Tender For Sub Station Work At Medical College, Jhunjhunu, jhunjhunu-Rajasthan

Rajasthan State Road Development And Construction Corporation Limited has published Tender For Sub Station Work At Medical College, Jhunjhunu. Submission Date for this Tender is 07-06-2023. Substation Tenders in jhunjhunu Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

37658464
Corrigendum : Tender For Sub Station Work At Medical College, Jhunjhunu
Open Tender
Indian
Rajasthan
jhunjhunu
07-06-2023

Tender Details

Tender For Sub Station Work At Medical College, Jhunjhunu

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 29-May-2023 Corrigendum to Nomenclature 29.05.2023 Other 07-06-2023
2 29-May-2023 corrigendum to modified dt. and nomenclature 29.05.2023 Date 07-06-2023

Key Value

Document Fees
INR 5900 /-
EMD
INR 1644000.0 /-
Tender Value
INR 8.22 Crore /-

BOQ Items

Name of Work : -Sub station work at Medical College, Jhunjhunu
Sl. No. Item Description
1SITC of 11 KV, 400/630 A, 20kA / 3 sec, Out door,Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, earthing switch, mechanical ON / OFF /Earth indication, Voltage presence indicator, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, Shunt trip coil, Anti reflex operating handle, right angle boots etc. as required.
2SITC of Silent DG Set (As per latest CPCB emissionnorms) complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled. Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown). Engine shall have residential silencer (isolated from main DG chamber), up to 3 M exhaust piping (with insulation & cladding), electronic / Mechanical governor, Manual & electric Start ,Batteries,Engine instruments panel, AVM and with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mmCRCA sheet steel (structure) with side wall fabricated from 1.6 mm CRCA sheet & filled with 100mm thick glass wool (96Kg/m3)/Foam. as per IS 8183 the doors of 100 mm thick and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/ opening are sealed with neoprene/EPDN gaskets.
3The enclosure has built in fuel tank, with protection and tripping of DG set against temperature of more than 50 degree centigrade. All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring & control system, MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dBA at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :GRP-1
4Radiator Cooled & Turbo Charged /AC
5380 KVA at 0.8 pf 415V 50Hz 3-?
6160 KVA at 0.8 pf 415V 50Hz 3-?
7Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applicationsincludingcutting,welding etc & fittings like elbows,flanges, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts . including the cost of thermal insulation with 50 mm thick layers of LRB rock wool (64 kg/m3 density) & 24 SWG aluminium sheet claddings etc complete as required.
8200 mm dia
9SITC of Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stopcommands, control Relays , selector switches for Ammeter & Voltmeter, Ammeter & Voltmeter , Control & Power Contactors, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets:
10PLC Based:
11320 to 500 KVA
1280 to 160 KVA
13SITC of ceiling suspended / wall mounted Factory fabricated & site assembled sandwich type TPNAluminium bus trunking including the cost of Enclosure ( 1.5 mm thick) , run components, expansion joints, provision for end feed units, tap off box , connection components , end covers , fixing bracket & accessories as required of following rating & specifications: Rated Insulation Voltage: 660V, Rated Frequency:50Hz, Rated Operating Voltage:415 / 440V, Short Time Ratingt: 35 KA for 1 sec, IP classification:IP 54 / 55, two no. GI earthing strip of 50 %ofPhase conductor
14100 Amp. to 400 Amp.
15500 Amp. to 630 Amp.
16Supply & Installation of TAP Off unit enclosure (w/o MCCB / ACB ) of following capacityMCCB / ACB & suitable forsandwich typeAluminiumbus trunkingas required.
17Up to 125 Amp. MCCB
18160 Amp.to 250 Amp. MCCB
19Supply & Installation of End Feed unit enclosure (w/o MCCB / ACB ) of following capacityMCCB / ACB & suitable forsandwich typeAluminiumbus trunkingas required.
20300 Amp.to 400 Amp. MCCB
21500 Amp.to630 Amp. MCCB
22P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with Copper conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. Group -1 Makes : Havell"s / Polycab / KEI / RR Kabel / Gemscab ( Cable to be laid in Existing Pipe/ Masonary Duct / Cable Tray ). Unarmoured
2335.0 Sq.mm x 4 core
24Supplying and making one end termination with heavy duty single compression brass gland SIBG type, heavy duty Copper lugs duly crimped with crimping tool, PVC tape etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required of size.
254 x 35.0 sq.mm
26P & Laying XLPE insulated IS:7098/II/85 of Group1 and approved make H.T.cable for working voltage 11 K.V.Earthed direct in ground including excavation of 30cmx100cm size trench, 25cmlayer of river sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection testing etc.as required of size.
273 core 300.0 Sq.mm
28Providing & making heat shrinkable type indoor/outdoor/straight through terminations/joint kit of Group1 and approved make suitable for XLPE insulated 11 KV / 33 KV cable, with required components, prepration of cable ends,testing etc. as required of following sizes .
2911 KV End Termination Kit Indoor type
303 core 240/300 Sq.mm
3111 KV End Termination Kit Outdoor type
323 core 240/300 Sq.mm
3311 KV Straight Through JointKit
343 core 240/300 Sq.mm
35Supplying and fixing of Aluminium / Copper bus barby means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves.
36Electrolytic grade Aluminium bus bar
37SF ofCurrent Transformer, with all necessary support in existing panel including connection etc. as required .
38from 200 / 5 to 400/5Ratio , 10 VA , class 1 accuracy
39from 500 / 5 to 1600/5 Ratio , 15 VA ,class 1 accuracy
40SF of110/220 V, LED (22.5 mm dia ) Indicatinglamp with integral circuit, terminal block, including connection etc. as required.
41Red/yellow/Green colour
42Blue colour
43SITC of Fixed /Draw out type 4 pole Air Circuit Breaker conforming to IS 60947 P - 2 in existingLT panel suitable for LT installation 440 V, 50 Hz and havingadjustable over load short-circuit, earth fault andmicroprocessor based release withseparate LED indication for each type of fault ,LCDdisplay , Thermal memoryat least 4NO & 4NC auxiliary contacts safety shutter and fault position acknowledgement mechanism . type ACB shall have separate indication for service, test, isolation, maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ), Uimp - 12 KV, including making connectionsetc. as required.Make:- ABB/ Legrand /L&T /Schinder
44Draw out type ( Motorised charging type )
451600 A Rating ,50 / 65kA
461250 A Rating ,50kA
47800 A Rating, 50kA
48Draw out type (Manual spring charged)
491250 A Rating ,50kA
50800 A Rating, 50kA
511000 A Rating , 50kA
52SITC of Fixed /Draw out type 3 pole Air Circuit Breaker conforming to IS 60947 P - 2 in existingLT panel suitable for LT installation 440 V, 50 Hz and havingadjustable over load short-circuit, earth fault andmicroprocessor based release withseparate LED indication for each type of fault ,LCDdisplay , Thermal memoryat least 4NO & 4NC auxiliary contacts safety shutter and fault position acknowledgement mechanism . type ACB shall have separate indication for service, test, isolation, maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , Uimp - 12 KV, including making connectionsetc. as required.
53Draw out type (Manual spring charged)
54800 A Rating, 50kA
55SITC of quick make and quick break3 pole current limiting MCCB having following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with frontface and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip , earth fault trip, push( test) to trip, including making connections with lugs & spreaders,etc. as required.
56With Thermal Magnetic release
57630 Amp , 35/50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu
58up to 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
59250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
60SITC of self healing MPP/MP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz and total wattage loss less than 0.5 Watt per KVAR . including making connections with suitable capacity conductors/cables testing etc. as required.
61Heavy duty Three phase 440 V , 50 Hz capacitor (Bank)
62SITC of microprocessor based three phase sensingpower factor correction relay having following sensing capacitysecondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall havedigit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR,metering facility as required.
6312 to 14 stage
64sensitivity up to 50 milli Amp
65P & F of440 Volt 3 pole capacitor(AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current, conforming to IS:13947-4-1/IEC:947-4-1, Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank.
66up to 6 KVAR
677 to 10 KVAR
6811 to 20 KVAR
6950 KVAR
70P & F of Multy functionmeter with LCD/ LED display capable of measuringelectrical parameters like V, I, F, PF, KW, Kva, Kvar, Kwh, Kvah, Kvarh display with 1A/5A CT input for LV/ HV network, RS 485 communication port etc. complete in all respect.
71S & F of Electricalinsulating rubber mattsconfirming to IS: 15652 /2006with one sideanti skid abberation marks and pasting the mat with synthetic rubber adhesive as required.
7211 KV,2.5 mm thick with proof voltage 22 KV / 3 min. and Break Down Voltage45 KV
73P & F paper phenolic resin bondedlaminates confirming to IS : 2036 -1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc platednut and bolts as required. Group-1.
746.4 mm thick
75P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required.Gp-AI
76Single pole MCB
776 A to 32 A rating
78Triple pole MCB
796 A to 32 A rating
8040 A 63 A rating
81Four pole MCB
826 A to 32 A rating
8340 A 63 A rating
84P&F of removable Voltage surge protection device (surge arrester) for protection against transient over voltage (8/20 micro -seconds) and to run current waves to ground, making connection, testing etc. as required. ( Imax=40 kA, Up= 1.2kV, Uc=275 volts )
85Triple pole & neutral
86P & F Cam operated rotary switches on existing panel with 2 way and off position
87Two pole
8816 A
89SITC of quick make and quick break4 POLEcurrent limiting MCCB having following current rating, short circuitbreaking capacityat 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with front face and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip ,earth fault trip, push( test) to trip , including making connections with lugs & spreaders,etc. as required of group 01.
90With Thermal Magnetic release
91up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
92up to 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
93160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
94200 Amp ,25/35kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
95250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu
96With Microprocessor based release
97400 Amp ,35 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu
98630 Amp , 35/50 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu
99P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required. Group-1 of size. (Only laying Charge)
1006.0 Sq.mm
1014 core
10216.0 Sq.mm
1034 core
10435.0 Sq.mm
1053.5 core
10670.0 Sq,mm
1073.5 core
108120.0 Sq,mm
1093.5 core
110185.0 Sq,mm
1113.5 core
112240.0 Sq.mm
1133.5 core
114300.0 Sq,mm
1153.5 core
116Supplying and making one end termination with heavy duty single compression brass gland SIBG type, heavy duty aluminium lugs duly crimped with crimping tool, PVC tape etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required. Group-1 of size.
1174 x 6.0 sq.mm
1184 x 10.0 sq.mm
1193.5 x 35.0 sq.mm
1203.5 x 70.0 sq.mm
1213.5 x 120.0 sq.mm
1223.5 x 185.0 sq.mm
1233.5 x 240.0 sq.mm
1243.5 x 300.0 sq.mm
125Supply and fixing of following accessories for Air circuit breakers. Group 1
126Shunt Trip Release
127Under Voltage Release
128Maintenance free Gel EarthingwithPipe in pipe / Pipein striptechnologyfilled with anti corrosive conductive compound ( CPRI Tested )below the ground in 150 - 200 mm dia. earth pit & surrounding filled with required mineralfillingcompound ( MFC should have hygroscopic property to retain the moisture for long time to create low resistance zone) and C.C.finished chamber covered with hinged type with locking arrangement C.I. Cover,C.I. Frame of size 300mm x 300mm complete testing of earth resistance as required. of following sizes.
129With Pipe in Pipe Technology (Inner pipe dia. / Outer pipe dia. ) 80 - 100 micron GI Coating
130GI pipe 2000 mm long, 50 / 25mm, Terminal 12 mm GI Strip
131GI pipe 3000 mm long, 80 / 40 mm, Terminal 14 mm GI Strip
132S & Laying following size earth wire / stripin horizontal or vertical run in ground / surface / recess including riveting, soldering, saddles, making connection etc. as required. Group-1.
13332mm x6mm G.I. ( Hot Dipped) Strip
13450mm x 6mm G.I. ( Hot Dipped) Strip
13550mm x 6mm copper strip
1368 SWG G.I. ( Hot Dipped) Wire
137Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , Painting etc. as required.
138Making hole in stone masonary/ RCC with core cutter for accomodating cables/earthing strip and making same with cement plasterincludingusing solvent to make water proof
13950mm to 150mm
140Supply and fixing of following accessories for MCCB
141Extended Rotary Handle
142P/Laying P.V.C./ XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with Copper conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved makein ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick underlayer ofsand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size.
1432.5 Sq.mm
14410 core
145Supplying and fixing of chain link fencing with angle iron posts 50x50x6mm placed at every 3 Mtr. apart 30cm in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner and every tenth post to be strutted with (50 x 50 x 6cm) angle iron provided and fixed and fitted with posts including earth work in excavation etc. complete with chain link size.
14650mm x 50mm x 3.15mm
147P & F of 4 star ratedvertical storage water heater with outer casing made of M.S.sheet finished with anti-corrosive powder coating,inner tank made of pure electrolytic copper/stainless steel / SPHP, Tubular copper sheathed and Nickel plated heating element/ twin ceremic cartridge heating element, stem type thermostat and thermal cut out,Dual indicating lamps for power supply and thermostat,PUF insulation, Pressure relase valve,fusible plug etc. as required held in position with 4 no. rack bolts,duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top,including making inlet,outlet heavy gauge C.P./ Flexible alloyconnection,testing etc. as required.
14815 Ltr.
14925 Ltr.
15035 Ltr.
151SITC of self contained drinking water cooler with energy efficient hermetic sealed type compressor,non CFC refrigerent suitable for operation on 230V/1pH/50Hz ac supply,Full stainless steel (S304)body and tank, stainless steel water tray,minimum two nos faucets and suitable drainage system complete in all respect with 300mm height MS fabricated and painted platform. Complete in all respect of the following capacity
152Cooling capacity 150 Ltr./Hr. and storage capacity 150 Ltrs
153SITC ofRO water system with Filtration stage = Particulate filter-Membrane life enhancer filter - sediment filter - Pre carbon filter -RO Membrane filter - Post carbon filter,Input power Rating - 230 V AC , 50 HZ, Percentage of Rejection TDS - 90% or better having following Features (a) Double purification by RO with ESS or latest technology with TDS indicator (b).Spin welded RO Membrane Housing to prevent tempering (c). Push fit components for leak proof performance (d). Fully automatic operation with auto start and auto off (e). SS construction for corrosion free lifespan (f). Equally suitable for water from all bore wells,,overhead storage tanks,water tankers and even municipal taps (g) RO Membrane Flushing - Auto Flush @ Every Start , Every Stop and every One Hourof working for one minute. complete in all respect with following capacity. Approved Make:Eureka forbes, Kent, AU Smith, Ion Exchange, pentair.
154Purification capacity- 50 LPH,Duty Cycle 270-500 liters/day,
155P & F of 36Watt IP20 LED 2"X2" fixture, Recessed/Surface type,having efficacy of not lessthan 100 Lumen/watt, made out from CRCA housing and with high purity/transmisvity duffuser for uniform light distribution high efficiency driver electronics and in compliance to IEC standard (integral with light fixtures) life time of more than 50000 burning hours, CCT 6000 K (minimum), CRI> 80, driver maintaining PF >0.90
156P & Fof IP20 LED Recessed / Surface Mounted, Round / Sqaure Non-Dimmable Downlight with die-cast aluminum housing & Heat Sink for heat dissipation, high purity reflector with external BIS certified 2.5 KV surge protected driver having efficiency > 85% and in compliance to IEC standards. System Lumen efficacy of = 100 lm / watt andlife time of minimum35000 Burning Hours with 70% of intial Lumen maintaned, CCT 3000°K / 4000°K/ 6000°K , maximum power consumption should not more than the specified rating and Fixture shall be of CE complianed.
157Surface Mounting
158LED Downlight 12 W
159LED Downlight 18/20W
160P&F on load change over switch, front handle operated, four pole 415 V conforming to IS:13947 P-III including connections , testing etc. as required in the following rating:
161Open execution type
162125 A
163200 A
164Supply, Fabricating & installing following sizes of powder coatedperforated M.S. cable trays including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders, fastners, supports etc. as required.
165300mm x 50mm x 1.6mm
166450mm x 50mm x 2.0mm
167Add extra @15% if GI Cable tray used in place of MS Cable tray
168SITC of high mast lighting system (as per CP3-TR7/1996 of ILE, UK) consisting of totally hot dip galvanised by single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm, mast head frame assembly with full cover, aviation obstructionlights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement ( winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, suitable ropes (AISI 316, 7 / 19 costruction ), EPR insulated PCP sheathed trailing cable, outdoor type control panel for auto on / off, reverse / forward motor operationand CC foundationof M - 25 grade complete as required. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised and certified by the manufacturers for satisfactory supply, erection, testing and commissioning of high mast. (See table E - 13 for specs.)
16920.0 Mtr Hm (in 2 section)
170P & F ofIP-65 protected high power LED flood light system with Pressure diecast aluminium housing , toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED fixturesupplied with pre wired cable of 1 mtr. Integrated driver shall be high efficiency having efficiency more than 85 % and in compliance to IEC standards/BIS certified. The System level Luminaire efficacy >=100with High Power LEDs of CREE/NICHIA/OSRAM/PHILIPS/SEOULmake is to be used . LED Driver Input Voltage AC 110 to 270 V AC with Auto resetting Safety Cut-off. Input Frequency 50Hz±3% Power Factor >0.95 Driver Efficiency >85% ,Control Gear Integral Design, THD(I) <10%,. Electrical Connector Must be provided Surge Protection Min >=5KV internal and 10KV external in 80W onwards,Humidity 10% to 90% RH Working Temp -20C to 50C . LED Luminaire Specifications: Life ExpectancyEqual or more than 50000 burning hrs with Minimum 70% lumen maintenance.Manufactures Word Mark/Name Engraved/Embossed on die cast housing to allow traceability/authenticity till life of fixture. Fixtures shall be CE complianced
171High Power LED Flood Light 150W
172Supply and erection of GI Octagonal / Conical pole of following length and dimension as per table E-10 with base plate on the cement concrete foundation of M-20 grade (1:1.5:3) with the help of anchor bolts of grade 6.8 (IS: 1367 P III ).The pole shall have a weatherproof flush door and locking arrangements. The complete work shall be supervised and certified by the manufacturers for satisfactory supply, erection, testing and commissioning.
173Octagonal MS Polesmade of S-355JO grade steel sheet , folded lengthwise to obtained Octagonal shape, having single longitudinal seam weld and hot dipped galvanised internally & externally in accordance with IS 2629. (See Table E - 10 for specs.)
1747 Mtr.
175Supply, Erection and Fixing of hot dipped galvanised Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles
176Single arm overhang
177P & F of IP 65 protected LED Street Light fixture 70-75 Watt with surge protection device 10KA) applicable for area lighting with extruded pressure diecast aluminium housing, system lumens efficacy of 100 lm/watt minimum, toughened glass with diffuser, suitable lenses on LED, 240V,50 Hz of High Power LED lamps supplied with pre-wired cable of 1 mtr. Integrated Driver shall be high efficiency having efficiency >85% and in compliance to IEC standards System life of 50,000 Burning Hours, CRI >80,PF>0.90 at full load, CCT 5700-6500 I( fas per direction of Engineer incharge]. Fixture shall be CE compliance
178S & F of Street light bracket made out from following size of " B "class GI pipe with heavy duty pole clamp, Saddles suitable fastners etc. as required.
17940 mm Dia.
180Providing and fixing of IP 65 protectd Polycarbonate / Polysterene fuse box moulded with inside knock outs of following size with hinged cover, transparent window,PU gasket, locking arrangement, duly holded with 2 nos. pole clamps of 20 mm x 3 mm flat with nut and bolts, complete with The box shall be provided with Din rail, 4 / 8 way 10.0 / 16.0sq.mm heavy duty connector, earth terminal,complete in all respect.
181125 mm X 200 mm X 122 mm
182P / L of Double wall corrugated HDPE pipe confirming to IS : 14930 P - 1 & 2with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required of Gemini or IS:14930 marked make.Outer Dia. / Inner dia.
18390 / 76 mm
184120 / 103 mm
185200 / 175 mm
186300 / 260 mm
187P/Laying ISI marked P.V.C. insulated submersible cable confirming to IS:694 with flexible copper conductor including making connection etc. as required.
1882.5 Sq.mm 3 core flat / Round (Gr - I)
189P & F ofac operated heavy duty 230 /440 Volt power contactor conforming to IS:13947-4-1/IEC:947-4-1 having provision of mechanical interlocking, auuxilary contacts, Din rail mounting type including making connections, testing etc. as required. Group-1.
1904 pole Power contactorswith following AC 1 Rating
19163 Amp
192600 Amp
193P&F of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming etc. as required. Group-1
194One day reserve (mechanical type )
195P & F paper phenolic resin bondedlaminates confirming to IS : 2036 -1995 for boxes/ frames including making holes for switches etc, with brass screws, washers/ zinc platednut and bolts as required. Group-1.
1966.4 mm thick
197P & F lightning conductor finial made out of 25 mm dia.,300 mm long G.I. tube having single prong at top with 85 mm dia., 3 m thick G.I. base plate including holes etc. complete as required.
198P & F of Early streamer Emission type lightning arrester on GI mast with air terminal configured as spheroid which is comprised ofseparate electrically isolated 4 panels surrounding an earthed central finial, the terminal shall be tested by CPRI for impulse current of 45 kA ( 8 / 20 Sec ) with 5 positive & 5 negative impulse, the arrester having following protection radius at level 1
19960 - 79 Mtr.
20030 - 48 Mtr.
201S & Laying of down conductor of 70 Sq.mm single core insulated flexible copper cable with accessories as required.
202NON BSR
203Supply installation testing & Commissioning of Copper wound distribution Transformerof following ratingand % Impedance, 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, ONAN Cooledlosses as per IS 1180 part I 2014 (Fourth Revision) Level-1, with boltless core designincluding standardaccessories like conservator with prismaticoillevelgauge , silica gel breather,Bucholz relay,pressed steel radiator fins, Radiator Valve(above 800 Kva) Suitable size HT cable box,LT cable box with Busbar connection for outgoing cables, Off -LTC (+/- 2.5%, +/- 5% to - 7.5% ),temperature rise of 40 degree C in oil / 45 degree C in winding , drain valve, Air release device,Dial type Oil & Winding Temperature gauge with alarm & trip contacts, first filling of transformer oil as per IS :335-1953 , Epoxy primer and PU based paint as Top coat, Unidirectional rollers for rating upto 800 kva & bi- directionalabove 800 Kva rollers with locking arrangement etc. as required. The Transformer shall be subjected to routine factory tests (as per IS:2026 and IS:1180) including Temperature rise test inOEM"s own lab shall be witnessed by Department engineer Physically.
204Transformer shall be tested from CTLof discombefore charging of transformer & complete installaion must be certified from Electrical Inspectorate office as per Indian Electricity rule, (CTL testing charges and Electrical Inspection charges shall be reimbursed by the department to the contractor)Following tests shall be carried out on each transformer at site by OEM enginer in presence of department authorised representative:- a) Ratio test on each tapping.b) Resistance of windings at principal and all tapings.c) Insulation resistance of the winding between HV to earth / HV to LV / LV to earth.d) Vector group test.e) Magnetic Balance test. All as per pre approved by Engineer in charge. MAKE:- Uttam Bharat / Danish /Verdhman / United / Voltamp.
205630 KVA with % Impedance 4.5
2061000 KVA with % Impedance 5.0
207Supply, installation, testing and commissioning of INDOOR type, 11 KV switch panel board fabricated out of minimum 2 mm thick sheet steelas per specifications. The panel shall be complete with cable termination arrangementfor incoming and outgoing with 1x 3C x 300 Sqmm XLPE 11 KV cable and required rating copper bus bar arrangement .The panel shall comprise of the following:
2084 Nos 11 KV, 25 kA for 3 sec (1 I/C and 3 O/C)630 A, horizontal drawout type VCB/SF6 breaker with motorised spring charge closing mechanism with antipumpingprotection and trip free features , motor voltage 240V AC and tripping / closing coil voltage , 24V DC and VCB /SF6 breaker complete with 3 NO + 3 NC auxillarycontact as sparecomplete with following of ( Make: ABB/ Schneider/ Siemens/L&T).
2091NOS. INCOMING , 3 Nos. 11 KV, 25 kA for 3 sec, 630 A, horizontal drawout type VCB/SF6 breaker with motorised spring charge closing mechanism with antipumpingprotection and trip free features ,motor voltage 230V AC and tripping / closing coil voltage , 24V DC and VCB /SF6 breaker complete with 3 NO + 3 NC auxillarycontact as sparecomplete with following:
2101 no. 240V AC spring charge motor.
2111 no. 24V DC shunt trip coil.
2123 set of 400-150/5-5A, core 1, class 0.5 accuracy, 5VA current transformer (cast resin) for metering, core 2 class 5P10, 5VA accuracy current transformer (cast resin) for protection.
2131 no Numerical non directional IDMT 3 O/C + 1 E/F protection relay for each breaker,1 no. master trip relay for each breaker,1 no. Trip circuit supervision relay for each breaker,1 no. Antipumping relay for each breaker.
2141 no. breaker control switch : (TNC) for each breaker,1 set of phase indication lamp (LED type) for each breaker,1 no. threepin socket + switch (240 V) for each breaker.
2151 set of circuit breaker ON/OFF/Auto trip / Spring charged/Trip circuit healthy indicating/ SF6 gas pressure indication lamp (LED type) for each breaker.
2161 no. 60W 230 V anti condensation space heater with thermostat with heater ON/Off switch for each breaker in breaker comprment & cable compartment.
2171 set of 800A 11kV rectangular electrolytic grade colour coded and sleeved copper busbars for each breaker.
218Motor On / Off togle switch for each breaker,Yellow/white Puh Button for Alarm Accept/Reset for each breaker,Black Push Button for Trip Circuit Check for each breaker.
219Suitable rating MCB for AC / DC supply control for each breaker.
220Door Lamp with Switch for each breaker.
221Electrical & mechanical interlocking of 2 nos outgoing breaker to prevent the short circuit between both breaker for 2 sets of outgoing breaker.
222HT Panel described above & as per specification.
223Providing & Laying P.V.C. / XLPE insulated & P.V.C. sheathed ArrmouredAluminiumcable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV withH4- Grade electrolyticaluminium conductor confirming to IS 8130 of purity >99.6 %, round / flat strip armouring of cables, Inner / outer sheath confirming to IS:5831in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) includingtesting etc. as required of following size. OEM must have it"s own in house NABL accrediated Laboratory for testing procedure as per IS:10810. Make :Havell"s, KEI, Gems Cab, Ishwar Cab,Unistar,Polycab,RR Kable,Grandlay
224800.0 Sq. mm
2251 core
226Supplying and making one end termination with Nickel plated heavy duty brass single compression gland (as per IS 12943-1990)) SIBG type consisting of Check Nut, Gland Body, Metal Washer(3 Nos.), Outer Seal Rubber Ring,Compression Nut,heavy duty aluminium lugs (as per IS 8309 -1993) duly crimped with crimping tool, PVC tape as perIS 8337-1976offollowing size ofPVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required.All as per pre approved by Engineer in charge.
2271 x 800.0 sq.mm
228SITC of LED batten with reliable and robust CRCA housing structure, CRI>80, System Lumen Output of 4100 lm with a System Wattage of not more than 40 Watts and a system efficacy of 100 lm/Watts, Lifetime of 50,000 burning hours @L70, Wide Operating Voltage Range of 140V-270V, Color Temperature Options of 5700K -6500K, Power Factor = 0.95, THD<10% with Short Circuit and over voltage cut off etc as required.LM 79 and LM80 report has to be submitted for documentary verification of above Specifications. (Make:- Phillips,Crompton , Wipro, Trilux, Havells)
229Supplying, installation, testing & commissioning of 9-10 watt 3000K mirror light all accessories i/c connections with 3 x 1.5 sq.mm PVC insulated FR copper conductor cable etc. as reqd. (Make Phillips, Havells, Crompton , Wipro, Trilux)
230Providing & Fixing of IS: 13875 & IEC :61326 confirming LED Digital type(up to 500) V range Volt meter / Direct- Ammeter /CT oertated ammeter/ Frequency meter / KWH meter / Multi Function Meter / Power analyzer of class 1 accuracyas per IS : 1248 of size 96mm x 96 mm including making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.All as per pre approved by Engineer in charge. For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
231Threephase AMP+HZ+PF+KW+KVA+KVAR+T.ENERGY+THD-I, THD-V & RUN HRS
232Supply and erection ofGalvanized Iron pole with galvanizing done in single dipping (Average coating thickness Minimum 65 Microns) continuously tapered poles having Octagonal / Circular cross-sections designed to withstand the maximum wind speed as per IS 875, The pole shaft shall be made from sheet steel (HT Steel Conforming to grade S355JO) and confirming to BSEN 10025 and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding. The welding of pole shaft shall be done by Submerged Arc Welding (SAW) process. pole shafts shall be provided with the rigid flange plate of suitable thickness (Fe 410 conforming to IS 226 / IS 2062) with provision for fixing 4 no. foundation bolts, This base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal Poles shall have lockable door of approximate 500 mm length at the elevation of 500 mm from the Base plate with bakelite sheet having 6A SP MCB and 16 sqmm stud type connector ( 4 nos) inside the pole at door opening for cable connection of following length and dimension as per table P-01 with base plate and foundation bolt on the Existing cement concrete foundation.Make:Philips, BPP, Surya, Valmont, CG, Transrail, Utkarsh
233Poles with Octagonal Cross Section
2344 Mtr.
235Providing and Laying RCC Foundation for Octagonal/ Conical Street Light poles, High mast Poles as per Drawing attach at TableP-4with Following Procedure& All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure "A" attached with this BSR .
236A) Excavation of Pit for Foundation Size upto required depth from Ground level
237B) Dressing of Pit and Dry stone pitching 200 mm thick including supply of stones and preparing surface complete.
238C) Providing and laying in position cement concrete of M-10 grade of 75 mm thickness
239D) Reinforcement for R.C.C. work with TMT bars including straightening, cutting, bending, placing in position and binding all complete.
240E) Centring and shuttering including strutting , propping etc. and removal of form work for Footing and Pedestal
241F) Providing & Fixing of 2 no. Required SizePLB HDPE Pipe& Foundation Bolt with template as per OEM Recommendations.
242G) Providing and LayingReinforce cement Concrete of M-25 grade in Footing and Pedestal including Curing the foundation for 7 days.
243H) Providing and Fixing Nosing Angle 40 mm x 40 mm x 6mm with 2 no. 100 mm long, 10 mm dia. Lugs on each face.
244Pole Foundation for Octagonal pole from 3 Mtr. To 6 Mtr.
245Supply & installation of cable identification plates duly secured to cables for identification suitable for cable sizes taken in the BOQ.
246P & F of ventilating fans with thermostate and ON/OFF selector switch including making connection, testing etc. as required.
247100 mm sweep
248S & Laying following size earth wire/strip of 1.5 mtr length for connecting earth strip of DG netural terminal including riveting, soldering, saddles, making connection etc. as required.
24950mm x 6mm flexible copper strip
250SITC of wall/ free standing floor mounted dust and vermin proof compartmentalisedcubical panel made out of2 mm thick CRCA sheet , required hardware,duly powder painted in required shade after rinsing . The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel, door handle, hinged door with locking arrangement for equipment/switchgear . Side walls and cable alley compartments having bolted type doors with detachable extension type structure. (only outer area on all sides shall be measured ) Make : Engineers & Engineers /Milestone / Pricision system control/Tricolite /ZENEIA/ Adlec
251P & F of IP 65 protected LED Post-Top-Light system withDie casthousing(Bottom+Top), poycarbonate diffuser, Maximum 40 watt,Mininum Lumnes 3600 Watt 220-240V, 50Hz (integrated Driver), LED lamps supplied with pre-wired cable of 1 mtr. Driver shall be high efficiency having efficiency > 85% and in compliance to IEC standards (Integral with light fixture).system life of 50000 Burning Hours with 70% of initial Lumens maintained.Light output in Cool white or Warm White Colour as per engineers choice. Fixtures shall be CEcompliance.Make :- Philips/Wipro/Crompton/Havells
252Supply, Installation, Testing and balancing of powder coated /Anodised extruded aluminium construction inlet fixed single air louvers with bird screenfor Exhaust air of size upto 2.0 sqft area, Installation has been done on the Exhaust Fanof make Systemair / Ravistar / Trox/MetalJoint/Airflow.
253P & F of Surface mounting LED bulk head fitting, efficacy >=100 lumens /watt  total Lumen  output  not  less  than  1000,  CRI>80  and  CCT=4000/6500 K(as reqd.), with inbuilt LED Driver and IP-65 & IK08 and better rated with pressure die cast aluminum housing & diffused polycarbonate diffuser complete as required.Make PHILIPS, Havells, Crompton , Wipro)
254P & FDouble ball bearing and with sturdy mesh guard metal body ,3 numbers metal blales oscillating tye wall mounting Fan, including fixing with anchor bolts, adjustable upward and downward tilt mechanism, noise level should <=75 db, power consumption <=120 watts, motor protection through thermal overload protection device, 3 speed regulator making connection testing etc. as required. Make:- Havells,Wipro,Crompton,Orient
255450 mm sweep With three speed regulator
256Supply and laying in ISI marked RCC hume pipe NP 3 as per IS - 458-1988 with coller etc including excavation of trench of 1.2 mtr depth & refilling the same after covering the pipe with 300 cement concerete mixture of 50 mm below the pipe, 150 mm both side of pipe and 300 mm above the pipe complete in all respect as per specification. ( payment of CC mixture will be made in seperate CC item of the BOQ as per measurement)
257200 mm dia
258300 mm dia