| 1 | Taking out Non clog submersible sewage pumping set from sewage well appx 12 m depthfoundation (after and including dewatering of sewage well) of 60 HP capacityby lifting and dismantling the same for assessing and carrying out the repair/servicing and replacement of unserviceable parts with new parts as listed in subsequent items and making good in running condition withtesting and balancing, reassembling and lowering the same in well & fixing on the foundation making connections and testing complete all as specified & directed by Engineer-in-Charge. |
| 2 | All as per Srl item No 1 here-in-before but of capacity 40 HP |
| 3 | All as per Srl item No 1 here-in-before but of capacity 30 HP |
| 4 | All as per Srl item No 1 here-in-before but of capacity 20 HP |
| 5 | All as per Srl item No 1 here-in-before but of capacity 7.5 HP to 10 HP |
| 6 | All as per Srl item No 1 here-in-before but of capacity 3 HP to 5 HP |
| 7 | Note for item No 1 to 6:- (a) The replaced parts of pump shall be measured & paid separately here-in-after as supply only as fixing is inclusive in the rate quoted for the item.(b) Dewatering of sewage well shall be included in the quoted rate of item.(c) Contractor have to arrange all safety equipments for works in sewage well at his own cost as directed by Engr-in-Charge.(d) Note: Serviceable sewage pump should be fittedwithin 12 Hrs otherwise a penalty ofRs 5000 per day will be imposed. |
| 8 | Taking out old unserviceable lubricating oil from the chamber, cleaning and refilling the fresh lubricating oil complete all as specifed & directed by Engineer-in-Charge. |
| 9 | Rewinding of motor 60HP non clogsubmersible sewage pumping setwith suitable size and proper guage of winding wire using best quality of insulation material provided with thermal switches for protection against excessive temp free and replacing O ring set full fastner set, Nitrile O ring and bearing, seals and varnish the motor using fine quality varnish complete all as specified & directed by Engineer -in- Charge. |
| 10 | All as per Srl item No 8 here-in-before but of pump motor 40 HP. |
| 11 | All as per Srl item No 8 here-in-before but of pump motor 30 HP. |
| 12 | All as per Srl item No 8 here-in-before but of pump motor 20 HP. |
| 13 | All as per Srl item No 8 here-in-before but of pump motor 7.5 to 10 HP |
| 14 | All as per Srl item No 8 here-in-before but of pump motor3 to 5 HP |
| 15 | Supply only CI impeller with guide bush suitable for 60HP Non clog submersible sewage pumping set complete all as specified & directed by Engineer-in-Charge. |
| 16 | All as per Srl item No 14 here-in-before but cap of pump 40 HP. |
| 17 | All as per Srl item No 14 here-in-before but cap of pump 30 HP. |
| 18 | All as per Srl item No 14 here-in-before but cap of pump 20 HP. |
| 19 | All as per Srl item No 14 here-in-before but cap of pump7.5 to 10 HP. |
| 20 | Supply only lubricated upper/lowerbearing for 60 Hp non clog submersible pump complete all as speicified & directed by Engineer-in-Charge. |
| 21 | All as per Srl item No 19 here-in-before but 40 HP |
| 22 | All as per Srl item No 19 here-in-before but30 HP. |
| 23 | All as per Srl item No 19 here-in-before but20 HP. |
| 24 | All as per Srl item No 19 here-in-before but7.5 HP to 10 HP. |
| 25 | All as per Srl item No 19 here-in-before but3 to 5 HP. |
| 26 | Supply only hard metal double upper and lower mechanical seal assesbly combination for non clog submersible pump, of capacitor 60 HP complete all as specified & directed by Engineer-in-Charge. |
| 27 | All as per Srl item No 25 here-in-before but cap of pump 40HP |
| 28 | All as per Srl item No 25 here-in-before but cap of pump 30HP |
| 29 | All as per Srl item No 25 here-in-before but cap of pump 20 HP |
| 30 | All as per Srl item No 25 here-in-before but cap of pump 7.5/10 HP |
| 31 | All as per Srl item No 25 here-in-before but cap of pump 3/5 HP |
| 32 | Supply and fixing in replacement CI auto coupling of size 100 mm dia from sewage well of size depth 10 Mtr and 9 Mtr dia. |
| 33 | Supply and fixing in replacement CI auto coupling of size 150 mm dia from sewage well of size depth 10 Mtr and 9 Mtr dia. |
| 34 | Supply and fixing in replacement CI auto coupling of size 250 mm dia from sewage well of size depth 10 Mtr and 9 Mtr dia. |
| 35 | Supply and fixing in replacement CIduck foot bend of size 100 mm dia from Sewage Well of size depth 10 Mtr and 9 mtr dia. |
| 36 | Supply and fixing in replacementCI duck foot bend of size 150 mm dia from Sewage Well of size depth 10 Mtr and 9 mtr dia. |
| 37 | Supply and fixing in replacementCI duck foot bend of size 250 mm dia from Sewage Well of size depth 10 Mtr and 9 mtr dia.Note for item No 31 to 36:- Dewatering of Sewage well is included in Quoted rate if required. |
| 38 | Supply and fix in replacement PVC insulated submersible copper cable flat/round of size 6 Sqmm 3 core complete all as specified & directed by Engineer-in-Charge |
| 39 | All as per Srl item No 37 here-in-before but 10 Sqmm 3 core. |
| 40 | All as per Srl item No 37 here-in-before but 16 Sqmm 3 core. |
| 41 | S&F in replacement CI column pipe both end flanged ISI marked of size 100mm dia including lowering down thecolumn pipe including dewatering of sewage well if required complete all as specified & directed by Engineer-in-charge. |
| 42 | All as per Srl item No 40 here-in-before but 150mm dia CI pipe. |
| 43 | All as per Srl item No 40 here-in-before but 250 mm dia CI pipe. |
| 44 | Supply and fix in replacement MS adjustable spiral bottom plate suitable for 40 to 60HP Motor complete all as specified & directed by Engineer-in-Charge. |
| 45 | All as per Srl item No 43 here-in-before but for size 20 to 30 HP motor. |
| 46 | All as per Srl item No 43 here-in-before but for 7.5 HP to 10 HP motor. |
| 47 | Supply and fix in replacement shaft AISI-410 suitable for 20 to 30 HP Motor. |
| 48 | All as per Srl item No 46 here-in-before but suitable for size 40 to 60 HP motor. |
| 49 | Supply and fix in replacement MS hexagonal nut and washers MS Steel eye Bolts, Allen Screws etc ISI Marked. |
| 50 | S & F in replacement Rubber gasket 150mm dia ISI marked complete all as specified & directed by Engineer-in-Charge. |
| 51 | All as per Srl item No 49 here-in-before but 100 mm dia. |
| 52 | S & F in replacement profile gasket (MS bracket) 100mm dia ISI marked suitable for non clog submersible pump complete all as specified & directed by Engineer-in-Charge |
| 53 | M&L PCC foundation of size 75cmx75cmx20cm with PCC 1:2:4 type B-1(ushing 20mm graded crushed store aggregate) including 8mm thick frame base plate of size 40cmx40cm suitable for 40 to 60HP Non Clog Submersible Pump including self drill bolt of size 150mm long and 15mm dia of shank fully threaded 04 Nos made of stainless steel complete all as specified & directed by Engineer-in-Charge.Note : The platform shall be constructed in sewage well of approximate 12mtr deep including dewatering if required and the contractor shall quote rate keeping in view the depth of sewage well and dewatering. |
| 54 | S & F in replacement CI sluice Valve PN 1.6 with SS Steel spindle and CI wheel ISI Marked of Size 100mm complete all as specified and directed by Engineer-in-Charge. |
| 55 | All as per Srl item No 53 here-in-before but 150 dia. |
| 56 | All as per Srl item No 53 here-in-before but 200 dia. |
| 57 | All as per Srl item No 53 here-in-before but 250 dia. |
| 58 | Supply fix and testing in replacement of Non Return Valve 250 mm dia PN 1.6, connected with two end flanges suitable for connecting with Pipe, nut-bolts etc including taking down old unserviceable one complete with flanges nut - bolts etc all as specified and directed. |
| 59 | All as per Srl item No 57 here-in-before but 150 mm dia. |
| 60 | All as per Srl item No 57 here-in-before but 100 mm dia. |
| 61 | S & F in replacement MS Nut, bolts and washers of size 5/8\"x3\", 5/8\"x4\" long complete all as specified and directed by Engineer-in-Charge. |
| 62 | Supply and fixing inreplacement Heavy duty fully automatic star-delta starter for Non clog Sewage submersible pump set of capacity 40 HP, 415 V, 50 Hz ,3 Phase, with suitable rating of contactor, overload relay range, with single phase protectioncomplete all as specified and directed by Engr-in-Charge. |
| 63 | Supply and fixing inreplacement Heavy duty fully automatic star-delta starter for Non clog Sewage submersible pump set of capacity 30 HP, 415 V , 50 Hz ,3 Phase,with suitable rating of contactor, overload relay range, with single phase protection with Ammeter Voltmeter complete all as specified and directed by Engr-in-Charge. |
| 64 | S&F in replacement BOCR 3EZ thermal over load relay 05-60 Amps,415 volts , 50 Hz complete all as specified and directed by Engr-in-charge.Note:- Contractor have to install BOCR Relay in starter with in 45 days after accepting of tender otherwise Rs 20000 /- per item will be recovered from contractor for non execution. |
| 65 | Dismanteling the UNSV sign board in sewage wells of Sector \"A\", \"B\" &\"C\" . Supply and fixing of retro reflector board of size 4\"x3\" with high quality retro reflector tape green base high intensity prismatic sheeting (HIP) grade white retro tape cutting good quality with 3mm thickACP sheet base including 40mm x 40mm square size MS pipe legs and all around the board appx 18feet incl welding the MS flat plate of size 25mm x 3mm across the board appx 10 feet including groutingthe sign board in PCC 1:2:4complete all as specified and directed by Engr-in-Charge. |
| 66 | Supply and fixing high quality ACP sheet board of size 5 feet x 3feet minimum with router cutting letter blue base of sheets and white colour acrylic letter with complete fitting of minimum 3 NosLED lights of 20 W of 4 feet includingwiring from existing DB Board complete all as specified and directed by Engr-in-Charge. Note- Detail of printing material for flex will be provided by department. |
| 67 | M&L for attending any type pump/motor/LT panels/DGs/Starters complaint at Sewage pump housesand rectify the same, rates are also included for replcement of thimbles any type and any size with nut-bolts and cable jointing with tap, gland packing, greasing in pumps/valves with all connected items all as specified by the Engr-in-Charge. Note: Complaint should be rectify within 06 Hrs otherwise a penalty of 1000 Rs per day will be imposed. |
| 68 | Scraping old existing paint from delivery line inside and outside the sewage well including making smooth surface and primer and applying two coat of synthetic enamel paint of pipe size 100 to 250 mmapproved colour as specified and directed by Engr-in-charge. |
| 69 | Dewatering sewage well and taking up rusty & chocked CI rising main 100mm dia from sewage well 10 to 12mtr deep opening up rusty & worn out nut & bolts cleaning the same with wire brush, bocky & refixing in sewage well by replacing nut, bolts & rubber gasket etc, complete all as specified and directed by Engr-in-Charge |
| 70 | All as per ser item No. 68 here in before but 150/250 mm dia. |
| 71 | Supply and fix replacement CI fittings Bend, tee, reducer etc for pipe 100m to 300mm dia complete all as specified and directed. |
| 72 | S&F Electric Resistance Insulated Rubber Floor mat sheet of size 1mx2mx25mm thick ISI marked and equivalent colour as per direction with fixing mtrls complete all as specified and directed. |
| 73 | Supply and fixing flex board of mininmum size 4 feet x 3feet including angle iron with painting complete all as specified and directed by Engr-in-charge. Note- Detail of printing material for flex will be provided by department. |
| 74 | M & L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 3.15 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level), and top edge of earth plate not less than 1.5 mtr below normal ground level, connected to galvanisedmeans of GI strip 32x6 mm and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion.Note:- Earthing shall be tested after execution and payment shall only be admissible if result found proper. |
| 75 | M&L for preperation of old decorated plastered or unplastered surfaces of walls of Sewge tanks/bldgs by complete brooming down or steel wire brushing , scrapping down smoke and applying two coatof Apexpaint complete at all Sewage wellinstallations all as specified and directed by Engr-in-Charge. |
| 76 | M & L for preperation of old decorated brick / concrete , plastered or unplastered surfaces of ceiling by brooming down with steel wire brushing, scraping down smoke soot, moulds, moss and effloroscent salts, trading oil and grasy spots etc. and applying one coat of white wash on ceiling/wall completeat all sewage wellinstallations all as specified and directed. |
| 77 | M&L forPCC ( 1:4:8 ) type D2 with 40 mm graded aggregate for foundations, filling and mass concrete complete all as specified and directed by Engr-in-Charge . |
| 78 | Desiliting/cleaning of sewage well of depth 12 Mtr and 9 Mtr dia taking out sludge by sludge vacuum truckin the form of solid also and getting out and removal to as distance exceeding 250mtr but not exc 500 Mtr and burried the same in low laying area as directed by Engr-in-Charge.Note :- (a) Dewatering of sewage well shall be included in the quoted rate of item.(b) Contractor have to arrange all safety equipments for works in sewage well at his own cost as directed by Engr-in-Charge.(c) Desilting of Sewage well should be donewithin 72 Hrs otherwise a penalty ofRs 5000/- per day will be imposed. |
| 79 | Material and labour for rubber moulded machine pressedprecast concrete interlocking paver block with grey cement confirming to IS -15658-2000 of 60 mm thickness , M-35 grade as in path , hard standing etc laid over and including 25 mm compacted sand cushioning , including 75 mm thick PCC 1:4:8 type D-2 using 40 mm graded crushed stone aggregate including surface excavation over area n. exc. 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil and remving excavated soil exc 50 mtr but n . exc 250 mtr, at any installation as per requirement complete all as specified and directed by Engr-in-charge. |
| 80 | Complete removal of the wild grass/ vegetation from surrounding area of SEWAGE Well installations area for each sewage well and making the surface clear and plain and spraying roundup chemical on the same clean areaas directed after removing and depositing the same at a distance not less than 50 mtr away from the site complete all as specified and directed. Note:- T&P machinary will be provided by the contractor. Cleaning should be done regularly as per directed by Engr in Charge. However, payment shall be made one time during contract period. otherwise penalty of Rs. 1000/ per dayper well for non cleaned surrounding area. |
| 81 | Maintenance and repair to leakage/blockage of water supply MS/CI/DI pipe line of 80 mm to 250 dia size including necessary excavation required for taking out burning out lead joint or damaged rubber ring/hole from position and making the disturbed surfaces as per existing surface after replacing new spun yarn and lead joint or Tyton joint or necessary fitting required as per site properly including welding workand making the pipe line leak proof completly to the entire satisfaction of Engineer-in-Charge .Note:- Excavation and earth work shall be included in quoted rate.Note: Complaint should be rectify within 12 Hrs otherwise a penalty of 1500 Rs per day will be imposed. |
| 82 | Note:-Amount of credit ofRs 220890.00 for retrieved materials is mentioned in Schedule of Credit attached in tender documents in pdf form which will be deducted offline while acceptance of tender. |