| 1 | Part A |
| 2 | Data collection, Baseline Survey and Studies, Designs, preparation of drawings, technical report and installation methodology as per provision of norms & JJM guidelines for sensor based measurement & Monitoring system and drinking water source security and sustainability. |
| 3 | Supply, Installation, Development, Testing & Commissioning of Web-based IOT/ SCADA System Required tags IOT/ SCADA Software along with O&M for 5 years (Compatible for 2 times nos. of water supply scheme)USB License KeyWeb enable – Unlimited UsersMobile ApplicationAPI (Application Programming Interface) SoftwareReport generation software24 Months SIM Card charges for data transmission. |
| 4 | Part B |
| 5 | Survey, Design, Supply, Installation, Testing & Commissioning of Soft starter based starter panel with GSM/GPRS based PLC / RTU System with appropriate gateway/ Edge device, pump protection, Energy sensor to enable remote/ Automated operation of pumps.Enclosure-1.6 mm CRCA sheet, wall mounted, single door, bottom front side cable entry point, Siemens grey 7035 color Soft Starter- Thyrister based, 415 V, 3phase, Acceleration-deceleration soft control, Inbuilt bypass contactor MCCB-Suitable rating MCCB, 36 KA, thermal magnetic based GSM/GPRS Module (RTU/PLC)-Web connected GSM/GPRS module, 5-30 V DC Input, Inbuilt DI-10 Nos., DO-6 Nos., AI-8 Nos., Pulse-1 No., Comm.- Modbus/ Eth.Meter-Multifunction energy meter with Modbus comm. able to monitor electrical parameters (Voltage, Current, Frequency, Power factor, KWH)HRC Fuses, Indication Lamps, Auto/manual selector switch, Start/Stop Push Button, Control Relays, CT\"s (15 VA resin cast), PT (250 VA, 415/220-110 V), Panel Light, Door Limit Switch, Suitable size copper cable, Other panel accessories-Thimble, connector, lugs, tie, striper, terminal blocks, etc and also install 22\" display screen at each water works. |
| 6 | 15 Kw / 20 Hp or as per site requirement |
| 7 | Supply, Installation, Testing & Commissioning of Battery powered IoT enabled mechanical type water Flow Meter(woltsman flow meter).Size range : 40 To 500 MM(1½” To 20”) Temp Range : 0°C to 45°C.Accuracy Class :Class B (±2 % @ Nominal flow rate)Product Standard : ISO-4064/IS-2373.Body Material cum Standard : IS-210 Gr. …Dial Details : Magnetic Drive, Extra Dry Dial.Protection Class : IP-68.Cable Length – 10 MeterMeasuring Tube – SS 304Accessories – Flanges, Tail Piece, DI Joints, Expander, Reducer, Rubber sheets, Nut-bolts, etc. complete in all respect. |
| 8 | Size (75 mm to 150 mm) as per site requirement |
| 9 | Supply, Installation, Testing & Commissioning of Float switch & Water Level transmitter along with auto trigger for switch On & Off the pump according to the level of OHSR (For OHSR) Ingress Protection – IP 66, Measuring range – Up to 20 M, Process temp.- -40 to 60 deg. C,Full PVDF Body – For a long sensor lifetime |
| 10 | Supply, Installation, Testing & Commissioning of Residual Chlorine Sensor with RTU to be installed at tail end including solar power battery system or any other electronic equipment along with its installation complete in all respect as per specifications |
| 11 | Measuring principle – Free Chlorine for Drinking water Measurement range – 0 to 5 mg/l HOCL |
| 12 | Supply, Installation, Testing & Commissioning of Wafer type Butterfly Valve with Electrical actuatorBody Material - CI/DI |
| 13 | Pressure Rating – PN16 Feedback - 100% Open & 100% close |
| 14 | size (80 mm to 150 mm) as per site requirement |
| 15 | Supply, Installation, Testing & Commissioning of Wafer type Butterfly Valve with Electrical actuatorBody Material - CI/DI |
| 16 | For Distribution line of Overhead Tanks |
| 17 | Pressure Rating – PN16 Feedback - 100% Open & 100% close |
| 18 | size (80 mm to 150 mm) as per site requirement |
| 19 | Supply, Installation, Testing & Commissioning of Pressure Transmitter |
| 20 | Measuring range – 10 kg/cm2 Output – 4 to 20 mA Aux Supply – 24 V DC |
| 21 | Supply, Installation, testing & Commissioning of Hydrostatic Depth Sensor (for determining spring level odf T/W ) |
| 22 | Measuring range – 50 Meter Output – 4 to 20 mA Aux. supply – 24 V DC |
| 23 | PART - C (Maintenance) |
| 24 | Operation and maintenance for each scheme per annum including all taxes and labour cess charges Complete Job. |
| 25 | For 1st year after completion of 3 months DLP @ 4.50% of Part-B |
| 26 | For 2nd year after completion of 1 year O&M @ 4.75% of Part-B |
| 27 | For 3rd year after completion of 2 year O&M @ 5.00% of Part-B |