Tender For Running & Maintenance Of E.I. Services In Non- Residential Area At Gtb Hospital Complex, Shahdara, Delhi. ( Sh: Supply Installation Testing Commissioning Of Starter Panel & Exhaust Fans, Servicing And Cleaning Of Exhaust System Install, delhi-Delhi

Public Works Department-PWD has published Tender For Running & Maintenance Of E.I. Services In Non- Residential Area At Gtb Hospital Complex, Shahdara, Delhi. ( Sh: Supply Installation Testing Commissioning Of Starter Panel & Exhaust Fans, Servicing And Cleaning Of Exhaust System Install. Submission Date for this Tender is 03-05-2023. Starter Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

37391057
Tender For Running & Maintenance Of E.I. Services In Non- Residential Area At Gtb Hospital Complex, Shahdara, Delhi. ( Sh: Supply Installation Testing Commissioning Of Starter Panel & Exhaust Fans, Servicing And Cleaning Of Exhaust System Install
Open Tender
Indian
Delhi
delhi
03-05-2023

Tender Details

Running & Maintenance Of E.I. Services In Non- Residential Area At Gtb Hospital Complex, Shahdara, Delhi. ( Sh: Supply Installation Testing Commissioning Of Starter Panel & Exhaust Fans, Servicing And Cleaning Of Exhaust System Installed At Kitchen Of Old Building & Boys Hostel. )

Key Value

Document Fees
Refer document
EMD
INR 11899.0 /-
Tender Value
INR 5.94 Lakhs /-

BOQ Items

Name of Work: Running & Maintenance of E.I. services in non- residential area at GTB Hospital complex, Shahdara, Delhi. (SH: SITC of Starter Panel & Exhaust fans, Servicing and cleaning of exhaust system installed at Kitchen of old building & Boys Hostel.)
Sl. No. Item Description
1(a) Removing servicing, cleaning of kitchen chimney Air filter cleaning with help of detergent scrap Patti etc.(Approx. of 10" length) Reinstalled the same complete as required. - 3 Nos. (b) Dismantling, servicing, cleaning, oiling & greasing 5Hp induction motor from kitchen chimney with help of scaffolding from height of 15 feet re-installation the same complete etc. as required. - 3 Nos. (c) Dismantling, servicing, cleaning, oiling & greasing of existing 18"/24" Exhaust fan, re-installation complete as required. - 6 nos. (d) Dismantling of 24" co-axial fan installed at kitchen from height of 15", testing & re-installation complete as required. - 3 Nos.
2Supply & fixing of 20"/24" aluminium blade for axial flow fan etc as required.
3SITC of 1 HP, Three phase Axia Flow Fan having 1440 RPM, 415V ±5%, 50 Hz etc as required.
4SITC of Motor Starter capacity 2.4-3.8 A (with Auto Switch) Three phase suitable for 1 HP with 20 A rating, etc complete as required.
5Supplying & fixing of 3 Core 2.50 Sqmm PVC insulated PVC sheathed round copper cable etc. complete as reqd.
6Supplying, installation, testing & commissioning of cubical type LT panel suitable for 415V, 3phase 4 wire 50Hz AC supply system having Front surface suitable for fabricated in compartmentalized (preferably) design from CRCA sheet steel of 2mm thick upto 350 mm deep i/c cleaning & finishing with 7 tank process for powder coating in approved shade, having 1250 Amp capacity four strip aluminum alloy bus bars of high conductivity, DMC/ SMC bus bars of high conductivity bus bar supports, with short circuit withstand capacity of31 MVAfor 1sec, bottom base channel of MSsection not less than 100mm x 50mm x 5mm thick, entire panel shall have a copper earth bus bar of size 25mm x 5 mm at rearwith 2 nos earth stud, solid connections from main bus bar to switch gears with required size of Aluminium Bus bar and control wiring with 2.5sqmm PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half knock outs for cable glands of suitable size complete etc as required. Incoming: 100 A TP MCCB- 1 No. with with spreader link i/c Rotary Handle Basic Multifunction meter Measurement of V,A,F, PF, KW, old energy, accuracy class 1.0-0.5 -1 No. LED Phase indicating light for RYB with 6A control MCB-1 No. Bus Bar: TPN aluminium extensible type main bus bars of minimum of 250 Amp capacity with heat shrinkable colored sleeves and i/c DMC/SMC bus bars supports at required intervals complete for cross section, size supports & their spacing etc. OUTGOING: 3 Phase DOL Starter with pushbutton & thermal overload relay protection a) 5 HP 3 Phase DOL Starter - 4 Nos. b) 1 HP 3 Phase DOL Starter - 4 Nos. c) 5 HP Single Phase DOL Starter - 1No., for submersible motor
7Supplying, laying & fixing of size 3x6 Sqmm PVC insulated and PVC sheathed/XLPE Copper Armoured power cable of 1.1 KV grade on Surface of wall/ trench etc complete as required. [Make: Polycab]
8Supplying & fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) a) 4 way (4 + 12), Double door
9Supplying and fixing of following ways surface/ recess mounting, vertical type, 415V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note: Vertical type MCB TPDB is normally used where 3 phase outlets are required.) a) 4 way (4 + 12), Double door
10Supplying & fixing 5A to 32A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing & commissioning etc. as required. A) a) Single pole
11b) TriplePole
12Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board i/c drilling holes in cubicle panel, making connections, etc. as required. a) 100 A, 16 kA, TPMCCB
13Supplying & making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 kV grade as required. A) 3½ X 25 sq. mm ( 28 mm)
14Supplying, laying & fixing of size 3.5x25 Sqmm PVC insulated & PVC sheathed/XLPE Armoured Aluminium power cable of 1.1 KV grade on Surface of wall/ trench etc complete as required. [Make: Polycab]
15Credit of old exhaust fan 1 HP
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail