| 1 | Surface excavation not exceeding 30 cm and averaging 15 cm deep and getting out in soft/loose soil including removing green vegetation, roots, bushes,etc from surrounding of LT feeder Boards/Poles/substations etc complete all as specified and directed. |
| 2 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 3.0 mtr in depth for laying of cables errecting of pole including getting out in any kind of soil complete all as specified and directed. |
| 3 | All as per item no. 02 here-in-above but exceeding more than 1.5 m in depth complete all as specified and directed. |
| 4 | Returning filling in including spreading, levelling, and well ramming, in layers not exceeding 25 cm each layer of any kind of soil complete all as specified and directed. |
| 5 | Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding1.5 mtr above the starting point complete all as specified and directed. |
| 6 | Clean dry sand laid in trenches/ducts for bedding andcushioning to cable, including spreading and leveling complete all as specified and directed.Note:-(i) Consolidated/punned sand shall be considered for purpose of payment.(ii) Sand shall be same as specified for plastering work. |
| 7 | Taking up or down 10 sqmm 2 core worn out/ damaged / partially serviceable/unserviceable PVC insulated underground cable, armoured, heavy duty with aluminium conductors 1100 volt grade fromtrench including taking out unserviceable bricks,pipes etc testing of cable in the presence of Engr-in-charge to ascertain seviceability,seggregating serviceable and unserviceable cable and keeping in safe custody the serviceable portion for reuse, stocking serviceable bricks for reuse complete all as specified and directed(Note: Earth work shall be measured and paid separately under relevant item of Sch \"A\" ). |
| 8 | All as per item No. 07 here-in before but for cable of size 4 core 10 sqmm. |
| 9 | All as per item No. 07 here-in before but for cable of size 4 core 16 sqmm. |
| 10 | All as per item No. 07 here-in before but for cable of size 4 core 25 sqmm. |
| 11 | All as per item No. 07 here-in before but for cable of size 4 core 35 sqmm. |
| 12 | All as per item No. 07 here-in before but for cable of size 3.5 core 95 sqmm. |
| 13 | All as per item No. 07 here-in before but cable of size 3.5 core 120 sqmm. |
| 14 | Supply,laying, commissioning and testing or passing through pipe in replacement, XLPE insulated, armoured, electric power UG cable (Heavy duty) with aluminium conductor, 1100 volts grade in duct / trenches for small length for extension/replacement of the defective cable of nominal cross sectional area 10 sqmm 2.0 core including brass compression cable gland, terminal aluminium lugs etc making connection and testing complete all as specified and directed.Note :-(i) Pipes and bricks for protection, mild steel clamp nut and bolts sand cushioning shall be measured and paid separately |
| 15 | All as per item No. 14 here-in before but cable of size 4 core 10 sqmm. |
| 16 | All as per item No. 14 here-in before but for cable of size 4 core 16 sqmm. |
| 17 | All as per item No. 14 here-in before but for cable of size 4 core 25 sqmm. |
| 18 | All as per item No. 14 here-in before but for cable of size 4 core 35 sqmm. |
| 19 | All as per item No. 14 here-in before but for cable of size 3.5 core 95 sqmm. |
| 20 | All as per item No. 14 here-in before but cable of size 3.5 core 120 sqmm. |
| 21 | Laying, commissioning and testing or passing through pipe, XLPE insulated, armoured, electric power UG cable (Heavy duty) with aluminium conductor, 1100 volts grade in duct / trenches for small length for extension/replacement of the defective cable of nominal cross sectional area 10 sqmm - 95 sqmm 2 Core - 4 core including brass compression cable gland, terminal aluminium lugs etc making connection and testing complete all as specified and directed.Note :- UG cable will be issued under Sch `B\" free for fixing/laying from AGE E/M (N) Patiala(ii) Excavation, Pipes and bricks for protection, mild steel clamp nut and bolts sand cushioning shall be measured and paid separately |
| 22 | All as per item No. 21 here-in before but of size 3.5 core 120-150 sqmm. |
| 23 | All as per item No. 21 here-in before but of size 3.5 core 185-240 sqmm. |
| 24 | M & L for precast concrete cable covers type 2 flat, size 250mmx150mmx40mm laid dry in trenches for cable protection complete all as specified and directed. |
| 25 | Taking down carefully galvanized iron steel wiredrawn straight horizontal as continuous earth wire on existing LT poles of size 4.0 mm diafrom LT over head lines, after unbinding from insulators for replacement incl Restringing/ restretching to dismantled serviceableG I wire.Note:- (i)ReplacedG I wire shall be measured and paid under respective item supply only of sch for measurement length of each wireshall be takenseparately. |
| 26 | Supply only galvanized iron steel wiredrawn straight/ horizontal as continuous earth wire on existing LT poles of size 4.0 mm dia complete all as specified and directed. |
| 27 | M&L for Dismantling insulators any type, any size from LT poles complete all as specified and directed. |
| 28 | M&L for Dismantling cross-arms of M.S. channel or angle sections etc from LT poles complete all as specified and directed. |
| 29 | M&L for Cross arms bracing supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shapes or sizes as indicated or directed and inclusive of one primer coat,one under coat and one finishing coat of paint complete all as specified and directed. |
| 30 | M & L for Stay assembly in replacement complete with accessories as shown in electrical plate No. 1 complete all as specified and directed.Note:- (loop type insulator, stay clamps, excavation and concrete measured separately |
| 31 | Supply and fix in replacement of stay wire galvanized iron stranded of size 7/3.15 mm,length of stay wire not exceeding 11 mtrs with each stay and fixed to stay and pole including tightening complete all as specified and directed. |
| 32 | Supply and fixing in replacement of loop type insulators porclain shackle type vitreous white, brown or green of size 65x90mm overall dimension and 20mm clearence hole all as specified and directed by Engineer-in-Charge, |
| 33 | M&L for Dismantling of ACSR conductors after unbinding from insulatorsNote:- (i)Total no of conductors in over head line to be taken down shall comprise a maximum of three phase, one neutral ,one street light/security light for measurement length of each conductor shall be takenseparately .All as specified and directed by Engineer in Charge. |
| 34 | Supply and fix in replacement of ACSR conductor weasel(6/1/2.59 mm)to bedrawn straighthorizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag ,jointing jumpers,etc complete all as specified and directed. |
| 35 | M&L for Painting to existing PCCpole of any typewith Black and yellow synthetic enamelpaint overexisting paint up to 1.5 m height from bottom alternatively strips 30 cm each including painting of ,clamps, nut, bolts with aluminum paint including providingpole number with white enamel paint and 100 mm dia(round)background ofblue enamel paint at site complete all as specified and directed. |
| 36 | Paint to existing steel tubular pole of any type complete withtwo coat of aluminium synthetic enamel paint from bottom to top of the pole inculding black and yellow paint upto 1.5 Mtr height from bottom alernaterely strip 30 cm eachincluding providingpole number with white enamel paint and 100 mm dia(round)background ofblue enamel paint at site complete all as directed. |
| 37 | M&L Paint to existing LT panel board of any type complete withtwo coat of weather proof synthetic enamel spraypaint over a coat of red oxide primer after preperation of the surfacecomplete all as directed. |
| 38 | Supply and fix in repair chain link fencing with post and door frame arrangement for LT panel/two pole structure/four pole structure/etc of height 4 feetcompleteall as specified and directed. |
| 39 | M&L for streching and tightning of existing ACSR conductor any size on LT pole 9 mtr long all as specified (one span consists of 5 ACSR conductors 1 earth wire and cradle guard) includind replacement of J hooks complete all as specified and directed. |
| 40 | M&L for replacement of shackle type porcelain vitreous, white brown or green insulator for working pressure 1.1 kv of size 100mm height and 115 mm dia including galvanized mild steel straps of section 38 x 5 mm size ,20 mm dia bolt nut and washers complete all as specified and directed . |
| 41 | Supply and fix LT spacer 02 way FIX type made out of PVC materialand suitable to work on 1100 volts fixed between 02 conductors in any position along the LT line for any size of conductoralong the feedercomplete all as specified and directed. |
| 42 | Supply and fix LT spacer 04 way F type made out of PVC materialand suitable to work on 1100 volts fixed between 04 conductors in any position along the LT line for any size of conductoralong the feedercomplete all as specified and directed. |
| 43 | Supply and fix LT spacer 05 way spiral type made out of PVC materialand suitable to work on 1100 volts fixed between 05 conductors in any position along the LT line for any size of conductoralong the feedercomplete all as specified and directed. |
| 44 | Supply and fix cable lugs aluminium any typesuitable for cable up to 70 sqmm including necessary crimping with crimping tool complete all as specified and directed . |
| 45 | All as per item 44 here-in-above but of size up to 120 sqmm. |
| 46 | All as per item 44 here-in-above but of size up to 150 sqmm. |
| 47 | All as per item 44 here-in-above but of size up to 240 sqmm. |
| 48 | All as per item 44 here-in-above but of size up to 300 sqmm. |
| 49 | M&L for replacement existing worn out /over heated/multi-jointed ACSR jumpers of LT over head lines with and inclXLPE/PVCinsulated 1100 volts multi stranded aluminium conductor single core cable of size 120 sqmm as per colour code in sequence Red ,yellow ,blue and black for neutralincl winding with ACSR conductors with suitable size aluminium binding wire complete all as specified and directed . (Length of one jumper not exceeding more than 2.0 mtrs . |
| 50 | M&L for replacement existing worn out /over heated/multi-jointed ACSR jumpers of LT over head lines with and inclXLPE/PVCinsulated 1100 volts multi stranded aluminium conductor single core cable of size 240 sqmm as per colour code in sequence Red ,yellow ,blue and black for neutralincl winding with ACSR conductors with suitable size aluminium binding wire complete all as specified and directed .(Length of one jumper not exceeding more than 2.0 mtrs . |
| 51 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 63 Amps 3 Pole breaking capacity at 415 volt AC 50 Hz 25 kA complete all as specified and directed. |
| 52 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 63 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 25 kA complete all as specified and directed. |
| 53 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 100 Amps 3 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 54 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 160 Amps 3 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 55 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 160 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 56 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 200 Amps 3 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 57 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 200 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 58 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 250 Amps 3 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 59 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 250 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 60 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 400 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 61 | S&F inreplacement ofMCCB with adjustable thermal and magentic setting typeRelease Range 630 Amps 4 Pole breaking capacity at 415 volt AC 50 Hz 36 kA complete all as specified and directed. |
| 62 | Supply and fix dangernotice plate of 1.6 mm thick mild steel sheet, vitreous enamelledwhite ,with letters and conventionalskull and bone in postal red color and fixed with flat iron clamps, nuts, bolts , and washersof size 200mmx 150 mm for LT complete all as specified and directed.Note :(Note:-the printingshall be hand written only stancils embossing shall not be allowed ,and size of letter shall be 50x10 mm (height x width .) |
| 63 | S&FLT Air Circuit Breaker 4 Pole, 415V, with Thermal Magnetic Release adjustable type (Manual Draw out type) of capacity 630 Amps complete all as specified and directed. |
| 64 | S&F LT Air Circuit Breaker 4 Pole, 415V, with Thermal Magnetic Release adjustable type (Manual Draw out type) of capacity 800 Amps complete all as specified and directed. |
| 65 | Demolition of concrete of any description and in any position not otherwise specially provided for complete all as specified and directed. |
| 66 | Earthing complete with Galvanized steel earth plate 600 x 600 x 6.0 mm burieddirectly in ground (earth pit not less then 2.25 Mtr deep below ground level) with top edge of the plate not less then 1.5 Mtr below normal ground level connected to GIstrip of size 25X4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel incl excavation and earth work, GI pipe light grade 25mm/40 mm bore for protection of GI wire /strip fromearth electrode to and incl the supplying and lying charcoaldust, common salt,PCC 1:3:6 type CI (using20 mm graded crushedstone aggregate)as inchamber and MS angle iron frame 40 x 40 x 3mm and RCCcover 40 mm thick 1:2:4 type B1 (using 20 mm gradedcrushed stone aggregate) reinforced with 8 mm dia. TMT bars @ 75mm c/c bothwayswith MS handle 12 mm dia, PGIfunnel andwire mesh, 20 mm dia GI pipe light grade for watering all as shown in electrical plate No. 3 of SSR Part I of 2009 and connected to earth test point incl testing complete all as specified and directed. |
| 67 | M & L for PCC 1:4:8 TYPE D-2 using 40 mm graded broken stone aggregate as in mass concrete in foundations etc. complete all as specified and directed. |
| 68 | M&L for PCC 1:2:4 type B-1 using 20 mm graded broken stone aggregate as in mass concrete in foundations etc complete all as specified and directed . |
| 69 | Material and labour for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate for coping around the pole strut above ground level, foundation of stay etc. including neccassory form work and finishing the surface fair and even without using extra cement complete all as specified and directed . |
| 70 | Repair to LT panel box/body by repalcing the damaged/rusted MS sheet of existing gauge fabricated cut to size of original length inclproviding hinges and other hard ware item like handless etc. complete all as specified and directed . |
| 71 | Meterial and labour for making locking provision to the LT panel board of any size/typeby providing MS flat iron 25x6 mm up to lengh 15cm duly welded tothe both front andback door duly holed for making provision for lock includingwelding of brocken/unserviceable hinges/mounting arrangements of doors and matching with enamel paint of existing colour on the disturbed surfacesandproviding pad lock not less than 75mm with triplicate key complete all as specified and directed. |
| 72 | S&Fin replacement of volt meter 100x100 mm squre type digital 0-600 Volts complete all as specified and directed. |
| 73 | S&Fin replacement ofAmpere meter 100x100 mm squasre type digital 0-800 mm Amp complete all as specified and directed. |
| 74 | Suppling and fixing in repalement selector switch for voltmeter and Ampere meter complete all as specified and directed. |
| 75 | Suppling and fixing of LT CTs 60 Amps up to 200 Amps current rasting 415 volts complete all as specified and directed. |
| 76 | All as per item no. 75 here-in-above but for 200 Amps up to 400 Amps current rating 415 volts. |
| 77 | All as per item no. 75 here-in-above but for 400 Amps and up to 800 Amps current rating 415 Volts. |
| 78 | Supply & fixing LED type indicator Red, Yellow, Blue complete with base and connection complete all as specified and directed. |
| 79 | M&L cable jointing kit for 1100 Volt grade cableheat shrink type joint complete with jointing meterial and ascessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to 150 sqmm complete all as specified and directed. |
| 80 | M&L cable jointing kit for 1100 Vgrade cable for indoor type heat shrink type joint complete with jointing meterial and ascessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 185 sqmm to 400sqmm complete all as specified and directed. |
| 81 | Supply,laying,galvanised steel tubing light grade complete ith all fitting of size 40 mm dia for cable protection along with pole across road etc. complete all as specified and directed. |
| 82 | All as per item Ser No 81 above but size of pipe 80 mm dia. |
| 83 | Supply installation in repairs, testing and commissioning in replacement of LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 630 amp marked red, yelllow, black and blue mounted on inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mmmultistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- Note:- Approval of panel drawing must obtained from AO before placing the order andPCC shall be measured and paid separately INCOMING:- (a) MCCB 400 Amps microprocessor based with adjustable thermal and magnetic 415 Volts,25KA, 4 pole.-01 No. OUT GOING:- (a) MCCB 63 Amps with adjustable type 4 pole 415 Volts, 16 KA-8 Nos(b) Digital type Volt meter 0-500 Voltssquare typewith selector switch- 01 No.(c) Digital type Ammeter 0-400 Amps square typewith selector switch- 01 No.(d)Wiring complete with copper wire of suitable size (e) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set.(f) Cable glands brass of suitable size for cable. |
| 84 | Supply installation in repairs, testing and commissioning in replacement ofLT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 400 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mmmultistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- Note:-Approval of panel drawing must obtained from AO before placing the order andPCC shall be measured and paid separately. INCOMING:- (a) MCCB 250 Amps microprocessor based with adjustable thermal and magnetic 415 Volts,25KA, 4 pole.-01 No. OUT GOING:- (a) MCCB 63 Amps with adjustable type 4 pole 415 Volts, 16 KA-5 Nos(b) Digital type Volt meter 0-500 Voltssquare typewith selector switch- 01 No.(c) Digital type Ammeter 0-400 Amps square typewith selector switch- 01 No.(d)Wiring complete with copper wire of suitable size (e) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set.(f) Cable glands brass of suitable size for cable. |
| 85 | Supply installation in repairs, testing and commissioning LT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 630 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mmmultistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- Note:- Approval of panel drawing must obtained from AO before placing the order andPCC shall be measured and paid separately INCOMING:- (a) MCCB 400 Amps microprocessor based with adjustable thermal and magnetic 415 Volts,36KA, 4 pole.-01 No. OUT GOING:- (a) MCCB 250 Amps with adjustable type 4 pole 415 Volts, 25 KA-02 Nos & MCCB 160 Amps with adjustable type 4 pole 415 Volts, 16 KA-02 Nos (b) Digital type Volt meter 0-500 Voltssquare typewith selector switch- 01 No.(c) Digital type Ammeter 0-400 Amps square typewith selector switch- 01 No.(d)Wiring complete with copper wire of suitable size (e) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set.(f) Cable glands brass of suitable size for cable. |
| 86 | Supply installation in repairs, testing and commissioning in replacement ofLT Feeder piller board out door type cubicle panel boardsuitable for 3 phase,4 wire 415 volt 50 hz factory febricated approved CPRI powder coated made out of 3.0 mm thick CRCA sheet and MS angle iron sectiom 40X40X6mm frame with front and back openable double door system with locking arragement louver and air vent gaket for netural flow of air with conopy, inner compartment made out of 2 mm the CRCA sheet duly compartmentalized for each MCCB of incoming and outgoing with lockable arragement with alluminium bus bar three phase and neutral of capacity of 400 amp marked red, yelllow, black and blue inslulators, made of high strength insulated material suitable 1100 voltage all controll PVC wires shall be with 2.5 sq mmmultistrand copper conductor and shall be properly bunched, tied, frerruled for proper indication , fixed on PCC foundation complete with following accessories:- Note:-Approval of panel drawing must obtained from AO before placing the order andPCC shall be measured and paid separately INCOMING:- (a) MCCB 250 Amps microprocessor based with adjustable thermal and magnetic 415 Volts,25KA, 4 pole.-01 No. OUT GOING:- (a) MCCB 63 Amps with adjustable type 4 pole 415 Volts, 16 KA-6 Nos(b) Digital type Volt meter 0-500 Voltssquare typewith selector switch- 01 No.(c) Digital type Ammeter 0-400 Amps square typewith selector switch- 01 No.(d)Wiring complete with copper wire of suitable size (e) Indicator lamp LED type, set of three marked red, yellow & blue - 01 Set.(f) Cable glands brass of suitable size for cable. |
| 87 | Suppy and fix rigid non-metallic PVC conduit 20 mm dia exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed. |
| 88 | Supply and fixing junction box of size 300 mm x 200 mm x 105 mm, made out of FRP sheet with weather proof hinged door including self locking arrangement, out door type weather and vermin proof complete comprising of insulated / high quality PVC sleeves aluminium bus bar of capacity 63 Amps 04 Nos (three phase RBY and black for neutral) with and including 6 Apms MCB single pole, single phase 230 volts, including 25 x 3 mm flat iron mounted on insulators, having arrangement of connecting incoming and outgoing cables complete and all as specified and directed. |
| 89 | Supply and fixiing PVC insulated round/flat copper cable of size 3 core, 2.5 Sqmm for connection of LED lights from FRP junction box to street light fitting complete all as specified and directed. |
| 90 | Boring of holes under road, pavement, hard standing by trench-less technology using ultrasound technique and necessary machine suitable to pass through 40 to 80 mm boreGItubing and cable etc complete all as specified and directed. |
| 91 | Supply in repairsand erecting of Prestressed concrete pole, 9.0 metres long, 102mm x 152mm at top and 102mm x 289mm at bottom, class 10 including painting complete all as specified and directed at site by Engr-in-Charge. |
| 92 | Supply and erecting in repairs in true verticle position of steel tublar pole 9 Mtrs long complete with cast iron base plate finial taper plug bolt nuts and screws as as specified and of type 410 SP-31 conforming to relevent IS including two coats of aluminium paint over aone coat of red oxide primer to the full length of the pole and also two coats of bituminus paint inside outside of bottom portion upto 1.5 mtrs length and provide circular bend 32 mm dia 1 Nos of length 2 mtrs duly fixed with necessary clamp for mounting LED security light all as specified and directed by Engr-in-Charge. Note:- Excavation and PCC shall be measured and paid separetaly. |
| 93 | Material and labour for Periodical cutting of trees /trimming of branches along the LToverhead lines in a girth of 03mtrs on either side of the conductors including removing the same and dumpingcomplete all as directed by Engr-in-Charge. Note : Expenditure for necessary tool and plants required for Periodical cutting of trees / trimming of branches along the HT /LT overhead lines are deemed to be included in rate quoted by the contractor. |
| 94 | Special Notes for above schedule of work:- (i) External electrification services are of being emergency work the site work arranged to contractor shall commence within 10 days and any further delay shall be resulted in penality as per PS.(ii) Contractor has to take upmost care to avoid damage to existing lines/structure during the excution of work.(iii) Contractor has to ensure the proper safety of his team to avoid any mishappening at site of work , if any mishappening occures the contractor will be solely responsible for it all as specified and directed by Engr in Charge |