| 1 | SITCofIP403polecurrentlimitingMouldedcasecircuit breaker(MCCB)madeofflameretardent&heatresistant materialhaving following current rating, short circuit breaking capacityat 440/415 V, 50 Hz; O/L & S/C settings as perPWDspecificationforelectricalWorks,conformingto IS/IEC60947P-2:2003withfront faceandcentralised adjustable, trip free mechanisum, true contact position indicator, lineloadinterchangeability, designedforboth horizontal&verticalmountingwithoutanyadverseeffect onelectricalperformance,suitableforoperationupto55 degreeandwithoutderatingupto40degree, pollution degree 3, having positive isolation capability, push(test) to trip, trip time less then 10 ms under s/c condition, Breaking capacityIcs=100%Icu.Uimp=8KV,ratedinsulation voltage800V,provisionforUVR,shunttrip,earthfault trip,doorinterlock,padlock&rotaryhandle,including making connections with lugs & spreaders,etc. as required. OEM shall have submitNABL / CPRI / ERDA accrediated lab type test certificate before execution. All as per pre approvedbyEngineerincharge. Foradditionaltechnical parameters of products/ work, refer Annexure \"A\" attached with this BSR .(PWD Electric BSR Rajasthan 2021/ E090300) |
| 2 | up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 3 | up to 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 4 | up to 160 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 5 | up to 200 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 6 | up to 250 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu |
| 7 | Providing&Fixingof240/415VACMCBwithpositiveisolationofbreakingcapacitynotlessthan10KA(B/C tripping characteristic as per type of load andsite requirement) 4KV impulse withstand voltage,as per PWD specification for electrical Works with ISI marked IS 8828(1996) / conforming to IEC 60898-1 2002, IEC 60947-2, lowwattlosses,tripfreemechanisum,energylimiting of class 3 as per IEC,minimum phase termination capacity of 35sq.mm.,conductorlineloadreversibility,labelholding facility,IP20contactprotectionandfittedwith existing distribution board/sheets, min. operation 20,000 upto 32 A rating and 10,000 upto 63 A, 5000 for 80 A ratingincluding makingconnections,testingetc.asrequired. .OEMshall havesubmit NABL/CPRI/ERDAaccrediatedlabtest reports beforeexecution&Allasperpreapprovedby Engineer in charge.For additional technical parameters of products/work ,referAnnexure\"A\"attachedwiththisFour ole MCB(PWD Electric BSR Rajasthan 2021/ E090300) |
| 8 | 6A to 32 A rating |
| 9 | 40 A rating |
| 10 | 50-63 Arating |
| 11 | SF of110/220 V, LED (22.5 mm dia ) Indicatinglamp with integral circuit, terminal block, including connection etc. as required.Red/yellow/Green colour |
| 12 | SF of (0-500) V range Volt meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Analog type ( 96 mm x 96 mm ) |
| 13 | SF of CT operated direct reading typeAmpere meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Analog type Below 500 A |
| 14 | SF ofCurrent Transformer, with all necessary support in existing panel including connection etc. as required . up to 150 / 5 Ratio , 5 VA , class 1 accuracy |
| 15 | SF of selector switch of 10 A for voltmeter (4 position ) including making connection etc.as required . |
| 16 | SF of CT linked selector switch of 10 AforAmpere meter (4 position ) including making connection etc.as required . |
| 17 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existingsurface or recessed conduit/casing capping including making connections etc. as required. |
| 18 | 1 x 2.5 sq.mm |
| 19 | 2 x 2.5 sq. mm. + 1x1.5sqmm |
| 20 | 1 x 10.0 sq.mm |
| 21 | P&F 240/415 V porcelain kitkat fuse (/HBC type) conforming to IS:2086,1983 0n existing board/ sheet including making connections with lugs, testing etc. as required. 100 A ,415 V |
| 22 | Supply and fixing of oil / Air breakDOL/ Star DeltaStartermade out of sheet steelpowder coated enclosure withsingle phasing protection, ON / OFFpush buttons,etc. complete in all respect suitable for following rating motors. Fully Automatic Star/ DeltaStarter |
| 23 | 20.0 HP to 25.0 HP |
| 24 | 30.0 HP to 35.0 HP |
| 25 | Supplying and makingend termination with heavy Copperlugs ( Pin / ring type ) duly crimped with crimping tool, PVC tape etc of following size. 25.0 Sq.mm |
| 26 | Providing&LayingP.V.C. /XLPEinsulated&P.V.C.sheathedUn-armoured/Armouredcoppercableof1.1KVgradeasperPWDspecificationforelectrical Works inexistingRCC/Hume/Stoneware/PVC pipe/ open duct/cable trench with filling of excavated earth in trench, on existing cable trays or on surface etc. includingmakingnecessaryconnection,testing etc. as required of size andas per points Copperconductorofelectrlyticgradecopper,purity>99.97%ISImarkedasperIS:1554P-I/IS:7098 P - I (PWD Electric BSR Rajasthan 2021/E110200) |
| 27 | 16Sq.mm 1 core flat / Round |
| 28 | 25 Sq.mm 1 core flat / Round |
| 29 | 2.5 Sq.mm 3 core flat / Round |
| 30 | 4.0 Sq.mm 3 core flat / Round |
| 31 | 6.0 Sq.mm 3 core flat / Round |
| 32 | Providing&FixingofACoperatedheavyduty230/440VoltpowercontactorasperPWDspecificationforelectricalWorks,ISImarkedIS/IEC60947-4-1:2000havingprovisionofmechanicalinterlocking,auxilarycontacts,Dinrailmountingtypeincludingmakingconnections,testingetc.asrequired.AllasperpreapprovedbyEngineerincharge.Foradditionaltechnicalparametersofproducts/work,referAnnexure \"A\" attached with this BSR 3 pole Power contactors with following AC 3 Rating (PWD Electric BSR Rajasthan 2021/E081600) |
| 33 | Up to 12 Amp |
| 34 | 13 to 25 Amp |
| 35 | 32 Amp |
| 36 | 40 Amp |
| 37 | 50 Amp |
| 38 | 70 Amp |
| 39 | 80 Amp |
| 40 | Providing & Fixing ofthermal over load relay wuiilt inbsingle phaseprotection and having at least 1NO & 1NC contacts, manual /auto reset facility including making connection testing etc. as required.All as per pre approved by Engineer in charge.For additional technical parameters of products/ work, refer Annexure \"A\" attached with this BSR .(PWD Electric BSR Rajasthan 2021/E081700) |
| 41 | Up to 14 Amp |
| 42 | 14 to 23 Amp |
| 43 | 20 to 33 Amp |
| 44 | 24 to 40 Amp |
| 45 | 36 to 60 Amp |
| 46 | 45 to 75 Amp |
| 47 | 66 to 110 Amp |
| 48 | Providing&FixingofselfhealingIP20MPPthyupnets capacitor(banks)asperPWDspecificationforelectricalWorks,ISImarked IS:13340-41/conformingtoIEC:831-1&2ORIEC:60831-1&2in existingpanelorparallelwithloadterminals,thecapacitorshallbe fitted with discharge resistors, pressure sensitive disconnector ( PSD ) andshallhavedissipationfactorlessthan0.0025at50Hzandtotal wattage loss less than 0.35 Watt per KVAR. Min over current capacity1.8 times rated current & peak inrush current min. 250 times of rated current,including making connections, testing etc. as required. All as perpreapprovedbyEngineerincharge. Foradditionaltechnical parameters of products/ work, refer Annexure \"A\" attached with this BSR . (PWD Electric BSR Rajasthan 2021/E081600) Heavy dutyThree phase 480 V, 50 Hzcylindrical capacitor (Bank) |
| 49 | Labour charges for removing electric fault in wiring / making connection through lugs (with the help of cramping tool) of motor pump set with starter atheadworks of water supply scheme/Tubewell/ openwell including cost of insulation tape etc. (O&MBSR/Churu/2019/6.1) |
| 50 | Labour charges for repairing of starter at site including opening and reassembling of starter with labour charges for replacing of defective parts with new one at site.(Parts will be supplied by Depatment)(O&MBSR/Churu/2019/6.3) |
| 51 | 5 to 100 HP. (O&MBSR/Churu/2019/6.3.1) |
| 52 | 101 to 150 HP. (O&MBSR/Churu/2019/6.3.2) |
| 53 | Supply & filling starter oil in oil immersed starters at site. |