Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 5 Mva, 33/6.6 Kv Substation On Turnkey Basis At Rampur Batura Ocp, Sohagpur Area, Secl, sohagpur-Madhya Pradesh

South Eastern Coalfields Limited-SECL has published Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 5 Mva, 33/6.6 Kv Substation On Turnkey Basis At Rampur Batura Ocp, Sohagpur Area, Secl. Submission Date for this Tender is 19-06-2023. Substation Tenders in sohagpur Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

37556025
Tender For Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 5 Mva, 33/6.6 Kv Substation On Turnkey Basis At Rampur Batura Ocp, Sohagpur Area, Secl
Open Tender
Indian
Madhya Pradesh
sohagpur
19-06-2023

Tender Details

Planning, Design, Engineering, Construction, Fabrication, Supply, Erection, Trial Run And Commissioning Of 2 X 5 Mva, 33/6.6 Kv Substation On Turnkey Basis At Rampur Batura Ocp, Sohagpur Area, Secl

Key Value

Document Fees
Refer document
EMD
INR 1466700.0 /-
Tender Value
INR 11.73 Crore /-

BOQ Items

Name of the Work / Contract No:
Sl. No. Item Description
1DESIGN AND ENGINEERING COST(for2 X 5 MVA, 33/6.6 kV S/S)
2Design and Engg onPLANT & MACHINERY ( P&M - Electrical) to be supplied by bidder inlcusive of Overhead constuction cost, Contigencices, but excluding GST
3Design and Enggon Civil & Structural work
4CIVIL CONSTRUCTION AND STRUCTURAL WORKSfor2 X 5 MVA, 33/6.6 kV S/S on Turnkey Basis at Jhiria West OCP inclusive of Insurance,Contingencie but excluding GST
5Sub-station Building
6Outdoor steel structures
7Foundation of outdoor structures including Transformer foundation
8Cable Trench
9Barbed wire fencing
10Boundary wall
11Gate
12Road
13Surface dressing
14Stone laying
15Anti weed treatment
16Bore well with submersible pump
17Path way
18Security Room
19RCC sump and Pump House
20Shed for DG & oil filter unit
21Drain along boundary wall
22Parking Shed
23Oil Overflow Chamber
24Oil Drain Pipe
25Survey & Soil testing
26SUPPLY OF PLANT & MACHINERY inclusive of Overhead Construction cost, Insurance, Contingencies, but excluding GST forsubstation ( 2 X 5 MVA, 33/6.6 kV Substation )
27Isolators, 33 kV (nominal),3 poles, pole mounted, 1250A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker (Min 4 Sets)
28Isolators, 33 kV (nominal), 3 poles, pole mounted, 1250A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker withEarthing switch (Min 2 Sets)
29Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker (Min 2 Sets)
30Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,25kA, arrangement for interlocking with 33 kV Vacuum Circuit breaker withEarthing switch (Min 2 Sets)
31Isolators, 33 kV (nominal), 3 poles, pole mounted, 630A,25kA, with D.O. Fuses. (Min 4 Sets)
32Lightning Arrestors, station class, 30 kV,10 kA, suitable for 33kV, solidly earthed (each set consists of 3 nos.) with counters/surge monitors (Min 6 Sets)
33Single phase current transformer ,outdoor type with required CT ratiofor 33 kV system for metering and protection (1 set consists of 3 units for 3 phase supply) (Min 5 Sets)
34Potential transformer ,outdoor type 33kV, 100 VA each 33/v 3 kV/ 110/ v 3 Vfor metering and protection each for three phase system (Min 2 Sets)
35Vacuum Circuit Breaker, 33kV,630 A/1250A, outdoor type, 25 kAwith remote control panelhaving IDMTL relay for O/L and E/F protection, ammeter, energymeter (Min 4 Nos)
36Power Transformer outdoor type plinth mounted 33/6.6kV, 5 MVA, ONAN cooled, DY-11 conforming to IS:2026 (current) having OFF-LOAD tap changer on HV side and LV neutral effectively earthed through required value of Resistance ( Restricted Neutral System) with all accessories including 33 kV remote control panel for on load tap changer as per IS:3639 (Current) with the rating as given below Rated kVA: 5000 Rated Voltage(primary):33000V Rated Voltage(secondary):6600V Connection and vector group:Dy11 (Min 02 Nos)
37Neutral Grounding Resistors with Protection (Min 2 Nos)
38Lightning Arrestors, station class, 6 kV,5 kA, suitable for 6.6kV, solidly earthed (each set consists of 3 nos.) with counters/surge monitors (Min 2 Nos)
39Isolators, 6.6 kV (nominal), 3 poles, pole mounted, 630A, arrangement for interlocking with 6.6 kV Vacuum Circuit breaker withEarthing switch (Min 2 Nos)
406.6 kV switch-board, indoor type, 19 panel, with vacuum circuit brakers75 MVA symmetrical breaking capacity. The function of eachpanel is as given below: All panels will conform to IS:3427 (Current) and relevant parts to IS:2516 ( current). These will be provided with cable entryboxes. The incoming panels will be provided with restricted earth fault protection. All panels will be provided with IDMTL relays for over current and earth fault protection. The incoming and outgoing panels shall be provided with Trivector meters. (Min 1 Set)
41Station Transformer,outdoor typerated as follows: Rated kVA: 160 Rated Voltage(primary):33000 V Rated Voltage(secondary):433 V, Cu wound , Plinth mounted (Min 1 Nos)
42Lighting Transformer,outdoor typerated as follows Rated kVA: 100 Rated Voltage(primary):33000 V Rated Voltage(secondary):230V(L-L) , plinth mounted (Min 1 Nos)
43415V switch board, indoor type with 4 nos MCCB having O/L,S/C and E/Lprotection, 25 MVA symmetrical breaking capacity (All out going panels will be provided with ammeter, and incoming panel with ammeter and voltmeter). The function of panels will be as follows : - 1 no, MCCB, 800A, CTR of 300/5 A, as controller for incoming feeder. - 3 nos, MCCBs, 400A, CTR of 100/5 A, as controller for outgoing feeders. (Min 1 Nos)
44230 V (L-L) Main Lighting Distribution boards with the following : --1no. MCCB, 3 pole,400 amps for control of incoming feeder. --3 nos.,MCBs, 2 pole,63 amps for control of out going feeders. --3 nos.,MCBs, 2 pole, 32 amps for control of out going feeders. (Min 1 Nos)
45Capacitor bank, 6.6 kV indoor type 1000 kVAR including APFC. (Min 2 Sets)
46Battery (110 V) lead Acid type, 200 AH and battery charging (with one stand bye battery charging unit) equipment, control panels, wooden racks etc.
47Earthing system (Safe Earth Electrode type) including earth pits, required galvanised strips/flats for inter connection etc.
48Lightning protection system consisting of spikes, earth pits, galvanised strips/flats, shield conductors etc.
49Luminaries
50Decorative, 1x12/15/18W and 2x15/18 W LED (Suitable rating) light fittings
51Suitable rating LED Bulbs for indoor lighting
52Tubular steel poles,11m height along with 90 W LED lamps with fittings
53Lighting masts, 16m height (Min) along with required nos. of 200 W LED lamps with fittings.
5490 W LED fitted on substation building (Min 4 Nos)
55Emergency lighting system suitable for operation on 110 V DC supply in substation building.
56Accessories such as sub distribution board, junction boxes,individual control cables, PVC conduits/ casings, back up fuses, switches, sockets, ceiling roses, single core PVC cable with copper conductors, flexible wire etc.
57Cable and accessories
58HT power cable, 6600 V grade, XLPE, FRLS, Copper conductor
59LT Power cable, 1100V grade, PVCSWA, 10 sq. mm.(minimum),3/4 core copper stranded conductors
60Outdoor Lighting cable, 1100V, PVCSWA , 2 cores, 10 sq mm (minimum) stranded Al conductors
61Outdoor Control cables, 1100V grade, PVCSWA, not less than 2.5 sq mm , copper conductors of with required number of cores
62Wires for internal wiring of 1.5 sq mm and 6 sq mm size, PVC insulated copper conductor cable of 1100 V grade.
63Cables for internal control wiring of illumination, ceiling fans, power sockets etc. 2.5 sq mm size, PVC insulated copper conductor of 1100 V grade
64Cable trays, cable racks, binding materials, cable glands/lugs, cablejointing kit, bolts, nuts, washers, termination kit etc.
65Overhead conductors,Insulators,Towers, poles, insulators, string bus, ACSR conductors, steel hardware etc for 33 kV sides in the out door yard. 2 pole structure fitted with gang operated AB switch, lightning arrester etc for out going feeders
66Fire Fighting System
67Fire fighting equipment consisting of fire hydrants hose cabinets, hose reels, valves, pipes,fire detection alarming system, high velocity water spraying system for transformers,diesel pump, electric pump with electricals and cables, jockey pump etc
68Supply of portable fire extinguisher system
69Sand buckets with stand
70Miscellaneous items
71Room air conditioners, min. 1.5 t capacity( 5 star rating ) including servo stabilizer
72Supply of 63 kVA Diesel Generator set (silent type) with 3 ph, 50 Hz ,415 V output supply with cable, change over switch and earthing etc (Min 1 Nos)
73Exhaust fans, 600 mm sweep.
74Ceiling fan ,1200 mm sweep along with electronic regulator (5 star rating)
75Water cooler with water purifier (Min 1 Nos)
76Vacuum Cleaner Set (Min 1 Nos)
77Erection and commissioning of Plant and Machinary for substation to be suplied by bidder as above inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST
78Training of O&M staff
79Store cost for maintenance of P&Mduring Defect Liability Period (DLP) of five years.
80Cost of Maintenace during during Defect Liability Period (DLP) of five years.
81Total impact of GST for the purpose of CTC