| Sl. No. | Item Description |
| 1 | Testing and setting the relays of VCB\"s/SF6s breakers of 33 KV by primary injection method of any make/model and servicing the mechanical parts, cleaning inside & outside with CRC-26 spray including replacing the unserviceable minor parts like springs, gear, nuts, bolts and washers, internal wiring if necessary and lubricating all thecomplete to the entire satification of Engr-in-charge. |
| 2 | Disconnecting and removing the unserviceable 33 KV burnt out 6/8 eight bolt clamps and supply and fixing new eight bolt type Aluminiumclamps suitable for panther aluminium jumpers / pipes including nuts, bolts, washers and testing complete all as specified and as directed. |
| 3 | S&F digital type volt meter suitable for Eleven KV breaker ranging (0-11KV/0 to 440 V) suitable for auxilary voltage 230 volts complete including taking down old unserviceable voltmeter complete all as directed. Make- MECCO/CONZERV/L&T |
| 4 | Disconnecting and taking down the worn out jumpers in 33 KV yard and supply and fix new jumpers cutting to adequate length of ACSR conductor panther complete all as specified and as directed. |
| 5 | Servicing of HT OCBs 400 to 1200 Amps, after manually operating and removing of old oil and top up with new oil and testing & commissioning complete all as directed. |
| 6 | Dehydration and filtration upto 5 MVA transformer 33/11 KVA, HT OCB oil indoor/outdoor/ isolation type at different location and different size of transformer from 63 KVA to 1000 KVA or any capacity Transoformer on DMRL/ATClocation with centrifuging machine, manually operated and achieve BDV 60 KV including carrying out oil testing before and after the dehydration process for each OCB complete all as directed. Note : Requiredoil for top up will be measured and paid separately under relevant item of schedule. |
| 7 | Supply only topping up of transformer/OCB oil as per IS :335, break down voltage not less than 60 KV all as specified and directed.Make :- Power Oil/Electrol |
| 8 | Supplying, installation, commissioning and testing in replacement of 33 KV Current Transformer (CT`s), indoor type, resin cast epoxy type,of 13.1 KA/Sec having ratio 400/1-1 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VAfor metering including associated wiring complete all as specified and directed |
| 9 | Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type,of 13.1 KA/Sec having ratio 200/1-1 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VAfor metering including associated wiring complete all as specified and directed |
| 10 | Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE, HTUG cable, 11000 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductorcable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete of size 95 sqmm 3 coreall as directed.Make: HAVELL\"S/UNIVERSAL/CCI/GLOSTER/POLYCAB/ KEC INTERNATIONAL (RPG)/FINOLEX |
| 11 | Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE,HTUG cable, 11000 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductorcable complete including lugs of required sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete of size 120 sqmm 3 coreall as directed.Make: HAVELL\"S/UNIVERSAL/CCI/GLOSTER/POLYCAB/ KEC INTERNATIONAL (RPG)/FINOLEX |
| 12 | Supply, laying, testing and commissioning in trenches/ ducts, fixed on walls/panels of XLPE LTUG cable, 1100 volts grade, PVC insulated, PVC unsheathed armoured with aluminum conductorcable complete including lugs of requied sizes for the following nominal cross sectional areas of cables including taking down old unserviceable cable complete all as directed:-Make: HAVELLS/ UNIVERSAL/ CCI/ GLOSTER/ POLYCAB/ KEC INTERNATIONAL (RPG) |
| 13 | 2 core x 10 Sqmm |
| 14 | 4 core x 16 Sqmm |
| 15 | 4 core x 25 Sqmm |
| 16 | 4 core x 35 Sqmm |
| 17 | 3.5 core x 50 Sqmm |
| 18 | 3.5 core x 70Sqmm |
| 19 | 3.5 core x 120Sqmm |
| 20 | 3.5 core x 185 Sqmm |
| 21 | 3.5 core x 150 Sqmm |
| 22 | 3.5 core x 300 Sqmm |
| 23 | 3.5 core x 400 Sqmm |
| 24 | M&L for Servicing & RepairstoAir-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotatingblades, with fixed contact jaws, arcing horns, applying petroleum jelly to moving mechanism, cleaning and lubricatingto isolator gear box assembly,tightening all nuts, bolts and clamps of jumpers etc, repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioningon load complete all as specified and directed. |
| 25 | S&F in replacement of LED indication lamp for breaker ON/OFF/TRIP/Breaker Spring Charged/R-Y-B etcfor 11/33 KV control panelincluding associated wiring, if reqd, complete all as specified and directed. |
| 26 | Supply, Lay & Test & Commissioning cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes 16 core 2.5 Sq mm. |
| 27 | M & L for cutting and removing grass, vegetation bushes etc from surrounding HT installation as bushes grows during a period of contract and removing all rubbish to a distance not exceeding 50 m as directed. |
| 28 | M&L for Repairs/maintenance of 11KV HT VCB/ SF6 breakers Panel including bus coupler of any type, size and capacity complete including the following :-Taking out 11KV HT VCB/OCB/SF6 breakers of 400/630/800 Amps rating trolley from HT Panel after switching off electric supply, checking of mechanical/motorised system for proper functioning of upward/downward movement of HT VCB trolley including opening the VCB & checking the quality of insulating. Cleaning & servicing the fixed/moving contact & blowing out dust from bus bar chamber, spout gear mechanism and applying the proper lubrication/greasing and cleaning/servicing the entire motorised mechanism of VCB including all spare parts required at site,reassembling the VCB connection, testing, commissioning andputting on load to the entire satisfaction of Engr-in-charge. |
| 29 | S&F Earthing complete with copper plate electrode 600x 600x 3 mm thick buried directly in ground vertically to a depthnot less than 2.25 mtr deep below normal ground level with top edge of earth plate, not less than 1.5 mtr below normal ground level connected to copper strip earth lead of size 20 x 3 mm by means of bolts, nuts/check nuts and washers etc of galvanised iron, protected by galvanised iron pipe light grade 50 mm dia and connected to main switch/control board including necessary excavation earth work in any type of soil and PCC 1:3:6 type C1 for earth chamber,40 mm thick RCC cover slab 1:2:4 type B1 with 6 mm dia TMT Bars at 140 mm ccboth ways,watering pipe 20 mm dia light grade GI, funnel, wire mesh, lugs, charcoal and salt etc complete all as shown in Electrical plate No. 3 SSR Part I and testing complete including removing unserviceable any type of items all as specified and directed.Note : Copper strip and GI pipe 50 mm dia beyond 7.5 metres per earth will be measured and paid separately. |
| 30 | All as per item No. 18 above but using 32 x 6 mm galvanised MS strip earthing lead and MS galvanised plate of size 600 x 600 x 6 mm as earth electrode. |
| 31 | S&F Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated location for loop earthing etc. as required of size 32x6mm GI strip complete all as specified and directed. |
| 32 | Supply & Fix Gasket in replacement forupto 5 MVA transformer (SRC RC 70C Grade) with including all required T&P for drain out and refilling trainsformer oil after proper filteration,comminissioning and testing complete complete all as directed. |
| 33 | Supply installing testing and commissioning in replacement the relay module Micom P111 making necessary cutting in the existing panel and necessary control wiring FRLS of size not less than 2.5Sqmm and providing Ferules for identification and necessary spares for fixing complete to the entire satisfaction of the Engr-in-Charge. |
| 34 | Testing and re-setting and calibration of protection relay of 11 KV RMU/VCBs/SF6 breaker (indoor/outdoor) forincoming and out going feeders with control panel and control cable differential relaythrough authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, Checking the condition of transformers (Oil & winding temp and B/H relay) and taking corrective checking and operating the switchgear and trip circuit of HT panel/breakers for its proper functioning complete all as specified and directed.Note:- Reports after calibration to be submitted and the autherised techinicion should attend the malfunctioning/routine service complints as and when required for entire contract period under warrenty. |
| 35 | M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. |
| 36 | M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm. |
| 37 | M&L for XLPE Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 400 sqmm. |
| 38 | M&L for XLPE cable jointing kit for 11 KV (earthed) for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 240 to 300 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed. |
| 39 | M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 120 to 185 sqmm, 3 core armoured aluminium conduct including taking down old unserviceable jointing kit complete all as directed. |
| 40 | M&L for XLPE cable jointing kit for 11 KV (earthed) for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 50 to 95 sqmm, 3 core armoured aluminium conductor including taking down old unserviceable jointing kit complete all as directed. |
| 41 | M&L stay assembly complete with accessories as shown in electrical plate no 1 including loop type isolator stay clamps stay strands excavation work and PCC work with 20 mm dia complete all as specified and directed. |
| 42 | Supply, fix and testing power pack with battery backup input 230 V AC, output 110 V DC, 1Amp suitable for existing HT 11 KV VCB panel complete all as specified and directed. |
| 43 | Supply, fix, testing and commissioning of Air break gang operated switch, triple pole mechanically operated out door type with all fittings/accessories mounted on and including 11 KV HT polymeric insulators and steel channel frame, GI operating rod 25 mm dia of suitable length with operating mechanism worked from ground level vertically operated including locking arrangement for operating handle with and including 7 levers Navtal lock complete suitable for current rating of 400 Amps HT 11 KV working pressure all as specified and directed. |
| 44 | Supply and Fix Dropout fuse unit, horn gap type single pole, mounted on and including insulators for 11 KV working pressure, fixed to and including MS channel with nuts, bolts washers etc, synthetic bounded fuse carrying tube complete with line taps and suitable for current carrying capacity upto 40 Amps only all as specified and directed. |
| 45 | M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive on one primer coat, one under coat and one finishing coat of paint. |
| 46 | Supply, Install and erect steel tubular swaged pole type 410 SP-55 of 11.0 mtrs long complete with cast iron base plate finial taper plug, pole cap, bolts, nuts and washers pole made out of MS tubing confirming to IS-2713 Part-II, including drilling of holes painting with two coats of bituminous paint internally and externally embedded portion in ground/concrete and painting to exposed surfaces with two coats aluminium paint and one coat of red oxide primer complete all as specified and directed.Note :- Excavation/Earth work in any type of soil/ strata PCC foundation, copingof poles, cross arms, clamps shall be measured and paid separately.Make :- M/s Bombay Tubes/ M/s Jindal Steel Products/ M/s India Tubes Co/ M/s Bharat poles/ National Tubing. |
| 47 | Supply, Install and erect steel tubular swaged pole type 410 SP-31 of 9.0 mtrs long complete with cast iron base plate finial taper plug, pole cap, bolts, nuts and washers pole made out of MS tubing confirming to IS-2713 Part-II, including drilling of holes painting with two coats of bituminous paint internally and externally embedded portion in ground/concrete and painting to exposed surfaces with two coats aluminium paint and one coat of red oxide primer complete all as specified and directed.Note :- Excavation/Earth work in any type of soil/ strata PCC foundation, copingof poles, cross arms, clamps shall be measured and paid separately.Make :- M/s Bombay Tubes/ M/s Jindal Steel Products/ M/s India Tubes Co/ M/s Bharat poles/ National Tubing |
| 48 | Material and Labour for PCC 1:3:6 type C2 wiring 40 mm stone aggregate for foundation of poles/transformer bed/cable duct foundation/panel base/ chain link supports etc including necessary form work etc complete all as specified and directed. |
| 49 | Material and Labour for PCC 1:2:4 type B1 wiring 20 mm graded stone aggregate for coping of pole including necessary form work etc complete all as specified and directed. |
| 50 | Material and Labour for Brick work with sub-class bricks straight or curved on plan exc 6m mean radious in CM (1:6) complete all as specified and directed. |
| 51 | Material & Labour for 10mm thick rendering in cement motar (1:6) mixed on brick or concrete surfaces finished even & smooth w/o using extra cement complete all as specified and directed. |
| 52 | Material & Labour for Providing precast cement concrete in landing cover slab type B-1 1:2:4 (20mm graded agg) set in cement 1:4 complete all as specified and directed. |
| 53 | M&L for spreading the 20mm coarse aggregate in various sub stations and other locations complete all as directed. |
| 54 | Supply and fix in repair of Impluse EmergencyFirst aid kit box with basic medicine like Band Aid strips of min 20 Nos, Anteseptic cream, Cotton, Surgical tape 1 inch, non sterial gauge swabs, Hydrogen peroxide bottle, medical spirit bottle complete all as specified and directed. |
| 55 | M&L for Preparation of old painted inner and outer surfaces ofindoor/out door HT/LT panels,spray painting the same with two coat of synthetic enamel paint grey and a coat of red oxide primer to achive smooth finishincluding writing of SM/MES No complete all as directed. |
| 56 | Testing and re-setting and checking connectionof control cable from transformer tap changerto panelof auto tap changer relay up to 5 MVA transformer through authorised service engineer, Checking of instruments function and taking corrective action for improvement if found improper, Tap changer panel l/breakers and tranformer control panel complete for its proper functioning complete all as specified and as directed. |
| 57 | M&L for maintenance servicing ,Calibration of existing APFC panel with and including repair/replacement of unsv of capacitor with existing size complete upto 500KVAR APFC Panelall as directed. |
| 58 | Supply and fix in repairs of Alarm annucator 12 window of model MBAS-0600 suitable for 33/11KV HT breaker completeall specified and directed. |
| 59 | S&F cable jointing kit forstraight through joint (epoxy) for 1.1 KV grade XLPE, PVC insulated and sheathed aluminium conductor under ground cable includingthimbles, nuts & bolts, washers etc and testing after jointing complete, all as directed for the following sizes.Make: M-seal/Raychem/Transeal/Denson |
| 60 | 6 sqmm to 16 sqmm 4 core |
| 61 | 25 sqmm to 50 sqmm 3.5 core |
| 62 | 70 sqmm to 120 sqmm 3.5 core |
| 63 | 150 sqmm to 400 sqmm 3.5 core |
| 64 | Material and labour painting of HT two pole structure 11 KV complete by scrapping the existing old paint and making the surfaces smooth including cross arms bracings complete and applying two coats of synthetic aluminium paintcomplete all asspecified and directed. |
| 65 | All as per Item No: 49 above but four/Six pole structureMake of Paint for item No. 3 & 4:Asian/Nerolac/Berger. |
| 66 | Labour for cutting the bushes and plants grown near the substation/ structures premises using necessary tools and plants and removing the plants from the root level at any depth and cleaning the premises completely and making good the site suitable forspreading the stone aggregate including disposing all the waste to a distance not exc 50M form the site all as directed by the Engr-in-Charge. |
| 67 | S&F digital type Ammeter suitable for Eleven KV breaker ranging (0-400) Amps suitable for auxilary voltage 230 volts including taking down old unserviceable Ammeter complete all as directed.Make- MECCO/CONZERV |
| 68 | M&L for spreading the 40mm coarse aggregate in various sub stations/Structure premises and other locations complete all as directed. |
| 69 | Cutting of trees and tree branches of girth up to 20cm and to a radius of 3M all around LT/HT OH linecomplete all as directed. Note: The distance between two adjacent poles will be considered as one span |
| 70 | M&L 11KV grade pin type, Porcelien insulator of clevis/Tounge/socket or ball type spindle including nuts and bolts of size type as specified by the manufacturer including all galvanised steel fittings as required at site and removing of unserviceable insulators complete all as specified and directed.Make :- Jaipuria/Rashtriya Electrical/Denson or make approved in the state Electricity board. |
| 71 | M&L for LT line zig zag PVC spacer including replacing the broken u/s spacers and necessary ladder arrangement should be made by the contractor during replacing as required at site. |
| 72 | M&L in replacementhorn gap fuse assembly mounted on porcelan insulatorand steel frame, D or Channeltype for HT 11 KV, 400Amps rated current including base frame made with \"C\" channel cross arms of suitable size shall beincluding removing the unserviceable drop out fuse assembly complete all as specified. Note: Fuse assembly for three phases will be considered as one Set. |
| 73 | M&L in replacement ofLightning arrester expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo Amp connecting to the earth strip including necessary fixing spares as required at site all as specified and directed. Note: A set of three lightening arresters will be considered as one set. |
| 74 | Repairs to AB switch (GOD) including replacement of male and female contacts, bolts & nuts and cleaning the carbon/ dust deposited on the switch contact surfaces and applying mineral jelly, oil grease to the moving/rotating partsetc after cleaning, removing carbon depositsincluding testing and commissioning the same for operation complete all as directed by Engr-in-charge.Note: The repairs to three poles of AB switch will be measured as on job. |
| 75 | Labour only for removing the binding of ACSR conductor of HT 3 phase4 wire over head line from insulator, removing the jumper, connector, service wire, UG cable and restringing the existing ACSR conductor of any size, length, span upto desired sag and fixing the same ACSR conductor on insulator by proper binding, jumper connection etc complete all as specified and directed. |
| 76 | M&L Earthing complete with galvanised steel earth plate electrode 600x600x6mm thick, buried directly and preferably vertically in ground ( earth pit not less than 2.25 mtr deep below ground level ) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip of 25x4mm(upto 7.5 M in length from earth plate) by means of bolts, nuts, check nuts and washers of galvanisediron or steel all as shown in electrical plate No 5, connected to earthing test point all as specified including earth work and excavation in any type of soil, PCC 1:3:6 type C1 chamber and RCC 1:2:4 type B1 cover 40 mm thick, with 8 mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 40 mm dia GI light grade pipe for earth lead protection, 20 mm dia GI light grade pipe for watering , water funnel, testing point etc., complete all as specified and testing on completion. |
| 77 | S&F rust free Acrylic Danger notice plate duly marked voltage danger and conventional skull and bones in signal red colour written in one local language and english with retro reflective stickering and fixing with GI/MS. clamps, bolts and nuts of approved size, for LT 440 volts all as specified. |
| 78 | All as per item no 64 above but forHT 11000 volts. |
| 79 | M&L for fixing the Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed. |
| 80 | Material and labour for locating UG cable fault through high voltage UG cable testing van through TSSPDCL or any authorised service provider in HT cables of any size or distance complete all as specified and directed to the entire satisfaction of Engr-in-Charge. |
| 81 | Material and labour for tracing the cable route using ultra sonic cable route locator of any HT/LT UG cables complete all as specified and directed. |
| 82 | Supply and fixing rectangular RCC cable route indicator of size not less than 1m long with curved on top surface duly marking with size of cable, location including painting with two coats of synthetic enamel paint on surface directed. |
| 83 | M&L for fabricating feeder distribution layout board on ACP sheet of thickness 3mm and size as required at site designing the layout as per the sketch provided by the Engr-in-charge using ecosolvent print including lamination and fixing to the wall using necessary fixing nuts, bolts and spares as required at site. The job includes removing of old layout board from its position complete all as specified and directed. |
| 84 | S&F/lay GI earth wire 4 mm dia on walls/flooras earth continuity conductor connected to DBs/ panels etc. |
| 85 | S&F in repairs MS chequered plate of 6 mm thick confirming to FE 290 grade 165 including provision of lifting handle for each plate on existing cable ducts and manhole covers for semi under ground sumps including painting with two coats of synthetic enamel paint over a coat of red oxide primer all complete all as directed. |
| 86 | Supply only Male contacts suitable for 33/11 KV Air Break switch complete all as directed. |
| 87 | Supply only Female contacts suitable for 33/11 KV Air Break switch complete all as directed. |
| 88 | Material and Labour for cutting existing BT road/PCC of size 45cm x 60cmfor taking out/laying of underground cable and including necessary earth work and refilling the same in layers well ramming including watering as required and matching with the existing surface with 200mm thick PCC 1:2:4 type B1 and curing the same with wet gunny bagsand removing debris to a distance not less than 50m completeall as specified and directed. |
| 89 | Supply and lay GI tubing 100mm dia, light grade for cable protection at road crossing/on poles and tubing sealed at bith ends after laying the cables including taking out old GI tubing complete all as directed. |
| 90 | All as per iem No 76 here-in-before but 80mm diaMake for item Nos.76 &77: ZENITH/ TATA/ JINDAL/SWASTIC |
| 91 | S&F in repairs MCCB 200 Amps, 4 pole 50 HZ, complete all as directed. |
| 92 | S&F in repairs MCCB 100 Amps, 4 pole 50 HZ, complete all as directed. |
| 93 | S&F in repairs MCCB 125 Amps, 4 pole 50 HZ, complete all as directed. |
| 94 | S&F in repairs MCCB 400 Amps, FP, 50HZ, complete all as directed. |
| 95 | S&F in repairs MCCB 630 Amps, 4 pole 50 HZ, complete all as directed.Note for item No. 81 to 82: Cost of fixing on to walls/surface on suitable angle iron bracket support and civil work shall be included quoted rate. |
| 96 | S&F in replacment MCCB enclosure ofsuitable size for MCCBs 4P upto 250Amps capacity of existing size complete all as directed. |
| 97 | S&F in replacment MCCB enclosure ofsuitable size for MCCBs 4P 400/630Amps capacityof existing size complete all as directed. |
| 98 | Replacement of air breather ofany type up to 5MVA transformer complete with filled silica gel complete all as directed. |
| 99 | Disconnection of all Primary/Secondary connection of the defective transformer of any KV rating, out door / indoor any make taking down / out from plinth / pole / platform with the help of crane and transporting the same carefully to workshop for repairand bringing back and install, with all connections as per directions, after repair to its existing position, upto 5MVA capacity of transformer complete with testing and commissioning, complete all as directed. |
| 100 | Opening of the 11 KV / 0.433 KV transformer upto 500 KVA by removing the inspection cover / top cover, decanning of the transformer oil up to the required level for replacement of leaked cork sealwith insulator or LT/HT bush (which is unsv) complete from the shell and making again connections of LT/HT bush to avoid leakage of oil refilling back to existing oil into the transformertesting & commissioning complete all as directed Note : HT/LT bush will measured and paid separately under relevant item and cork sealwith insulator is deemed to be included in quoted rate. |
| 101 | M&L for opening the top of Transformer upto 5000KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level and testing the transformer complete all as directed. |
| 102 | Supply & fixing of air termination single pointed copper rod 12mm dia and 300 mm long including removal of the existing and complete all as directed |
| 103 | S& F Aluminium strip 25 x 3 mm with saddles and fixing screws etc for roof conductors and down conductors above ground including removal of existing and complete all as directed |
| 104 | M&L for Renewal of Fuse wire by using appropriate amp rating tinned copper fuse wire with all safety precaution like hand gloves Earth rod at site of any height of six/four/two pole structure all as directed. |
| 105 | Supplying only Tinned Copper fuse wire of16SWG to 22 SWG or 30 Amps to 200 Amps capacity . |
| 106 | S&F in repairs for Test pointterminal block made out of gun metal or phosphorus bronzed size 75x75x25mm, drilled and screwed including 03 Nos 8mm dia 25mm long hexagonal head screw all as specified and as directed. |
| 107 | S&F in repairs for GI pipe light grade 50 mm bore , 1.2 mtr long duly threaded on both side for fixing GI socket & making necessary arragement for holding of air terminal rod all as specified & directed |
| 108 | M&L for opening the top of Transformer upto 625 KVA for renewal of jumpering (with brazing or welding) with new copper wire of existing size after removal of burnt out jumpering including decanning of oil upto required level for completing the workand testing the tranformercomplete all as directed. |
| 109 | Supply and fixing of HT bushing including metal parts and washer complete for any make of plinth/pole mounted transformer upto 5000KVA capacity complete all as directed. |
| 110 | Supply and fixing of LT rod / studs for upto 5000 KVA capacity KVA transformer made of brass with nuts and washers, Insulator and fittings etc as per size and shape of original complete all as directed. |
| 111 | M&L for replacement of Aluminium conductor, steel reinforced,Weasel typecomplete all as directed. |
| 112 | Supply and fixing of HT bushing including metal parts and washer complete for any make of plinth/pole mounted transformer up to 5 MVA capacity complete all as directed. |
| 113 | Supply and fixing of LT rod / studs for up to 5 MVAA transformer made of brass with nuts and washers, Insulator and fittings etc as per size and shape of original complete all as directed. |
| 114 | M&L Pin type, porcelain, vitreous, white,brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50mmheight, 65/100mm dia for 550 volts grade complete all as directed. |
| 115 | Supply and fixing in repairspost top porcelain insulator vitreous brown with GI clamp, nuts, bolts etc suitable for 11000 Volts grade working pressure complete all as directed. |
| 116 | M&L inreplacementof Shackle Type insulator 1100V 100mm hight 115 mm dia same as per existing complete. |
| 117 | M&L in replacement of analog type Winding temperature indicator, 50-60 HZ, 110-220 V IP 48 temperature 0-160 degree mild steel body andindicator for oil/ temperature for any type/size /capacity transformer all as specified and as directed |
| 118 | M&L in replacement of analog type Oil tempreture indicator, 50-60 HZ,110-220 V IP 48 temperature 0-160 degree mild steel body andindicator for oil/ temperature or any type/size /capacity transformer all as specified and as directed |
| 119 | M&L in replacement of Mog Magnetic oil level indicator,of aluminium body, industrial use of size 1500mm, temperature indication upto 30 DC , works on max pressure 4Kg/sqcm accuracy 95% completefor any type/size /capacity transformer all as specified and directed |
| 120 | M&L in replacement of buchholz relay/gas operative relayof existing size and shape all as specified and as directed |
| 121 | M&L for Charcoal dust/breeze to fill in existing earthing pit to recharge the pit |
| 122 | M&L for common salt to fill in existing earthing pit to recharge the pit |
| 123 | M&L for 2 core round flexicopper wire of 1sqmm dia for AC/DC supply connections to VCBs/SF6 with suitable size glands and insulated lugs of required qty complete all as directed. |
| 124 | Supply, Lay & Test & Commissioning cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes round flex control cable of size 12 core 1.5 Sq mm.VCBs/SF6 with suitable size glands and insulated lugs of required qty complete all as directed. |
| 125 | M&l in replacement of analog type winding temperature indicator/ Oil temperature indicator , 50-60Hz, 110-220V, IP 48 tempreture 0-160 degree mild steel body and indicator for oil/tempreture for any type/size /capacity tranformer all as specified and directed. |
| 126 | Supply, erect, Testing & Commissioning of numerical protection relay relay Model Micom P127,complete control wiring with material, Programming/setting/calibration including softwareof relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay.Make- Schneider or Techno Commercially equivalent ABB/L&T/Semiens |
| 127 | Supply, erect, Testing & Commissioning of numerical protection relay relay Model Micom P 122,complete control wiring with material, Programming/setting/calibration including softwareof relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay.Make- Schneider or Techno Commercially equivalent ABB/L&T/Semiens |
| 128 | Supply, erect, Testing & Commissioning of VAA Auxilaryrelay Alstom Model VAA11,22,33,21,3123 , 110V complete control wiring with material, Programming/setting/calibration including softwareof relays required and necessary addition/alternation of panel alongwith dismantling of old unserviceable old type of relay.Make- ALSTOM or eqiuvalent |
| 129 | M&Lfor replacement of UNSV push button of existing size in breakers/panelscomplete all as directed. |
| 130 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in soft loose soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as directed. |
| 131 | Returning, filling in, including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick using soil complete all as directed. |
| 132 | Removing excavated surplussoil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed. |
| 133 | Supply and spreading of natural, clean, dry, river sand in trenches for cable protection / transformer yard/ two pole structure yardcomplete all as directed.Note:- Punned thickness only shall be measured for payment purpose. |
| 134 | Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1 with peak, size300mm x 180mm x 40mmcomplete all as directed. |
| 135 | Making Primery/Secondary coil with insulating copper wire of required gauge, craft paper cotton tape HT/LT insulation as per specification of old transformerup to 5000 KVA including making of coil as required of various capacity of transformer complete all as directed . |
| 136 | Reconditioning of over heated 33/11 KV coil of transformer from to up to 5000 KVA after removing all old insulation any type and re-insulation as required and remaking of coils complete all as directed . |
| 137 | M & L for Inspection and servicing of OLTC of transformer of capacity 1.5 MVA and checking the electrical/manual operation of tap changer mechanism, check the integrity of the active components /contact surface mating for all tap positions, voltage ratio test for all tap position etcincluding cleaning of theOLTC complete all as directed.Note : The Contrator shall be responsible for correct servicing of the OLTC and servicing to be done through OEM of OLTC. |
| 138 | Supply and fix wiring and commissioning including thormostate switch space heater 200w for VCB/SF6 breaker/RMU complete all as directed. |
| 139 | Supply and fix TNC switch /Ammeter/Voltmeter/digital with selector switch complete all as directed. |
| 140 | Servicing of capacitor bank 200 KVAR, 12 KV, 3 Ph Dry Type Series Reactor and checking of capacitance of capacitor including control & power wiring, barrel fuses cleaning of spare parts including testing of relay & contactor, tightening of nuts/bolts etcafter taking shutdown as per electrical safety norms complete all as directedNote: Spares costing upto 1500.00 shall be deemed to be included the in quoted rate. |
| 141 | S&F in repairs Silica gel complete all as directed. |