCC structures like retaining walls of the basement,water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 partsintegral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 partsintegral crystalline slurry : 1 part water) for horizontal surfaces and applying thesame from negative (internal) side with the help of synthetic fiber brush. The materialshall meet the requirements as specified in ACI-212-3R-2010 i.e by reducingpermeability of concrete by more than 90% compared with control concrete as perDIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystallineslurry shall be capable of self-healing of cracks up to a width of 0.50mm. The workshall be carried out all complete as per specification and the direction of the engineerin-charge. The product performance shall carry guarantee for 10 years against anyleakage.For horizontal surface one coat @1.10 kg per sqm.
50FLOORING 8.2.2.2 Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
51FLOORING 8.31 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622(thickness to be specified by the manufacturer), of approved make, in all colours,shades except burgundy, bottle green, black of any size as approved by Engineerin-Charge,in skirting, risers of steps and dados, over 12 mm thick bed of cementmortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @3.3kg per sqm, including pointing in white cement mixed with pigment of matchingshade complete.
52FLOORING 11.21.2.1 Providing and fixing 10 mm thick acid and /or alkali resistant tiles of approved make and colour using acid and / or alkali resisting mortar bedding, and joints filled with acid and /or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in-Charge.In dado/ skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand)Acid and alkali resistant tile
53FLOORING 4.17 Making plinth protection 50 mm thick of cement concrete 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75 mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth.
54FLOORING 16.68 Providing and laying 60 mm thick factory made cement concrete interlocking paver block of M - 30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.
55FLOORING 13.9.1 Cement plaster 1:3 ( 1 cement : 3 coarse sand) finished with a floating coat of neat cement.12 mm cement plaster
56FLOORING 11.4 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer"s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete
57FLOORING 11.41.2 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
58FLOORING 11.46.2 Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm
59FLOORING 11.21.1.1 Providing and fixing 10 mm thick acid and /or alkali resistant tiles of approved make and colour using acid and / or alkali resisting mortar bedding, and joints filled with acid and /or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in-Charge.In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand)Acid and alkali resistant tile
60FLOORING 4.20.2.1 Providing and laying in position ready mixed plain cement concrete, with cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, excluding the cost of centering, shuttering and finishing, including cost of curing, admixtures in recommended proportions as per IS:9103 to accelerate/retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineer - in - charge. Note : 1) Excess /less cement used than specified in this item is payble / recoverable separately.All works above plinth and upto floor V level :M- 15 grade plain cement concrete (cement content considered @ 240 kg /cum)
61FLOORING od402067/2022_2023 Providing and laying Antiskid Ceramic floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), including pointing the joints with white cement and matching pigment etc., complete.
(Rate of tile Rs.50/sqft)(Data Based on 11.37)
62JOINERY 9.83 Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm),with necessary accessories and screws etc. complete.
63JOINERY 9.121 Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminated shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2 mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame.
64JOINERY 9.122.1 Providing and fixing to existing door frames.30 mm thick Glas Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS : 14856, including fixing to frames.
65JOINERY 10.6.1 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.25 mm M.S. laths with 1.25 mm thick top cover
66JOINERY 21.1.2.3 For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micorn)
67JOINERY 21.1.1.2 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS :733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc.Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
68JOINERY 21.2.2 Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
69JOINERY 21.3.2 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness
70JOINERY 21.3.3 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 8 mm thickness
71JOINERY 11.8 Extra for making chequers of approved pattern on cement concrete floors, steps, landing, pavements etc
72JOINERY 9.97.3 Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:200x10 mm
73JOINERY 9.97.5 Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:100x10 mm
74JOINERY 9.100.1 Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm
75JOINERY 9.113 Providing and fixing bright finished 100 mm mortice lock with 6 levers without pair of handles of approved quality for aluminium door, with necessary screws etc complete as per direction of Engineer- in- charge
76JOINERY 9.101.1 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Single rubber stopper
77JOINERY 10.7 Providing and fixing ball bearing for rolling shutters.
78JOINERY od402049/2022_2023 Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:200mm
79SANITARY INSTALLATIONS 17.34.2 Providing and fixing toilet paper holder:Vitreous china
80SANITARY INSTALLATIONS 17.71 Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms
81SANITARY INSTALLATIONS 17.81 Providing and fixing floor mounted, white vitreous china single piece, doubletraps syphonic water closet of approved brand/make, shape, size and patternincluding integrated white vitreous china cistern of capacity 10 litres with dualflushing system, including all fittings and fixtures with seat cover, cistern fittings,nuts, bolts and gasket etc including making connection with the existing P/Strap, complete in all respect as per directions of Engineer-in-Charge.
82SANITARY INSTALLATIONS 50.17.1.3 Supplying and fixing CP Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge
83SANITARY INSTALLATIONS 50.17.1.5 Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge
84SANITARY INSTALLATIONS 18.16.1 Providing and fixing brass stop cock of approved quality :15 mm nominal bore
85SANITARY INSTALLATIONS 18.16.2 Providing and fixing brass stop cock of approved quality :20 mm nominal bore
86SANITARY INSTALLATIONS 18.51.1 Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
87SANITARY INSTALLATIONS 17.7.7 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Flat back wash basin size 450x300 mm with single 15 mm C.P. brass pillar tap
88SANITARY INSTALLATIONS 17.32.3 Providing and fixing mirror of superior glass ( of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :Oval shape 450x350 mm (outer dimensions)
89SANITARY INSTALLATIONS 18.63 Providing and fixing PTMT angle stop cock 15 mm nominal bore, weighing not less than 85 gms
90SANITARY INSTALLATIONS 18.53.1 Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 893115 mm nominal bore
91SANITARY INSTALLATIONS 17.7.6 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Angle back wash basin size 400x400 mm with single 15 mm C.P. brass pillar tap
92SANITARY INSTALLATIONS 17.28.1.1 Providing and fixing P.V.C. waste pipe for sink or wash basin including PVC.waste fittings complete.Semi rigid pipe32 mm dia
93SANITARY INSTALLATIONS 17.77.1 Providing and fixing M.S.holder bat clamp of approved design to sand cast iron /cast iron (spun) pipes comprising of M.S. flat brackets made of 50x5 mm flat of specified shape, projecting 75 mm outside the wall surface and fixed on wall with 4 nos, 6 mm dia expansion hold fasteners, including drilling necessary holes in brick wall / CC/RCC surface and the cost of bolts etc. The pipes shall be fixed to the already fixed brackets with the help of 30 mm x 1.6 mm galvanised M.S. flats of specified shape and of total length 420 mm and shall be fixed with M.S. nuts, bolts, & washers of size 25x6 mm, one bolts on each side of the pipe.Total bracket length 580 mm of approved shape and design ( for single 100 mm dia pipe)
94SANITARY INSTALLATIONS 18.21.1.2 Providing and fixing uplasticised PVC connection pipe with brass unions:30 cm length20 mm nominal bore
95SANITARY INSTALLATIONS od9083/2023_2024 Making soak pit 1.2 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey
comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long
complete as per standard design.
With common burnt clay F.P.S. (non modular) bricks of class designation 7.5.
96WATER SUPPLY 18.7.3 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall25 mm nominal outer dia pipes
97WATER SUPPLY 18.8.3 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal outer dia pipes
98WATER SUPPLY 18.17.1 Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) :25 mm nominal bore
99WATER SUPPLY 18.18.3 Providing and fixing ball valve (brass) of approved quality, High or low pressure, with plastic floats complete:25 mm nominal bore
100WATER SUPPLY 18.37.1 Constructing masonry chamber 60x45x50 cm inside, in brick work in cement mortar 1:4 ( 1 cement : 4 coarse sand) for water meter complete with C.I double flap surface box 400x200x200 mm ( inside ) with locking arrangement and RCC top slab 1:2:4 mix ( 1 cement : 2 coarse sand : 4 grades stone aggregate 20 nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5fine sand : 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 ( 1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design:With common burnt clay F.P.S. ( non modular ) bricks of class designation 7.5
101WATER SUPPLY 18.60.1 Providing and fixing enclosed type water meter (bulk type) conforming to IS: 2373 and tested by Municipal Board complete with bolts, nuts, rubber insertions etc. ( The tail pieces if required will be paid separately):80 mm dia nominal bore
102WATER SUPPLY 18.48 Providing and placing on terrace (at all floor levels) polyethylene water storage tank :ISI 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.
103WATER SUPPLY 18.62.3 Providing and fixing PTMT Ball cock of approved quality, colour and make complete with Epoxy coated aluminium rod with L.P / H.P.H.D plastic ball.25 mm nominal bore, 152 mm long, weighing not less than 440 gms
104WATER SUPPLY 18.74.1 Providing and fixing unplasticised P.V.C. connection pipe with PTMT Nuts, Collar and bush approved quality and colour .15 mm nominal bore with 30 cm length
105WATER SUPPLY 18.74.2 Providing and fixing unplasticised P.V.C. connection pipe with PTMT Nuts, Collar and bush approved quality and colour .15 mm nominal bore with 45 cm length
106WATER SUPPLY 18.75.1 Providing and fixing PTMT extension nipple for water thank pipe, fittings of approved quality and colour .15 mm nominal bore weighing not less than 32 gms
107WATER SUPPLY 18.75.2 Providing and fixing PTMT extension nipple for water thank pipe, fittings of approved quality and colour .20 mm nominal bore, weighing not less than 40 gms
108WATER SUPPLY 18.75.3 Providing and fixing PTMT extension nipple for water thank pipe, fittings of approved quality and colour .25 mm nominal bore, weighing not less than 62 gms
109WATER SUPPLY 18.53A Providing and fixing C.P. Brass extension nipple (size 15mmx50mm) ofapproved make and quality as per direction of Engineer-in-charge
110DRAINAGE 50.18.8.6.2 Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 50 mm pipe 6 kgf/cm2
111DRAINAGE 50.18.8.8.1 Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 75 mm pipe 6 Kgf/cm2
112DRAINAGE 50.18.8.9.1 Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chased and making good the wall etc. 110 mm pipe 6kgf/cm2
113DRAINAGE 50.18.9.9.1 Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
114DRAINAGE 50.18.9.18.1 Providing and fixing PVC pipes including fixing the pipe with clamps/clips at 1.00 m spacing. This included jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 75 mm dia 6Kgf/cm2 - External work- Exposed on wall
115DRAINAGE 50.18.9.19.1 Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall
116DRAINAGE 19.2.1 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all - round S.W. pipes including bed concrete as per standard design:100 mm diameter S.W. pipe
117DRAINAGE 19.2.2 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all - round S.W. pipes including bed concrete as per standard design:150 mm diameter S.W.pipe
118DRAINAGE 19.4.1.1 Providing and fixing square-mouth S.W. gully trap class SP -1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design:100x100 mm size P typeWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5
119DRAINAGE 19.4.2.1 150x100 mm size P typeWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5
120DRAINAGE 17.60.1.1 Providing and fixing trap of self cleansing design with screwed down or hinged grating without vent arm complete, including cost of cutting and making good the walls and floors:100 mm inlet and 100 mm outletSand cast iron S & S as per IS : 3989
121DRAINAGE 18.77 Cutting holes up to 15x15 cm in R.C.C. floors and roofs for passing drain pipe etc. and repairing the hole after insertion of drain pipe etc. with cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size), including finishing complete so as to make it leak proof
122DRAINAGE 51.19.ST4 Supplying and installing ready made PVC Septic tank including the cost of carriage, trenching, placing at the level below ground level as specified as per the direction of engineer in charge (Provision for CC/RCC/Sand/06mm aggregate for the preparation of bed shall be paid separately)4. 35 to 50 flush capacity
123DRAINAGE 50.18.9.21 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Elbow
124DRAINAGE 50.18.9.21.2 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia 45 degree Elbow
125DRAINAGE 50.18.9.21.3 Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia Door Elbow
126DRAINAGE 50.18.9.21.4 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Bend
127DRAINAGE 50.18.9.21.5 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75x75x75 mm dia Tee
128DRAINAGE 50.18.9.21.6 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75x75x75 mm dia Door Tee
129DRAINAGE 50.18.9.21.7 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Vent cowl
130DRAINAGE 50.18.9.21.8 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia End cap
131DRAINAGE 50.18.9.21.9 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 75 mm dia Socket /coupling
132DRAINAGE 50.18.9.21.10 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75x63 mm dia Reducer
133DRAINAGE 50.18.9.22.1 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia Elbow
134DRAINAGE 50.18.9.22.2 Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia 45 degree Elbow
135DRAINAGE 50.18.9.22.3 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement-110 mm dia Door Elbow
136DRAINAGE 50.18.9.22.4 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend
137DRAINAGE 50.18.9.22.5 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes including jointing with PVC solvent cement 110x110x110 mm dia Tee
138DRAINAGE 50.18.9.22.6 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x110x110 mm dia Door tee
139DRAINAGE 50.18.9.22.7 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x110x75 mm dia Door Tee
140DRAINAGE 50.18.9.22.8 Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl
141DRAINAGE 50.18.9.22.9 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia offset
142DRAINAGE 50.18.9.22.10 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia End Cap
143DRAINAGE 50.18.9.22.11 Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes,including jointing with PVC solvent cement - 110 mm dia Socket/ coupling
144DRAINAGE 50.18.9.22.12 Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x75 mm dia Reducer
145DRAINAGE 19.30.2.1 Constructing brick masonry chamber for underground C.I. inpection chamber and bends with bricks in cement mortar 1:4 ( 1 cement: 4 coarse sand) C.I.cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23kg and weight of frame 15 kg), R.C.C top slab with 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:5:10 (1 cement: 5 fine sand: 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand) finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design:Inside dimensions 500x700 mm and 45 cm deep for pipe line with one or two inlets:With common burnt clay F.P.S (non modular) bricks of class designation 7.5
146DRAINAGE 17.29 Providing and fixing 100 mm sand cast Iron grating for gully trap
147DRAINAGE od376165/2022_2023 Providing and fixing UPVC trap ("P" or "S") of self cleaning design with or without vent horn complete, as shown in detailed drawing including inlet fitting wherever required including cost of cutting and making good the walls & floors. (a) 110 mm inlet and 110 mm outlet
148DRAINAGE od377190/2022_2023 Providing and fixing uPVC Height riser with two or three inlets of 40, 50 / 63 mm size, mm outer dia uPVC pipes and fixed to uPVC traps with rubber ring / solvent cement joint complete
149DRAINAGE 19.6.1 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement : 2 fine sand) including testing of joints etc. complete:100 mm dia R.C. C pipe
150DRAINAGE 19.6.2 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 ( 1 cement : 2 fine sand) including testing of joints etc. complete:150 mm dia R.C.C. pipe
151DRAINAGE od396677/2022_2023 Supplying and fixing C.I with out frame for soak pit: 500 mm diameter C.I. (medium duty) the weight of the cover to be not less than 58 kg
152DRAINAGE 19.7.1.2 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size,) inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) finished with a floating coat of neat cement complete as per standard design:Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weigh of cover 23 kg and weight of frame 15 kg):With Sewer bricks conforming to IS : 4885
153RAINWATER PIPE 12.41.2 Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.110 mm diameter
154RAINWATER PIPE 12.42.2.2 Providing and fixing on wall face unplasticised- PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS :5382, leaving 10 mm gap for thermal expansionSingle pushfit Coupler110 mm
155RAINWATER PIPE 12.42.5.2 Providing and fixing on wall face unplasticised- PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS :5382, leaving 10 mm gap for thermal expansionBend 87.50110 mm bend
156RAINWATER PIPE 12.42.6.2 Providing and fixing on wall face unplasticised- PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS :5382, leaving 10 mm gap for thermal expansionShoe (Plain)110 mm Shoe
157RAINWATER PIPE 12.43.2 Providing and fixing unplasticised- PVC pipe clips of approved design to unplasticised- PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 ( 1 cement : 4 coarse sand) and making good the wall etc. complete.110 mm
158RAINWATER PIPE 12.46 Providing and fixing to the inlet mouth of rain water pipe PTMT ( an Engineering Thermoplastic) grating square (Slit) 150 mm square with a height of 8 mm and weighing not less than 100 gms
159Transformer Yard Steel work: 10.2 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, includingcutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
160Transformer Yard Steel work: 10.16.1Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes
161Transformer Yard Steel work: 10.19Providing and fixing mild steel round holding down bolts with nuts and washer plates complete.
162Transformer Yard Steel work: 16.70.2Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts , bolts and washers as required complete as per the direction of Engineer-in- charge.Made of G.I wire of dia 4 mm. PVC coated to achieve outer dia. not less than 5 mmin required colour and shade
163Transformer Yard Steel work: 9.48.1Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square orround bars etc. including priming coat with approved steel primer all complete.Fixed to steel windows by welding
164Transformer Yard Steel work: od402052/2022_2023Fixing of rail and associated steel work in transformer plinth in single section, with or without connecting plate, including cutting, hoisting, fixing in position ad applying a priming coat of approved steel primer all complete.
165Transformer Yard Steel work: od402053/2022_2023 Bolt setting in concrete (set of 4 leg) during the course of foundation concrete in line and level usingtemplates including cuttibg, drilling and bolting if necessary etc. complete
166Transformer Yard Steel work: od402058/2022_2023Supplying and providing chequered plate 6mm thick fabricated as per required sizes
167Transformer Yard Steel work: od402068/2022_2023 Galvanized structural steel work in single section, fixed with or without connecting plate, including cutting, hoisting, fixing in position all complete.
168FIRE od377937/2022_2023 Supply and installation of ABC Stored pressure type Fire Extinguisher 4 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder as per IS 14609 with ISI Mark for Fighting ABC Class of Fire,stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket. The Extinguisher should be manufactured strictly as per IS: 15683:2006 with ISI mark.
169FIRE od378064/2022_2023 "Supply and installation of Fire Extinguisher, Carbon di-oxide type capacity 4.5 Kg with provision of wall bracket (fixed with anchor fastener) or floor mounted ISI marked (IS:2878) Flat base including valve,discharge hose of not less than 10 mm dia, 1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 filled to a filling rate of not more than 0.667 and wall suspension bracket."
170FIRE od378189/2022_2023 Supply and installation of photoluminescent glow Signage such as Fire exit of standard size (300*150 MM) as per conventional design/ colour code on 3 mm thick Aluminum composite, panel conforming to IS 9457. The signage will be either fixed on the wall with the help of screws & double tape or hanged from the false ceiling with the help of chain & screws etc.
171ROAD WORK 3.6 Excavation for roadwork in soil with hydraulic excavator of 0.9 cum bucket capacity including cutting and loading in tippers, trimming bottom and side slopes, in accordance with requirements of lines, grades and cross sections, and transporting to the embankment location within all lifts and lead upto 1000m
172ROAD WORK 4.12 Providing, laying, spreading and compacting graded stone aggregate to Wet Mix Macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density
173ROAD WORK 5.1.a Providing and applying primer coat with bitumen emulsion ( SS) on prepared surface of granular Base including clearing of road surface and spraying primer at the rate of 0.70 - 1.0 kg/sqm using mechanicalmeans
174ROAD WORK 5.2.c Providing and applying tack coat with bitumen emulsion (RS) using emulsion pressure distributor at the rate of 0.30 - 0.35 kg per sqm on the prepared Cement Concrete pavementcleaned with mechanical broom
175ROAD WORK 5.4.2b Dense Graded Bituminous Macadam : - For grading - II (26.5 mm nominal size) Providing and laying dense graded bituminous macadam with 100-120 TPH batch type HMP producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder (VG 30) @ 4.0 to 4.5 per cent by weight of total mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and alignment, rolling with smooth wheeled,vibratory and tandem rollers to achieve the desired compaction as per MoRTH specification clause No. 505 complete in all respects
176ROAD WORK 5.6.2.b Providing and laying bituminous concrete with 100-120 TPH hot mix plant producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder (NRMB) @ 5.4 per cent of mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MORTH specification clause No. 507 complete in all respects For Grading -II (13.2 mm Nominal size)
177ROAD WORK 4.1.B.1 Construction of granular sub-base by providing graded material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with vibratory roller to achieve the desired density, complete as per clause 401. Grading-V - For sub base cum drainage layer - Mix in Place Method
178OTHER YARD WORKS od402054/2022_2023 Laying and spreading aggregate of specified size on compacted surface in the yard
179OTHER YARD WORKS od402485/2022_2023 Supplying and stacking at size 40 mm size aggregate for spreading in yard.
180OTHER YARD WORKS od402570/2022_2023 Preparation and consolidation of ground after excavating earth to an average 15 cm depth, dressing to camber and consolidating with plate compactor including making good the undulations etc. and disposal of surplus earth with lead upto 50m.
181ELECTRICAL WORKS od375955/2022_2023 -Lightning Arrestor : Supply, Installation, Testing and Commissioning of outdoor Zinc oxide gapless type 50Hz, 96 kV, 10 kA lightning arrestor, of energy class III with surge counter and milli ammeter, with all accessories conforming to IS 3070 with creepage distance of 25mm/KV minimum polymeric insulator and with all accessories including necessary clamps and connectors suitable Al tubular bus bar conductor, supporting steel structure, earthing from equipment to earth mat and compatible for SCADA system as required on suitable existing foundation (Refer detailed technical specification).
182ELECTRICAL WORKS  od375958/2022_2023 -Current Transformer (single core): Supply, Installation, Testing and commissioning of outdoor type live tank design 110 kV, 100/1 A single core CT, 15 VA , class 0.2S accuracy on polymeric insulator with all accessories conforming to IEC 60044-1, IS 2705 with creepage distance of 25mm/ KV minimum on a suitable existing foundation with necessary supporting steel structure, earthing from equipment to earth mat, necessary clamps and connectors suitable for connecting to Al tubular bus bar, and compatible for SCADA system as required complete. The CT should be calibrated from KSEB. (Refer detailed technical specification).
183ELECTRICAL WORKS od376285/2022_2023 -Current Transformer (Three core) : Supply, Installation, Testing and commissioning of outdoor type live tank design 110 kV, 100/1 A three core CT, 15 VA, core 1 having class 0.5 accuracy, core 2 having class 5P10 accuracy and core 3 having PS class accuracy on polymeric insulator with all accessories conforming to IEC 60044-1, IS 2705 with creepage distance of 25mm/ KV minimum on a suitable existing foundation with necessary supporting steel structure, earthing from equipment to earth mat, necessary clamps and connectors suitable for connecting to Al tubular bus bar, and compatible for SCADA system as required complete. (Refer detailed technical specification)
184ELECTRICAL WORKS  od376352/2022_2023-Voltage Transformer with one secondary core: Supply, Installation, Testing and Commissioning of outdoor type of110/v3 kV/110/ v3 V with one secondary Inductive Voltage Transformer with 30 VA, CL 0.2 accuracy for metering with all accessories conforming to IEC 60044-2, IS 3156-1992 with creepage distance of 25mm/ KV minimum on polymeric insulator and with all accessories including necessary clamps and connectors suitable for connecting to Al tubular bus bar conductor, supporting steel structure, earthing from equipment to earth mat and compatible for SCADA system as required complete on a suitable existing foundation. (Refer detailed technical specification).
185ELECTRICAL WORKS od376445/2022_2023-Voltage Transformer with two secondary core: Supply, Installation, Testing and Commissioning of outdoor type of110/v3 kV/110/ v3 V with two secondary Inductive Voltage Transformer with 50 VA, CL 0.5 accuracy for metering and CL 3P for protection with 100VA and all accessories conforming to IEC 60044-2, IS3156-1992 with creepage distance of 25mm/ KV minimum on polymeric insulator and with all accessories including necessary clamps and connectors suitable for Al tubular bus bar conductor, supporting steel structure, earthing from equipment to earth mat and compatible for SCADA system as required complete on suitable existing foundation.(Refer detailed technical specification).
186ELECTRICAL WORKS od376457/2022_2023 -Motorized Double Break Isolator without Earth Switch: Supply, Installation, Testing and Commissioning of outdoor type ,motorized gang operated 3 pole centre rotating solid core porcelain based Isolator with horizontal disconnecting double break, 110 kV, 800 A with out earth switch having minimum creepage distance of 25mm/ kV,31.5 kA 1 sec rated short circuit current and with all accessories including necessary clamps and connectors suitable for connecting to Al tubular bus bar, supporting steel structure, earthing from equipment to earth mat and compatible for SCADA system as required complete on suitable existing foundation and conforming to IS : 9921 & IEC 62271.(Refer detailed technical specification)
187ELECTRICAL WORKS  od376525/2022_2023 -Motorized Double break Isolator with Earth Switch : Supply, Installation, Testing and Commissioning of outdoor type, motorized gang operated 3 pole centre rotating solid core porcelain based Isolator with horizontal disconnecting double break, 110 kV, 800 A with earth switch having minimum creepage distance of 25mm/ KV,31.5 kA / 1 sec rated short circuit current and with all accessories including necessary clamps and connectors suitable for connecting to Al tubular bus bar, supporting steel structure, earthing from equipment to earth mat and compatible for SCADA system as required complete on suitable existing foundation and conforming to IS : 9921 & IEC 62271.(Refer detailed technical specification)
188ELECTRICAL WORKS od376695/2022_2023- 110kV SF6 Circuit Breaker : Supply, Installation, Testing and Commissioning of outdoor spring-spring type live tank design 110kV (rms), 1250 A, 3 pole gang operated 110 kV, rated for 31.5 kA (1 sec) short circuit current, SF6 gas insulated circuit breaker conforming to IEC 62271 having a creepage distance to earth of 25mm/ KV on porcelain insulator, sufficient spare gas in a separate bottle with gas filling kit, on a existing foundation with all accessories including supporting structure, earthing, etc and compatible for SCADA system as required complete. . The circuit breaker shall be IEC 61850 compatible.(Refer detailed technical specification)
189ELECTRICAL WORKS od376820/2022_2023 -ABT Meter - ABT Meter and Check Meter: Supply, Installation, Testing and commissioning of digital ABT meter (Accuracy Class 0.2S) & Check meter for 110kV side including weatherproof kiosk made of 14SWG CRCA sheet powder coated for outdoor installation (IP 54). The item includes contactors, connectors, test terminal block, indication lamp etc. complete as per KSEB standard. (Refer detailed technical specification).
190ELECTRICAL WORKS  od380337/2022_2023 -  110/11KV TRANSFORMER: Supply of Outdoor type 12.5/16 MVA, 110/11kV, ONAN/ONAF, 3 phase,50 Hz, power transformer with OLTC having manual/ motorized controls with digital AVR and communicative interface for SCADA, taps -15 % to +10% in steps of 1.56%, conforming to IS: 2026/77 / IEC 60076 , with provision for nitrogen filled fire protection system, RTCC panel with SCADA compatibility, oil conservator, cooling fans, self-dehydrating breather, Magnetic oil level gauge, first fill of oil and all accessories complete and having the following specifications. Voltage Ratio: 110/11 kV, Vector Group : Dyn11, Type of Winding: Paper insulated, Rectangular copper conductor, Fittings: Standard fittings as per IS:2026/77, The item shall be inclusive of inbuilt 11kV neutral CTs of core-1 1000/1, 15 VA , class PS accuracy for differential protection and core-2 200/5, 15 VA, class 5P10 accuracy for stand-by earth fault protection all accessories complete. The transformer shall be suitable to terminate IPS tube on 110kV side and cables on 11kV side. (Refer detailed technical specification)
191ELECTRICAL WORKS  od376827/2022_2023 - 400kVA Station Transformer: Supply, installation, testing and commissioning of dry type indoor 11/0.433kV, 400kVA, 3 phase, Dyn11, 50 Hz, lasersciber core, copper wound Station auxiliary transformer with off load taps of +5% to -7.5% insteps of 2.5% conforming to IS:11171/85 & IEC 60726 and complete with all accessories . The transformer shall have cable entry for both HV & LV side. The transformer shall have Neutral CT of 100/5A 15VA Cl 5P10 for low set earth fault protection & the relay shall be provided in the MSB panel (Refer detailed technical specification)
192ELECTRICAL WORKS   od376828/2022_2023 - DG Set: Supply, Installation, Testing and Commissioning of 125 KVA radiator cooled, four stroke, multi cylinder electric start D.G Set with acoustic enclosure and control panel. The DG shall have AMF control panel The alternator shall be brushless, self excited, self regulated, brushless, suitable for prime operation at 1500 rpm, generating 415V +/- 5% at 0.8 p.f, 50Hz, 3 phase, 4 wire system generally conforming to BS: 2613 & IS: 4722. Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as anti vibration pad, 2 nos. lead acid batteries (as specified by engine manufacturer) and engine driven battery charger along with leads, battery stand, base fuel tank, Residential silencer, exhaust pipe insulated with hood on top suitable size cable termination box etc as required. The interconnection cable from the generator control panel to ESB for the AMF operation is included in this item. The AMF operation shall be achieved through ATS having AMF facility. The DG shall be provided with external battery charger suitable for lead acid battery provided along with DG set. The battery charger shall have trickle & boost charge with selector switch, protection against over charging, DC ammeter & voltmeter etc.with all accessories shall be provided in the DG control panel. Rate shall be inclusive of all lift, lead, first fill of lubricating oil, diesel for testing & commissioning, necessary spares &accessories, civil work such as grouting, finishing etc excluding foundation as per single line diagram & particular specification. The work should be as per Electrical Inspectorate / Pollution control board norms.
193ELECTRICAL WORKS  od376829/2022_2023 - UPS Supply, installation, testing & commissioning of 5 kVA, single phase input, single Phase output, true on-line UPS system with 15minutes back up, output isolation transformer, including all accessories, SMF batteries VRLA type with powder coated CRCA cabinet including all accessories such as cabling etc as required complete having following specification. The UPS system consist of one numbers of UPS unit and one set of battery bank. The UPS shall Fully digital controlled based on DSP, Power factor corrected from end > 0.9, Pure sine wave output, Full time output voltage & frequency regulation, Auto regulation of battery end voltage, Intelligent interface with LED/LCD display, Static bypass switch / manual bypass switch, Auto temperature compensation. The installation testing and commissioning includes including hoisting to the respective location, assembling of batteries, lining up, bolting the units, checking all the control wirings, pre commissioning checks, all the tests at site as per standards etc complete and as detailed in technical specification.
194ELECTRICAL WORKS od376825/2022_2023- Control and Relay panel CRP - II (110kV Transformer side): Design, Supply, installation, testing and commissioning of indoor type, free standing, Control & Relay Panel for remote operation and protection of 110/ 11kV Transformer bay. The CRP shall be IEC 61850 compatible. The Panel shall be cubicle type, made out of 2mm thick CRCA sheet, totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification. complete with the following accessories. a) Numerical relay for line side Main Protection - Differential & REF Protection. b) Numerical Relay for Back Up Protection: Directional Over Current and Earth Fault Protection. c) Digital Power Analyzer, Voltmeter, Ammeter, Hz meter, MW, MVAR. d) Fault indication, reset, test buttons, reset provisions shall be available in BCU as well as in SAS panel. e) Bay Control Unit. f) TNC switch for Breaker Operation. g)Test terminal Blocks. h) Integration to Process Bus.(Refer Technical specification & Drawing )
195ELECTRICAL WORKS od376815/2022_2023 -Control and Relay panel CRP - I&III (110kV Line side): Design, Supply, installation, testing and commissioning of indoor type, free standing, Control & Relay Panel for remote operation and protection of 110kV line side switchyard equipments in incoming 110kV line bay. The CRP shall be IEC 61850 compatible. The Panel shall be cubicle type, made out of 2mm thick CRCA sheet, totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification. complete with the following accessories. a) Numerical relay for line side Main Protection - Differential Protection. b) Numerical Relay for Back Up Protection: Directional Over Current and Earth Fault Protection. c) Digital Power Analyzer, Voltmeter, Ammeter, Hz meter, MW, MVAR. d)standard SLD and fault indication, reset, test buttons, reset provisions shall be available in BCU as well as in SAS panel. e) Bay Control Unit.f) TNC switch for Breaker Operation.g)Test terminal Blocks. f) Integration to Process Bus.(Refer Technical specification & Drawing)
196ELECTRICAL WORKS  od376826/2022_2023 - 11kV VCB Panel: Supply of 11 kV,1250A 26.3kA( for 3seconds), Electrically operated draw out type VCB with fully encapsulated vacuum interrupter panel with busbar extendable on both side ,fabricated out of 14 gauge AluZinc sheet .The panel shall be arc flash tested with 1250A aluminum busbar & support insulators, space heater with thermostat, cubicle illumination lamp, MCBs for AC/DC Control, 110V DC motor operated spring charged mechanism, anti-pumping device, 110V DC shunt trip and closing coil, necessary control wiring etc having following specific components and as per IS / IEC standards. Incomer - 1 Nos. i)11kV VCB, 1250 A, 26.3kA, 3 sec. for receiving 11kV supply from the 12.5/16 MVA, 110/11kV Transformer - 1 No. ii) 11kV/v3 / 110V/v3, 50VA, Cl 0.5 PT - 1 set. iii) Core 1 - 1000/5A Cl 0.5 15VA resin cast CT for Metering - 1 set, iv) Core II - 1000/5A Cl 5P10 15VA resin cast CT for Protection - 1 Set, v) Core III - 1000/1A Cl PS 15VA resin cast CT for Protection - 1 Set. vi) RYB & ON/OFF LED indication lamps, TNC breaker control switch etc vi) 4A C curve control MCB & 11kV PT HRC Fuse. vii) Numerical relay for protection with IEC 61850 compatibility. viii) Digital Power Analyzer with communication and TOD facility (Schneider Electric PM5310 make or equivalent), ix) Analog meters. Bus PT- 1 No. i) Draw out type bus PT with PT HRC fuse in separate chamber or shall be of plug in/ withdrawal type-3No, ii) One number Earthing Truck for cable side-1no. 11kV VCB Outgoing Panel with 1 no. VCB (For ring and Spare) - 7 nos. i)11kV VCB, 1250 A, 25kA, 3 sec as outgoing - 1 No, ii) Core I - 300/5A Cl 0.5 15VA resin cast CT for Metering - 3 Nos, iii) Core II - 300/5A Cl 5P10 15VA resin cast CT for Protection - 3 Nos. iv) RYB & ON/OFF LED indication lamps etc. v) Numerical relay for protection with IEC 61850 compatibility. vi) Digital Power Analyzer with communication and TOD facility (Schneider Electric PM5310 make or equivalent), vii) Analog meters. Vacuum circuit breaker panels shall conform to IEC 62271. The control voltage should be 110V DC for trip, closing and compatible for SCADA system complete .Each VCB panel should have panel lighting (LED light fixture) and panel heater with temperature control thermostat.
197ELECTRICAL WORKS od382708/2022_2023 - MSB Supply, Installation, Testing & Commissioning of LT Switch Board (MSB), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having IEC 61439 certification and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification. Incomer-1. 630A, FP, 25 kA, Microprocessor based,motorised MCCB ,adjustable over load 0.4In to 1 In and adjustable short circuit 1.5 to 8 Ir and earth fault release,shunt trip,auxiliary and trip alarm contacts - 1no. Busbar.630A TPN busbar chamber with Aluminium busbar. Analoge Meters. 4A,C curve SP MCB-3nos.RYB Indicating lamps LED type - 3 Nos.(0-500)V Class 1 with 90 deg defl. Scale-1 No.Voltmeter selector switch- 1 No.(0-600)A Class 1 with 90 deg defl. Scale-1 Nos.Ammeter selector switch-1 No.600/5 A 15 VA Class 1 CTs -3 Nos. ON/OFF/TRIP indication lamp, LED type-3 Nos. Digital multifunction meter ( V, A, F,pf,kW,kWh) - 1No. Outgoings- 250A,TP+NL 25kA MCCB with thermal release having adjustable over load 0.8 In to 1 In, adjustable short circuit 6 to 10 In -2 Nos. 125A, TP+NL 25kA MCCB with thermal release having adjustable over load 0.8 In to 1 In, adjustable short circuit 6 to 10 In -3 Nos.63A,TP+NL 25kA MCCB with thermal release having adjustable over load 0.8 In to 1 In, adjustable short circuit 6 to 10 In - 3No.
198ELECTRICAL WORKS  od382709/2022_2023 -  Emergency Switch Board (ESB): Supply, Installation, Testing & Commissioning of LT Switch Board (MSB), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having IEC 61439 certification and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification. Incomer- 250A TP+NL Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).- 2nos.250A, 4P, 415V ,Auto transfer switch with AMF facility-1 No. Busbar -250A TPN busbar chamber with Aluminium busbar Meters -4A,C curve SP MCB-6nos RYB Indicating lamps LED type - 6Nos.(0-500)V Class 1 with 90 deg defl. Scale-2 No.Voltmeter selector switch- 2 No. (0-250)A Class 1 with 90 deg defl. Scale-2 No, Ammeter selector switch- 2 No. 250/5 A 15 VA Class 1 CTs -6 Nos, ON/OFF/TRIP indication lamp, LED type-6Nos, Outgoings 125A TP+NL Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).- 4nos. 63A TP+NL Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).- 5nos.
199ELECTRICAL WORKS   od378622/2022_2023- Transformer Rail track: Supply and Installation of Transformer rail track with all necessary accessories. (size 60 lbs/yard i.e. about 29.76 kg/m).
200ELECTRICAL WORKS  od378640/2022_2023 - Earth Wire: Supply Laying , testing & commissioning of 7/3.15 mm GI wire for earth wire as per IS 2141. (For details refer Detailed Technical Specification)
201ELECTRICAL WORKS  od378635/2022_2023- Supply, installation, testing and commissioning of 110KV Porcelain type post insulator. with all accessories including necessary clamps and connectors suitable for connecting to Al tubular bus bar, supporting steel structure, earthing from equipment to earth mat and compatible for SCADA system as required complete on suitable existing foundation (For details refer Detailed Technical Specification)
202ELECTRICAL WORKS od378641/2022_2023 -  2.5"" IPS Aluminum tube: Supply, installation, testing and commissioning 2.5"" IPS Aluminium tube of size of 73.03 mm as Outer Diameter made of rigid aluminum alloy round tube bus bar Schedule 40 with Internal dia of 62.71 mm complete as per specification (For details refer Detailed Technical Specification)
203ELECTRICAL WORKS od378642/2022_2023 - Aluminium connectors & Accessories: Supply & Installation, testing and commissioning of all hardware & its accessories for the erection of 2.5"" Al tube busbar. The item includes Aluminium joints, sleeve for Al tube, connectors, all clamps those connected to Isolator, LA, CT, PT, corona bell for Al tube, clamp for connecting 110kV bushing of transformer to Al tube bus bar, PG clamp, string hardware for shield wire and all other clamps necessary for the connection in the yard etc.
204ELECTRICAL WORKS od385507/2022_2023-  Supply, Stringing, fixing, testing and Commissioning of ACSR Kundah / Moose single conductor for one phase of 110KV bus by cutting the conductor to sufficient length, crimping using compressor / bolting the two ends, washing, cleaning and drying the insulator discs, fixing the conductors to the yard structure including sufficient tension using string of insulators and hardware complete at both ends and fixing of arcing hornes
205ELECTRICAL WORKS  od378643/2022_2023 -  Emergency Push Button: Supply, installation, testing and commissioning of push button station with key lockable mushroom head type push button at OFF position mounted on suitable thermoplastic weather proof UV resistant box of IP 66 protection and to be erected on MS angle frame with necessary foundation & painted or to be grouted to the wall for emergency tripping of transformer
206ELECTRICAL WORKS 2.18- Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
207ELECTRICAL WORKS  2.19- Supplying and fixing 20 amps 415volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top along with 20 amps "C" curve, TPMCB, in sheet enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
208ELECTRICAL WORKS 2.20-  Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket outlet, with 4 pole and earth, metal enclosed plug top alongwith 30 amps "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
209ELECTRICAL WORKS  od377292/2022_2023 -  SCADA: Design, Supply, Installation, Testing and commissioning of Supervisory Control And Data Acquisition System for control and monitoring the operation of the complete 110kV substation including 11kV and RMU distribution system. It shall have the hardware & software necessary for the following operation a) Data connectivity with Numerical relay & digital power analyzer for getting status & indication of all parameters. b) Provision for data connectivity with RMU distribution network for getting the status of RMU & shall have provision for future RMU"s. c) 110kV Isolator, circuit breaker & Earth switch position. d) Tap position indication from OLTC of the 110kV Transformer e) Compatible for getting data from 110kV yard PT, CT, LA. The scope also includes providing the following equipment a) Desktop computer (hot standby) - 2 nos. b) UPS - 1 no. c) Laser Colour Printer - 1 nos d) Inkjet Printers- 1 Nos e) Data connectors - As required f) Intelligent multiplexer - As required g) RS 485 / 232 and Ethernet converter - As required h) GPS system for RTC. i) Communication cables from CRP to SAS, 11kV Panels to SAS- As required. The SCADA system shall perform all the interlock systems as specified by the Electrical Inspectorate. (Refer Technical specification.)
210ELECTRICAL WORKS od378178/2022_2023 - Battery Charger: Supply, installation, testing & commissioning of indoor, floor mounted, IP42, with 60 Amps rated float cum boost type battery charger 110V DC output power supply battery charger with DC switch / MCB DB, digital meters to monitor Voltage and current with RS 485 communication port, indication lamps, protective relays, interconnections, earthing etc. The rate quoted shall be inclusive of all the necessary internal control wiring and accessories as required complete. (Refer detailed technical specification)
211ELECTRICAL WORKS  od378438/2022_2023 -  VRLA Battery: Supply, installation, testing & commissioning of110V Station Battery with 2Volt, 425AH stationary type SMF VRLA batteries (55nos, 2 Volt) on a non-metallic stand capable of supplying continuous load of 60A. The feeder panel shall consist of 63 A MCB incomer and 4 nos. of 32 A MCB outgoing which shall be in the same scope. (Refer detailed technical specification)
212ELECTRICAL WORKS  od381415/2022_2023 -  Split AC Unit: Supply, installation testing and commissioning of 2 TR minimum capacity Hi wall Split air conditioning unit (Indoor and Outdoor Unit) complete with suitable capacity drive motor, air cooled condenser with all accessories, hermetically sealed scroll/rotary compressor, outdoor unit and hi wall units for single phase 230 V supply minimum 5 star rated as per BEE and with suitable stabilizer with necessary supports vibration isolators suitable as required as per manufacturers recommendation, suitably sized copper refrigerant piping as per relevant ASHRAE Standards (both suction and liquid piping) including 19 mm thick closed cell nitrile rubber insulation as per specification interconnecting indoor & outdoor units with required pipe fittings and accessories like bends, tees, reducers, supports finished with 7 mils factory laminated treated fibre glass cloth, necessary power/control cabling, suitably supported on trays/ split clamps etc., CPVC condensate drain pipe (upto 5 m) 6kg/sq.cm of suitable dia connecting the drain pan of the indoor units to nearest drain point with U-trap, insulated with 9 mm thick closed cell nitrile rubber insulation, required pipe fittings and accessories like bends, tees, reducers, supports, clamps, finished with 7 mils factory laminated treated fibre glass cloth, first charge refrigerant gas R410A/R407C, cordless remote etc complete as required as per specification/ISHRAE standards.
213ELECTRICAL WORKS  od378644/2022_2023 : Supply of following 11kV grade XLPE insulated PVC sheathed wire armored aluminum conductor power cable suitable for 11kV earthed system conforming to IS 7098(Part 2) and other relevant standards. (Refer detailed technical specification) 3 Core 300 Sq.mm 11kV(E)
214ELECTRICAL WORKS  od378645/2022_2023: Supply of following 11kV grade XLPE insulated PVC sheathed wire armoured aluminium conductor power cable suitable for 11kV earthed system conforming to IS 7098(Part 2) and other relevant standards. (Refer detailed technical specification) 1 Core 630 Sq.mm 11kV(E)
215ELECTRICAL WORKS od378647/2022_2023: Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminum /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date.2x6 sq.mm Al
216ELECTRICAL WORKS od378929/2022_2023:Supply of following 11kV grade XLPE insulated PVC sheathed wire armored aluminum conductor power cable suitable for 11kV earthed system conforming to IS 7098(Part 2) and other relevant standards. (Refer detailed technical specification) 3C 185 Sq mm Al (E)
217ELECTRICAL WORKS  od379002/2022_2023: Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminum /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date.3.5C 300 Sq mm Al
218ELECTRICAL WORKS od379970/2022_2023: Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date. 3.5C 70 sq.mm Al
219ELECTRICAL WORKS od379852/2022_2023 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date. 3.5C 50 Sq mm Al
220ELECTRICAL WORKS od379216/2022_2023 :Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date. 3.5C 35 Sq mm Al
221ELECTRICAL WORKS  od379854/2022_2023: Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date. 4C 16 Sq mm Al
222ELECTRICAL WORKS  od379919/2022_2023: Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date. 4C 10sqmm AL
223ELECTRICAL WORKS od379346/2022_2023 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, armoured Aluminium /copper conductor control/power cable conforming to IS 7098 (Part 1) amended up to date. 4C 25 Sq mm Al
224ELECTRICAL WORKS od385508/2022_2023: Supply laying and making termination of various sizes of 1.1 kV XLPE insulated armoured copper cable for control/metering cabling for connecting/inter connecting various equipment in 110KV yard to panels in 110KV yard/substation building/CRP/11KV Panels/ other equipment etc including supply of suitable size PVC pipes and accessories for drawing exposed cables as complete etc as per the approved cable schedule, IS/IEC Standards applicable
225ELECTRICAL WORKS od379972/2022_2023:  Supplying and making indoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 1 core, XLPE aluminium conductor cable of 11 KV grade as required - 1CX 630 Sq mm Al
226ELECTRICAL WORKS  10.2.4-  Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: 300 sq. mm
227ELECTRICAL WORKS 9.1.1 - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 6 sq. mm (19mm)
228ELECTRICAL WORKS  9.1.16-  Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 185 sq. mm (57mm)
229ELECTRICAL WORKS  9.1.21 - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2X 35 sq. mm (32mm)
230ELECTRICAL WORKS  9.1.22 - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2 X 50 sq. mm (35mm)
231ELECTRICAL WORKS 9.1.23 -  Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2X 70 sq. mm (38mm)
232ELECTRICAL WORKS  9.1.30 -  Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2X 300 sq. mm (70mm)
233ELECTRICAL WORKS 9.1.32 - Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (25mm)
234ELECTRICAL WORKS 9.1.33- Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm)
235ELECTRICAL WORKS 9.1.34 -Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25 sq. mm (28mm)
236ELECTRICAL WORKS 8.1.2-Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 120 sq. mm and upto 400 sq. mm
237ELECTRICAL WORKS  8.2.2 -  Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc
238ELECTRICAL WORKS  8.3.2 - Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 120 sq. mm and upto 400 sq. mm
239ELECTRICAL WORKS  8.4.2- Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required. Above 120 sq. mm and upto 400 sq. mm
240ELECTRICAL WORKS od380271/2022_2023- Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size on the wall surface as required. Above 120 sq. mm and upto 400 sq. mm
241ELECTRICAL WORKS 7.1.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm
242ELECTRICAL WORKS 7.2.1 Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm
243ELECTRICAL WORKS 7.5.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
244ELECTRICAL WORKS  7.6.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm
245ELECTRICAL WORKS 7.7.1 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
246ELECTRICAL WORKS 7.8.1 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
247ELECTRICAL WORKS 7.8.2 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
248ELECTRICAL WORKS 7.8.3 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
249ELECTRICAL WORKS  7.8.4 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
250ELECTRICAL WORKS  7.9 Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
251ELECTRICAL WORKS  7.10 Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
252ELECTRICAL WORKS od381413/2022_2023 Fabrication, supply and installation of following size of perforated Hot Dipped Galvanised Iron cable tray including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling or clamped on floor/ ceiling/ wall using MS supports including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as required. 150 mm width X 50 mm depth X 1.6 mm thickness
253ELECTRICAL WORKS od381450/2022_2023 Fabrication, supply and installation of following size of perforated Hot Dipped Galvanised Iron cable tray including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling or clamped on floor/ ceiling/ wall using MS supports including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as required. 300 mm width X 50 mm depth X 1.6 mm thickness
254ELECTRICAL WORKS od381506/2022_2023 Fabrication, supply and installation of following size of perforated Hot Dipped Galvanised Iron cable tray including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling or clamped on floor/ ceiling/ wall using MS supports including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as required. 450 mm width X 50 mm depth X 2.0 mm thickness
255ELECTRICAL WORKS  od381540/2022_2023 Fabrication, supply and installation of following size of perforated Hot Dipped Galvanised Iron cable tray including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling or clamped on floor/ ceiling/ wall using MS supports including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as required. 600 mm width X 50 mm depth X 2.0 mm thickness
256ELECTRICAL WORKS  od379651/2022_2023 Earth Mat Supply & laying of 50 X 10 mm GI earth mat in the switch yard at a depth of 0.6m from ground level, made up of GI strip of following sizes for the mesh as well as risers including bracing the strips and applying anticorrosive paints at the joints, after excavating the switch yard before the equipment foundation and concrete works, testing and commissioning and interconnection to equipments, to yard fencing etc complete.
257ELECTRICAL WORKS  od385510/2022_2023 copper bonded Steel Rod Supply ,driving into earth 17.5/20 mm dia copper bonded Steel rod 3M depth to augment the earth mat of the switch yard and connecting the same with 50 x 10 mm GI strip braced with all necessary connectors."
258ELECTRICAL WORKS 5.6 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
259ELECTRICAL WORKS 5.8 Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
260ELECTRICAL WORKS  5.9 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
261ELECTRICAL WORKS od385513/2022_2023 Supplying and laying 50 mm X 6 mm G.I strip at 0.50 metre below ground as stripearth electrode, including connection/ terminating with G.I. nut, bolt, spring, washeretc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nutbolt & spring washer spaced at 50mm)
262ELECTRICAL WORKS od385514/2022_2023 Supplying and laying 50 mm X 10 mm G.I strip at 0.50 metre below ground as stripearth electrode, including connection/ terminating with G.I. nut, bolt, spring, washeretc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nutbolt & spring washer spaced at 50mm)
263ELECTRICAL WORKS  5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
264ELECTRICAL WORKS od380322/2022_2023 Providing and fixing 50*6 mm G.I. strip on surface or in recess for connections etc. as required.
265ELECTRICAL WORKS od380303/2022_2023 Providing and fixing 50*10 mm G.I. strip on surface or in recess for connections etc. as required.
266ELECTRICAL WORKS od382407/2022_2023 Supplying and laying 8 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including connection/ termination with GI thimble etc. as required.
267ELECTRICAL WORKS od385500/2022_2023 Providing and fixing 8 SWG dia G.I. wire on surface or in recess for loop earthing asrequired.
268ELECTRICAL WORKS 5.17 Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
269ELECTRICAL WORKS od380328/2022_2023 Providing maintenance free Earthing system as per IS 2309 ,IEC 62305 part3 standards. Providing maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of 3m length having a diameter of 20 mm with copper coating thickness of 250 microns with self-coupling peg & bore arrangement . Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The mineral compound is required to have minimum 25Kg of the total composite. Earth electrode inspection chamber with heavy duty cover should be used to cover the Earth Rod. The dimension shall be 300 mmx 300 mmx 200 mm with a weight bearing capacity of 50KN.
270ELECTRICAL WORKS 1.10.3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. Group C
271ELECTRICAL WORKS 1.11 Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
272ELECTRICAL WORKS   1.14.1 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2x1.5 sq.mm + 1x1.5 sq.mm earth wire
273ELECTRICAL WORKS 1.14.2 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
274ELECTRICAL WORKS 1.14.3 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
275ELECTRICAL WORKS 1.14.4 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
276ELECTRICAL WORKS  1.21.1 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
277ELECTRICAL WORKS  1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
278ELECTRICAL WORKS 1.21.3 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
279ELECTRICAL WORKS  1.24.1 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 5/6 amps switch
280ELECTRICAL WORKS  1.24.3 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 15/16 amp switch
281ELECTRICAL WORKS  1.24.4 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 3 pin 5/6 amp socket outlet
282ELECTRICAL WORKS  1.24.5 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 amp socket outlet
283ELECTRICAL WORKS  1.24.6 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Telephone socket outlet
284ELECTRICAL WORKS  1.24.7 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. TV antenna socket outlet
285ELECTRICAL WORKS  1.24.8 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. Bell push
286ELECTRICAL WORKS  1.25 Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
287ELECTRICAL WORKS  1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
288ELECTRICAL WORKS 1.27.1 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mmX75mm)
289ELECTRICAL WORKS  1.27.2 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 3 Module (100mmX75mm)
290ELECTRICAL WORKS  1.27.3 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 4 Module (125mmX75mm)
291ELECTRICAL WORKS 1.27.4 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 6 Module (200mmX75mm)
292ELECTRICAL WORKS  1.27.5 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 8 Module (125mmX125mm)
293ELECTRICAL WORKS   1.28.1 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 1 or 2 Module
294ELECTRICAL WORKS  1.28.2 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 3 Module
295ELECTRICAL WORKS  1.28.3 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 4 Module
296ELECTRICAL WORKS 1.28.4 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 6 Module
297ELECTRICAL WORKS  1.28.5 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 8 Module
298ELECTRICAL WORKS 1.53.1 Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required 1 run of Cable
299ELECTRICAL WORKS  1.53.2 Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required 2 run of Cable
300ELECTRICAL WORKS  1.53.3 Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required 3 run of Cable
301ELECTRICAL WORKS  1.55.3 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
302ELECTRICAL WORKS  2.3.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator 12 way, Double door
303ELECTRICAL WORKS  2.4.1 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But withoutMCB/RCCB/Isolator) 4 way (4 + 12), Double door
304ELECTRICAL WORKS  2.5.1 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB"s (but without MCB"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door
305ELECTRICAL WORKS  2.10.1 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
306ELECTRICAL WORKS  2.10.3 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole
307ELECTRICAL WORKS 2.10.4 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
308ELECTRICAL WORKS  2.13.1 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
309ELECTRICAL WORKS  2.13.2 Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
310ELECTRICAL WORKS  2.5.2 Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB"s (but without MCB"s and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (4 + 24), Double door
311ELECTRICAL WORKS 2.15.1 Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
312ELECTRICAL WORKS   2.15.2 Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
313ELECTRICAL WORKS  2.15.3 Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
314ELECTRICAL WORKS   2.22 Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
315ELECTRICAL WORKS od380304/2022_2023 Supply of 20W 4 feet industrial type indoor surface mounted LED Batten with minimum 2000 lumens light output in 5700K CCT, greater than 100 lumens per watt system efficacy, with High Efficiency Extruded aluminium housing and polycarbonate Diffuser with provision of end-to-end connection, along with high power LED having minimum 50,000 burning hours as per L70. The driver shall, power factor > 0.9, Ripple less than 5%, 4kV surge protection and including all the necessary accessories as required complete. The luminaire and Driver shall be separately BIS Approved.
316ELECTRICAL WORKS  od380325/2022_2023 Supply of 9 W, outdoor Bulkhead surface mounted round with 700 lumens light output, >110 Lumens per watt system efficiency IP66 with IK10 Protection, 50,000 burning hours as per L70, CRI>80. The housing is of single piece pressure die-cast aluminium housing & cover retaining frame and corrosion resistance with Heat resistant toughened frosted glass cover glare free light distribution. The luminaire and the driver shall be separately BIS approved.
317ELECTRICAL WORKS  od380314/2022_2023 Supply of 10W indoor surface mounted LED Batten with minimum 900 lumens light output in 5700K CCT, greater than 100 lumens per watt system efficacy, with high-efficiency Extruded aluminium housing and Polycarbonate Diffuser with the provision of End to End connection, along with high power LED having minimum 50,000 burning hours as per L70. The driver shall have, a power factor > 0.9, and include all the necessary accessories as required complete. The luminaire and Driver shall be separately BIS Approved.
318ELECTRICAL WORKS od380316/2022_2023 Supply of 40W (2x20) W 4 feet industrial type indoor surface mounted LED Batten with minimum 4000 lumens light output in 5700K CCT, greater than 100 lumens per watt system efficacy, with High Efficiency Extruded aluminium housing and polycarbonate Diffuser with provision of end-to-end connection, along with high power LED having minimum 50,000 burning hours as per L70. The driver shall have a power factor > 0.9, Ripple less than 5%, 4kV surge protection and including all the necessary accessories as required complete. The luminaire and Driver shall be separately BIS Approved.
319ELECTRICAL WORKS  od380332/2022_2023 Supply of the following sizes of 1200 mm sweep, 5-star rated BLDC ceiling fan, including regulator/remote with double ball bearing, Aluminium pressure die cast body with Aluminium blades, canopies, hanging shackle, 30 cm down rod and without speed regulator suitable for 240V 50 HZ AC supply
320ELECTRICAL WORKS od380333/2022_2023 Supply of 250 mm sweep,900 rpm light duty exhaust fan in plastic body with self-opening louvers working on 230 V AC supply complete with all accessories as required.
321ELECTRICAL WORKS  od382343/2022_2023 Supply of 450 mm sweep,1400 rpm heavy duty exhaust fanworking on 230 V AC supply complete with all accessories as required.
322ELECTRICAL WORKS  1.41 Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
323ELECTRICAL WORKS 1.44 Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
324ELECTRICAL WORKS 1.47 Supplying and fixing extra down rod of 10 cm length G.I. pipe, 15 mm dia, heavy gauge including painting etc. as required. (Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
325ELECTRICAL WORKS  1.50.1 Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required. Upto 450 mm sweep
326ELECTRICAL WORKS od381527/2022_2023 Supply of 200 W +/-10% LED Floodlight with 24000 Lumens light output in 5700K CCT Greater than 120 lumens per Watt system efficacy, IP66 with IK08 Protection, 50,000 burning hours as per L70.THD,<10%and Power factor 0.95 the driver shall have 150-240 operating voltage ranges with Pressure diecast aluminium housing and toughened glass of seperately BIS approved.
327ELECTRICAL WORKS  od381528/2022_2023 Supply of 25W +/-10% LED street light with 2750 Lumens light output in 5700K CCT Greater than 150 lumens per Watt system efficacy, IP66 with IK08 Protection, 50,000 burning hours as per L70.THD,<10%and Power factor 0.95 the driver shall have 150-240 operating voltage ranges with Pressure diecast aluminium housing and a toughened glass of separately BIS approved.
328ELECTRICAL WORKS od382710/2022_2023 Supply Installation, Testing and Commissioning of 5M Octagonal Pole RROP 0501 having top dia of 70mm bottom dia of 130mm, sheet thickness of 3mm with base plate dimensions as 200x200x12mm along with OEM supplied foundation bolts and OEM supplied standard 1M Single Arm bracket with pipe dia of 48mm OD and cap length of minimum 225mm.
329ELECTRICAL WORKS  od381529/2022_2023 Supply, Installation, Testing and Commissioning of 20W +/-10% LED post top with 1900 Lumens light output in 5700K CCT Greater than 150 lumens per Watt system efficacy, IP65 with IK05 Protection, 50,000 burning hours as per L70.THD,<10%and Power factor 0.95 the driver shall have 150-240 operating voltage ranges with Pressure diecast aluminium housing and a toughened glass of separately BIS approved.
330ELECTRICAL WORKS  od379932/2022_2023 LED Streetlight Supply, Installation, Testing and Commissioning of 90W (+/-10%) LED Streetlight with minimum 10800 Lumens light output in 5700K CCT, Greater than 120 Lumens per watt system efficacy and high-power LED having minimum 50,000 burning hours as per L70. The driver shall have 140-270 Operating voltage range and 440V withstand capacity for min 8 hours. THD <10% and Power factor 0.95. The housing shall be made of LM6 grade pressure diecast Aluminium housing having 500hours NSS salt spray tested finish and Toughened Glass to achieve IP66 Protection. The luminaire and Driver shall be separately BIS Approved, equivalent of Philips BRP333 LED110 CW FG PSU S1 or equivalent approved make.
331ELECTRICAL WORKS  od380335/2022_2023 9m Pole for Streetlight Supply Installation, Testing and Commissioning of 9 Metres octagonal pole made of Steel plate Hot dip Galvanised of min 70 microns thickness, Top 70mm and bottom 155mm, BasePlate minimum 250x250x16mm, 3mm sheet thickness in single sections, 4nos foundation bolts of 750mm length and M24 Dia. The Pole shall be supplied along with a 1.5mtr length single arm bracket having 5 to 10 degree tilt and provision for mounting 90W streetlight.
332ELECTRICAL WORKS  od380017/2022_2023 Main Streetlight Panel Supply, Installation, Testing & Commissioning of LT Switch Board, cubicle type, made out of 2mm thick CRCA sheet, totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalized, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc. The panel shall be fabricated from a firm having IEC 61439 certification and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification. Incomer-1 125A, FP, MCCB Isolator-1 No. Busbar 125A TPN busbar chamber with Aluminium busbar 4A, C curve SP MCB-3nos, RYB Indicating lamps LED type - 3 Nos.120/5 A 15 VA Class 1 CTs -3 NosDigital multifunction meter (V, A, F,pf,kW,kWh) - 1No. Outgoings 40A, TP+NL 25kA MCCB with thermal release having adjustable overload 0.8 In to 1 In, adjustable short circuit 6 to 10 In -7 Nos.
333ELECTRICAL WORKS od380064/2022_2023 CCMS Panel/FEEDER PILLAR CUM 3phase CCMS PANEL (including suitable founadtion ) FOR GROUP CONTROL Supplying, unloading at site, shifting to site, assembling, levelling, grouting, erecting, earthing Testing, & Commissioning of Street light Feeder Pillar boxes as per tender specification. The feeder pillar shall be for group control of LED with all hard wares for power, control and communication devices and required software. It shall be a GPRS/GSM/ RF based remote street light monitoring system with capacity for self - protection from short circuit, over voltage and anti-theft alert, Latch relay is to be provided for switching operations. Auto MCB trip rectification should be there. Device capability for scheduling the on/off timings of lighting control switchgears based on the available sun-rise and sunset. Special emergency on/off facility with wireless control. System capability to capture and provide all electrical parameters at variable time intervals and live data collection timings. Enclosure should be mounted on pedestial stand and also Panel should have a water canopy and it should be IP 54 certified from NABL accrediated laboratory. smart energy meter for billing purpose) of ISI marking with 13779 standrads and accuracy class 1.0 with required CT’s For the smart energy meter, HES shall be provided by the bidder and to be integrated with MDM system. The bidder shall also include software chargers in the rate. Panel should have the following minimum number of incoming and outgoing feeders Incoming 40A TP+NL MCB -01 no, 3 nos of RYB indication lamp Outgoings 16A SP MCB – 18 nos Separate neutral link shall be provided.
334ELECTRICAL WORKS od380336/2022_2023 Ring Main Unit Supply, erection, testing and commissioning of 12kV, 630A,21kA/3sec, 3 Way, Data Acquisition compatible extensible out door Type IP54 SF6 Gas Insulated Ring Main Unit with Two (2) Motorized Load Break Switch (LBS) and One (1) Motorized Vacuum Circuit Breakers (VCB) with FRTU & Metering panel, and installation of same on including civil foundations using foundation bolts and including cost of terminations etc. complete including cost of all materials and labour as per standards and as per the directions of engineer in charge. The FRTU shall be built in with RMU compartment and compatible with integration of SCADA system. FRTU complete with DI, DO, AI and Modbus communication ports and power supply (24 V, DC) The number of DIs and DOs in FRTU shall be suitable for communication with each limb of RMUs with SCADA system.
335ELECTRICAL WORKS  od391634/2022_2023 Supply of 11kV gloves
336ELECTRICAL WORKS  od391501/2022_2023 Supply of electrical grade 11kV synthetic rubber mat.
337ELECTRICAL WORKS  od391501/2022_2023 Supply of electrical grade 11kV synthetic rubber mat.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail