Tender For Electrification Work Of 1 No. Washing Plant And Other Allied Work At Dtc Nehru Place Depot, Delhi-Delhi

Delhi Transport Corporation has published Tender For Electrification Work Of 1 No. Washing Plant And Other Allied Work At Dtc Nehru Place Depot. Submission Date for this Tender is 17-04-2023. Industrial Process Machinery and Equipments Tenders in Delhi Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

37138492
Corrigendum : Tender For Electrification Work Of 1 No. Washing Plant And Other Allied Work At Dtc Nehru Place Depot
Open Tender
Indian
Delhi
Delhi
17-04-2023

Tender Details

Electrification Work Of 1 No. Washing Plant And Other Allied Work At Dtc Nehru Place Depot

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 13-Apr-2023 DateCorrigendum Date 17-04-2023

Key Value

Document Fees
Refer document
EMD
INR 7825.0 /-
Tender Value
INR 3.91 Lakhs /-

BOQ Items

Name of Work: Electrification work of 1 No. washing plant and other allied work at DTC Nehru Place Depot
Sl. No. Item Description
1Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
2Group C
3Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
4Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
5Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
62 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
7Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
8Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and15/16 A modular switch, connections etc. as required
9Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
10Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
11125 A, 16 kA,TPMCCB
12Supplying and fixing following way, single pole and neutral, sheetsteel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator)
136 way, Double door
14Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phaseoutlets are required.)
158 way (4 + 24), Double door
16Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
17Single pole
18Double pole
19Triple pole
20Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A, “C” curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
21Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
22Supplying and laying 25 mm X 5 mm G.I strip at 0.50 meter below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm)
23Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
24Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size on wall surface as required.
25Up to 35 sq. mm (clamped with 1mm thick saddle)
26Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
272 X 16 sq. mm (22mm)
284 X 25 sq. mm (28mm)
29S/I/T/C of outdoor type feeder pillar, metal clad, suitable for 415 volt, 3 phase, 50 Hz with suitable foundation and arrangement for incoming / outgoing cabling/cable termination, earthing, locking arrangement, insulated aluminium bus-bar system, interconnection etc.( As per fig. 2 of CPWD Electrical Specification) with provision of phase indicating lamps, voltmeter/ammeter with selector switch on the incoming side. Incoming : 250A TPN MCCB, 50 KA BC1 No Outgoing : 100A TPN MCCB, 25 KA BC6 Nos.
30Supply of XPLE insulated PVC sheathed AL conductor cable 1.1 KV grade conforming to IS-7098 of size 4X25 sq. mm.
31Supply of XPLE insulated PVC sheathed Armoured AL conductor cable 1.1 KV grade conforming to IS-7098 of size 2X16 sq. mm.
32Supplying & fixing of LED flood light fittings 1X100 WattIP - 66
33S/I/T/C of complete LED Tube fitting 20 watt
34S/I/T/C of 48"" Ceiling fan High Speed
35Rate (DSR-2016 + Add prevailing cost index @ 22.69% On DSR-2016 rate)
36Rate -@ 9.5% below on DSR-2016+Add prevailing cost index @ 22.69%
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail